Electrical

Conduit Fill Calculator

Percentage fill for a raceway from conductor size, count, and insulation type, for EMT, RMC, IMC, PVC, ENT, and the flexible conduits, checked against the 53, 31, and 40 percent limits with the smallest trade size that fits.

Inputs

Applies to every conductor entered below.

Not every type is made in every size. The result says so if the pair does not exist.

Calculated reference results

Fill of 3/4 in EMT
10.0%

Limit for 4 conductors is 40%

Total conductor area, THHN, THWN, THWN-2
0.0532sq in
EMT 3/4 in internal area
0.533sq in

Internal diameter 0.824 in

Area available at the limit
0.2132sq in
Smallest EMT that fits
1/2 in

The arithmetic

  1. 4 x 12 THHN, THWN, THWN-2 at 0.0133 sq in = 0.0532 sq in
  2. Total conductor area = 0.0532 sq in
  3. EMT 3/4 in area = pi/4 x 0.824^2 = 0.533 sq in
  4. Fill = 0.0532 / 0.533 x 100 = 10.0%
  5. Limit for 4 conductors = 40%

What this does not account for

  • Every conductor entered is assumed to have the selected insulation. A raceway with mixed insulations must be summed by hand from Chapter 9 Table 5.
  • Fill is only one constraint. Conductor count also drives the ampacity adjustment factor, and a conduit that passes fill can still force conductors to be upsized.
  • Nipples not over 24 inches long are permitted 60% fill under Chapter 9 Note 4. That is not applied here.
  • Compact-stranded conductors use Table 5A, and multiconductor cables in a raceway use the cable dimensions. Neither is covered here.

How this is calculated

Conduit fill is the total cross-sectional area of the conductors divided by the internal area of the raceway. Chapter 9 Table 1 limits it to 53% for one conductor, 31% for two, and 40% for three or more. Conductor area depends on the insulation type and comes from Table 5; raceway area depends on the conduit type and comes from Table 4. Both are selected here rather than assumed, because a 12 AWG RHW conductor occupies nearly three times the area of a 12 AWG THHN.

Formulas

Fill % = (sum of conductor areas / raceway internal area) x 100

  • conductor area = pi/4 x (approximate diameter)^2, Chapter 9 Table 5
  • raceway internal area = pi/4 x (internal diameter)^2, Chapter 9 Table 4

Assumptions and limitations built into this calculator

  • Conductor areas are Chapter 9 Table 5 approximate dimensions for the selected insulation; the manufacturer data for a specific product may differ.
  • Raceway areas are Chapter 9 Table 4 internal dimensions for the selected conduit type.
  • Fill limits are Chapter 9 Table 1: 53% for one conductor, 31% for two, 40% for three or more.
  • Equipment grounding and bonding conductors count toward fill.

Frequently asked questions

Why does the insulation type matter so much?
Fill is measured by the space the insulated conductor occupies, not by the copper. THHN has a thin nylon jacket; RHW has thick rubber insulation plus a fibrous covering. At 12 AWG that is 0.0133 versus 0.0353 square inches, so a raceway that is fine for THHN can be badly overfilled with RHW.
Why is the limit 40% and not something higher?
The limits exist so conductors can be pulled without damage and so heat can escape. Chapter 9 Table 1 sets 53% for a single conductor, 31% for two, and 40% for three or more.
Does the equipment grounding conductor count toward fill?
Yes. Every conductor in the raceway counts toward fill, including grounding conductors, even though grounding conductors do not count toward the ampacity adjustment factor.
Why does the same trade size hold different amounts in different conduit types?
Trade size is nominal. The wall thickness differs by product, so the bore differs: half-inch Schedule 80 PVC has 0.217 square inches inside, half-inch EMT 0.304, and half-inch IMC 0.342.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.