Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub

Instrumentation

4-20 mA Signal Reference

Current, percent of span, and voltage across a 250 ohm input for a 4-20 mA loop, including the NAMUR fault thresholds.

Source of these values

Arithmetic relationships of the 4-20 mA standard, with fault thresholds from NAMUR NE 43.

CurrentPercent of spanVolts across 250 ohmMeaning
0 mA0.00 VOpen loop: broken conductor, dead supply, or failed transmitter
3.6 mA-2.5%0.90 VNAMUR NE 43 low fault threshold
3.8 mA-1.25%0.95 VBelow range, often a slightly under-ranged calibration
4 mA0%1.00 VBottom of the calibrated range
8 mA25%2.00 V
12 mA50%3.00 VMidpoint. The check that catches span errors.
16 mA75%4.00 V
20 mA100%5.00 VTop of the calibrated range
20.5 mA103%5.13 VAbove range but still measuring on many transmitters
21 mA106%5.25 VNAMUR NE 43 high fault threshold
22 mA112.5%5.50 VTypical maximum a transmitter will drive

In short

In a 4-20 mA loop, 4 mA is 0% of span and 20 mA is 100%. Across a 250 ohm input this becomes 1 to 5 volts. Under NAMUR NE 43, a reading below 3.6 mA or above 21 mA indicates a device fault rather than a process value.

Notes and limits

  • The 4 mA live zero is what makes a broken conductor detectable. At 0 mA the loop is open; a 0-20 mA scheme cannot tell that apart from a genuine zero reading.
  • Configure the fault direction deliberately. On a wet well level, failing low can make the controller think the well is empty and stop pumping while it fills.
  • HART communication generally requires a minimum loop resistance of about 230 ohms, which the standard 250 ohm input satisfies.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.