Electrical

Conductor Ampacity Table

Allowable ampacity for copper and aluminum conductors at the 60, 75, and 90 degree C columns, for not more than three current-carrying conductors at 30 degrees C ambient.

Source of these values

Values as commonly published for NFPA 70 (National Electrical Code) Table 310.16. Reproduced for convenience. Verify against the edition adopted in your jurisdiction.

SizeCu 60 CCu 75 CCu 90 CAl 60 CAl 75 CAl 90 C
14152025———
12202530152025
10303540253035
8405055354045
6556575405055
4708595556575
385100115657585
2951151307590100
111013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
750 kcmil400475535320385435
1000 kcmil455545615375445500

In short

Allowable conductor ampacity depends on size, material, and insulation temperature rating. At the 75 degree C column, copper carries 25 amperes at 12 AWG, 35 at 10 AWG, 50 at 8 AWG, and 65 at 6 AWG. These figures assume not more than three current-carrying conductors in a raceway at a 30 degree C ambient, and correction and adjustment factors apply on top of them.

Notes and limits

  • Based on not more than three current-carrying conductors in a raceway, cable, or earth, at an ambient of 30 degrees C.
  • The ambient correction factor and the adjustment factor for more than three current-carrying conductors both apply on top of these figures.
  • The 90 degree C column is normally used only as a starting point for derating. Per 110.14(C), the finished ampacity cannot exceed the column matching the lowest-rated termination, which is commonly 60 or 75 degrees C.
  • 240.4(D) separately limits the overcurrent device for small conductors: 15 A for 14 AWG copper, 20 A for 12 AWG copper, and 30 A for 10 AWG copper, with limited exceptions.
  • This is the table for the general case. Other installation methods, such as conductors in free air, use different tables.

Direct contact