Adjustment Factors for Conductor Count

Ampacity multipliers applied when more than three current-carrying conductors share a raceway or cable.

Source of these values

Values as commonly published for NFPA 70 Table 310.15(C)(1). Verify against your adopted edition.

Current-carrying conductorsAdjustment factorPercent
1 to 31.00100%
4 to 60.8080%
7 to 90.7070%
10 to 200.5050%
21 to 300.4545%
31 to 400.4040%
41 and above0.3535%

In short

When more than three current-carrying conductors share a raceway or cable, mutual heating reduces the ampacity of each. Four to six conductors are multiplied by 80%, seven to nine by 70%, ten to twenty by 50%, and the factor continues to fall as the count rises.

Notes and limits

  • Ungrounded conductors always count. Equipment grounding conductors do not.
  • A neutral carrying only the unbalanced current of a multiwire branch circuit generally does not count, but a neutral in a system with significant harmonic content does.
  • This factor and the ambient temperature correction factor both apply, multiplied together.