CURRYCONTROLS.COMControls & Automation Knowledge Hub

Electrical

Wire Gauge, Circular Mils, and Area

Circular mil area and approximate insulated cross-sectional area for AWG and kcmil conductor sizes.

Source of these values

Circular mil values are the standard AWG geometric definitions. Insulated areas are the approximate values commonly published for THHN and THWN-2 in NFPA 70 Chapter 9 Table 5.

SizeCircular milsTHHN area, sq inRelative area
144,1100.00970.6x of 12 AWG
126,5300.01331.0x of 12 AWG
1010,3800.02111.6x of 12 AWG
816,5100.03662.5x of 12 AWG
626,2400.05074.0x of 12 AWG
441,7400.08246.4x of 12 AWG
352,6200.09738.1x of 12 AWG
266,3600.115810.2x of 12 AWG
183,6900.156212.8x of 12 AWG
1/0105,6000.185516.2x of 12 AWG
2/0133,1000.222320.4x of 12 AWG
3/0167,8000.267925.7x of 12 AWG
4/0211,6000.323732.4x of 12 AWG
250 kcmil250,0000.397038.3x of 12 AWG
300 kcmil300,0000.460845.9x of 12 AWG
350 kcmil350,0000.524253.6x of 12 AWG
400 kcmil400,0000.586361.3x of 12 AWG
500 kcmil500,0000.707376.6x of 12 AWG
600 kcmil600,0000.867691.9x of 12 AWG
750 kcmil750,0001.0496114.9x of 12 AWG
1000 kcmil1,000,0001.3478153.1x of 12 AWG

In short

Circular mils express conductor cross-sectional area and are the basis of the voltage drop formula. A 12 AWG conductor is 6,530 circular mils, 4/0 AWG is 211,600, and one kcmil is 1,000 circular mils. Each three AWG sizes roughly doubles the area.

Notes and limits

  • Insulated areas here are for THHN and THWN-2. The insulated conductor area table lists XHHW, TW, THW and RHW alongside, and using the wrong one changes a conduit fill result.
  • Circular mils are used directly in the voltage drop formula. Doubling the circular mils halves the voltage drop at the same current and distance.