Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub

Electrical

Conduit Internal Area by Type and Trade Size

Internal cross-sectional area of EMT, ENT, FMC, IMC, LFMC, LFNC-B, RMC, and Schedule 40 and 80 PVC by trade size, the figure conduit fill is measured against.

Source of these values

Internal diameters as commonly published for NFPA 70 Chapter 9 Table 4. Areas are computed as pi/4 times the diameter squared, which is how the table itself is derived, and every value is checked at build time against a separately recorded copy of the published area. Fill percentages are from Chapter 9 Table 1. Verify against your adopted edition.

Trade sizeEMT, sq inENT, sq inFMC, sq inIMC, sq inLFMC, sq inLFNC-B, sq inRMC, sq inPVC Sch 80, sq inPVC Sch 40, sq in
3/8 in——0.116—0.1920.192———
1/2 in0.3040.2460.3170.3420.3140.3140.3140.2170.285
3/4 in0.5330.4540.5330.5860.5410.5410.5490.4090.508
1 in0.8640.7850.8170.9590.8730.8730.8870.6880.832
1-1/4 in1.4961.4101.2771.6471.5281.5281.5261.2371.453
1-1/2 in2.0361.9361.8582.2251.9811.9812.0711.7111.986
2 in3.3563.2053.2693.6313.2463.2463.4082.8743.291
2-1/2 in5.858—4.9095.1354.881—4.8664.1194.695
3 in8.846—7.0697.9227.475—7.4996.4427.268
3-1/2 in11.545—9.62110.5849.731—10.0108.6889.737
4 in14.753—12.56613.63112.692—12.88211.25812.554
5 in——————20.21217.85519.761
6 in——————29.15825.59828.567

In short

Conduit fill is measured against the raceway internal area from NFPA 70 Chapter 9 Table 4, and that area differs by conduit type at the same trade size. Half-inch EMT has 0.304 square inches, half-inch RMC 0.314, half-inch IMC 0.342, and half-inch Schedule 80 PVC only 0.217. The usable share is 53% for one conductor, 31% for two, and 40% for three or more.

Notes and limits

  • Values are the 100% internal area. Multiply by 0.53, 0.31, or 0.40 for the usable area with one, two, or three or more conductors, or use the conduit fill calculator, which does this and reports the smallest size that fits.
  • A dash means the raceway is not made in that trade size under its article.
  • A nipple not over 24 inches long is permitted 60% fill under Chapter 9 Note 4.
  • Every conductor counts toward fill, including equipment grounding conductors, even though grounding conductors do not count toward the ampacity adjustment factor.
  • EMT, ENT, FMC, IMC, LFMC, LFNC-B, RMC and PVC are governed by Articles 358, 362, 348, 342, 350, 356, 344 and 352 respectively.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.