Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
TroubleshootingTroubleshootingInstrumentationLevelLift Stations

Level Reading Jumps

A level that steps, spikes, or flips to a fixed value while the water moves smoothly: the false echoes, foam, turbulence, condensation, cable faults, and controller-side causes behind each pattern, and how to tell them apart from the trend before opening a hatch.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

Symptom

The level trend shows steps, spikes, or sudden flips to a fixed value that the wet well or tank could not physically have done, while the pumps and the rest of the process behave normally between the jumps.

The short answer

Level Reading Jumps

A level reading that jumps while the actual level moves smoothly is a measurement artifact, and its shape identifies the cause. A jump to the same fixed value each time is a false echo from an obstruction on a radar or ultrasonic. Spikes that come and go with inflow are turbulence, splashing, or foam. Steps that coincide with a pump start are electrical noise or a ground loop. Dropouts to zero or full scale are a loose connection, a wet cable, or a lost echo. Trend the level at high resolution against the pump status and the pattern names the cause.

Key points

  • Trend it at one-second resolution with the pump status. The shape of the jump is the diagnosis.
  • A jump to the same fixed value every time is a false echo or a stuck reading, not the water.
  • Spikes that follow inflow or pump starts are turbulence, foam, noise, or a ground loop.
  • A dropout to 4 mA or 20 mA is a signal loss: connection, cable, echo, or transmitter fault.
  • Controller filtering hides the jumps and the pumps cycle on the wrong level. Find the cause instead.

Possible causes and what to check

Possible causeWhat to check
False echo from an obstructionRadar or ultrasonic: the reading flips to a fixed distance as the surface passes a pump, rail, cable, or the inflow pipe. Re-run the false echo mapping at low level.
Turbulence or splashing at the inflowSpikes during inflow surges; worse when the well is low and the inflow falls further. Relocate the sensor, add a stilling well or a baffle, or increase damping modestly.
Foam or floating debrisReading rises or becomes erratic when foam is present; ultrasonic and radar read the foam surface. Higher frequency radar, foam control, or a submersible transmitter as a second measurement.
Condensation on an ultrasonic transducerErratic readings in humid or cold conditions, often in the morning. A sunshade, a heated transducer, or radar.
Temperature gradient over an ultrasonicSlow drift and steps as the air warms; the speed of sound changes. Temperature compensation at the transducer; radar.
Electrical noise or ground loopSteps or spikes exactly at a pump or drive start. Check shield grounding, cable routing, and the loop for a second ground.
Loose terminal or damaged cableDropouts to zero or full scale, often when the cable moves or in wet weather. Inspect terminations and the cable in the well.
Submersible transmitter vent tube blockedA slow offset that changes with barometric pressure, and steps when the vent clears. Check the vent tube and the desiccant.
Submersible transmitter fouled or buriedReading stops responding or steps when the pump stirs the grit. Clean and raise the transmitter.
Controller filtering or scalingSteps that match the resolution of an integer scaling, or a filter that lets a spike through at the update rate. Check the raw value against the scaled one.
Wireless or network link droppingThe reading holds and then jumps to the current value when the link returns. Check the communication status and timestamps.

Read the trend first

A level measurement in a wet well is one of the noisiest signals in a utility, and the shape of the disturbance says more than any measurement at the panel. Pull a trend at the fastest resolution the historian has, overlay the pump run status and, if available, the inflow or a rain gauge, and look at when the jumps happen and what value they jump to.

Trend shapePoints toward
Flips to the same value every time, then returnsFalse echo from a fixed obstruction
Spikes upward during inflow surgesSplashing, turbulence at the inflow
Erratic reading that rises above the true levelFoam or a floating mat on the surface
Step or spike exactly at a pump or drive startElectrical noise or a ground loop
Dropout to 4 mA, 20 mA, or the failure currentSignal loss: connection, cable, lost echo, transmitter fault
Erratic in the early morning or in humid weatherCondensation on an ultrasonic transducer
Slow drift with steps as the day warmsTemperature effect on an ultrasonic; air temperature gradient in the well
Holds flat, then jumps to catch upCommunication link dropping; stale value
Steps of a fixed sizeInteger scaling resolution in the controller

Diagnostic procedure

  1. 1

    Confirm the water is not doing it

    A well with a large inflow surge really does jump a few inches. Compare the jump with what the inflow could produce and with a float or a second measurement if there is one.

  2. 2

    Match the pattern

    From the table. Most jumps fit one row, and the row says where to go.

  3. 3

    For a fixed-value flip, open the transmitter echo curve

    Radar and ultrasonic transmitters show their echo profile in the configuration tool. The false echo is visible as a peak at the distance the reading flips to. Re-map at low level, and check the mounting for a new obstruction: a cable, a rag on a rail, a float.

  4. 4

    For inflow spikes, look at the sensor position

    A sensor over the inflow stream or in the pump discharge turbulence reads the disturbance. Move it, add a stilling well or a baffle, or accept a modest increase in damping.

  5. 5

    For pump-start steps, check the electrical path

    Shield grounded at one end, cable separated from motor and drive conductors, a second ground on the transmitter or the shield. The ground loop diagnosis page covers the measurements.

  6. 6

    For dropouts, check the connections and the cable

    Terminations in the panel and the junction box, the cable where it enters the well and where it hangs, the transmitter connector. Flex the cable while watching the reading.

  7. 7

    For a submersible, check the vent and the sensor

    The vent tube must be open to the atmosphere through a dry desiccant; the sensor face must be clear of grit and rags and above the sludge.

  8. 8

    For a held value that jumps, check communications

    The communication status and the timestamp. A radio or network link that drops and recovers produces exactly this shape, and the fix is on the link.

  9. 9

    Fix and verify

    Correct the cause and watch the trend through several pump cycles, including an inflow event, before calling it done.

Choosing a better measurement

Some wells defeat a single sensor. Foam, grease mats, splashing inflow, and confined geometry can make radar, ultrasonic, and submersible pressure each unreliable in turn. The robust answer at such a station is two measurements of different types, a radar and a submersible transmitter, compared in the controller, with the floats as the third layer. The controller uses the one that is behaving, alarms the disagreement, and never lets one bad sensor run the pumps alone.

Frequently asked questions

Why does the level jump only when the well is nearly empty?
The obstruction or the disturbance is low in the well: a pump body, the inflow falling further when the level is low, or a submersible transmitter being stirred by the pump intake. Re-map at low level, move the sensor, or raise the stop setpoint slightly.
The radar was fine for years and now jumps. What changed?
Something new in the beam: a float cable, a rag caught on a rail, a pump replaced with a different profile, a new ladder. Look in the well from the hatch. The echo curve in the configuration tool shows the new reflection.
Can I just add deadband to the pump setpoints?
Deadband stops the pump from cycling on noise at the setpoint, and it is part of a good sequence. It does not fix a measurement that jumps a foot, and a deadband wide enough to cover that changes the station operation. Fix the measurement.
Should I replace the ultrasonic with a radar?
If the causes are condensation, temperature gradients, or vapor, yes; radar is largely immune to all three and has become the default for wet wells. If the cause is a false echo from an obstruction, a radar has the same problem and needs the same mapping.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.