4-20 mA Signal Is Unstable

An analog reading that will not settle. How to separate a genuine process swing from induced noise, a ground loop, or a loop running out of voltage.

8 min readUpdated Aug 23, 2026Published Apr 21, 2026By Eric Sullivan

Symptom

The analog value on the HMI moves continuously, jumps erratically, or wanders slowly without a corresponding change in the process.

The short answer

4-20 mA Signal Is Unstable

An unstable 4-20 mA reading is usually one of four things: a genuine process fluctuation, induced electrical noise from nearby drives or motors, a ground loop from the circuit being earthed at more than one point, or insufficient loop voltage for the total loop resistance. Determine which by observing whether the instability correlates with equipment operation and whether it appears at the transmitter or only at the panel.

Key points

  • First establish whether the process itself is actually moving.
  • Noise that correlates with a drive running points to induced interference or a ground loop.
  • Measure at the transmitter and at the panel to locate which segment is adding the instability.
  • Instability only near full scale suggests insufficient loop voltage.
  • Filtering in the controller hides the symptom and should be the last step, not the first.

Possible causes and what to check

Possible causeWhat to check
The process is genuinely fluctuatingCompare against a local gauge or a second measurement. A pump cycling or turbulence at a probe produces real movement.
Induced noise from a VFD or motor cableObserve whether the instability starts when a drive runs. Check signal cable routing and separation from drive output conductors.
Ground loopMeasure AC voltage between the panel ground and the field device ground. Confirm the cable shield is grounded at one end only.
Insufficient loop voltageCalculate total loop resistance against supply voltage and transmitter compliance. Instability or clipping near 20 mA is the signature.
Loose or corroded terminalInspect and re-torque every termination in the loop. Flex the cable at each termination while watching the reading.
Failing transmitter or power supplySubstitute a loop calibrator for the transmitter. If the reading stabilizes, the transmitter is the source.
Turbulence or installation positionFor flow and level, check whether the sensing point sees a disturbed flow profile or a falling stream.
Analog card channel faultMove the loop to a spare channel and observe. This isolates the input hardware in two minutes.

Start by characterizing the instability

Before touching a wire, describe what the signal is doing. The shape of the instability narrows the cause more than any single measurement will.

What it looks likePoints toward
Fast, small, constant fuzzInduced electrical noise
Large jumps that coincide with a motor startGround loop or severe induced noise
Slow wandering over minutesGenuine process movement, or a thermal effect
Steady until the reading approaches full scaleInsufficient loop voltage
Intermittent dropouts to zeroLoose termination or an intermittent open
Stepped movement rather than smoothPoor resolution, or heavy filtering already applied
Only unstable in wet weatherMoisture in a junction box or conduit

Diagnostic procedure

  1. 1

    Confirm the process is not actually moving

    Check a local gauge, a sight glass, or a second instrument. It sounds obvious and it is regularly the answer, particularly on discharge pressure with a pump cycling or on a level probe near an inflow stream.

  2. 2

    Correlate with equipment operation

    Note whether the instability starts and stops with a specific drive, pump, or blower. This one observation separates electrical interference from everything else.

  3. 3

    Measure at the panel non-intrusively

    Read voltage across the input sense resistor. If it is unstable here, the instability is real on the wire and you continue outward. If it is stable here while the HMI is not, the problem is in scaling, filtering, or the SCADA tag.

  4. 4

    Measure at the transmitter

    Use test jacks or a series measurement at the transmitter. Stable at the transmitter and unstable at the panel means the cable run is picking up the disturbance. Unstable at both means the transmitter or the process is the source.

  5. 5

    Substitute a calibrator

    Disconnect the transmitter and inject a fixed 12 mA. If the panel reading is now rock steady, the transmitter or the process is responsible. If it is still unstable, the wiring, the card, or a ground problem owns it.

  6. 6

    Check grounding

    Verify the shield is grounded at exactly one end. Measure AC voltage between the two ground references. More than a few hundred millivolts is worth pursuing.

  7. 7

    Check loop voltage headroom

    Calculate maximum allowable loop resistance from supply voltage and transmitter compliance voltage, and compare against the actual total. Marginal headroom produces instability that gets worse as the signal rises.

  8. 8

    Move to a spare channel

    If everything above is clean, move the loop to a different analog input. A failing channel is uncommon but not rare, and this test is quick and conclusive.

Common mistakes

  • Adding filtering in the PLC first. It makes the display look better and hides a genuine fault that will get worse.
  • Replacing the transmitter before proving the transmitter is the source. It is the most expensive step and frequently the wrong one.
  • Grounding the shield at both ends "to make sure it is grounded". This creates the ground loop you are trying to eliminate.
  • Testing with the drive stopped and declaring the problem solved. Reproduce the condition before believing a fix.
  • Ignoring a small persistent instability. A signal that has become slightly noisy over months is often a termination that is slowly failing.

Fixes, in order of preference

  1. 01Correct the actual cause: re-route the cable, re-terminate the connection, fix the shield grounding, or raise the loop supply voltage.
  2. 02Add a signal isolator where a second ground cannot be removed.
  3. 03Improve the installation: separate the signal cable from drive output conductors, use proper twisted shielded pair, and add distance where possible.
  4. 04Move the sensing point if turbulence or installation position is the cause.
  5. 05Only then, apply modest filtering in the controller, and document that you did and why.

Frequently asked questions

Why does my analog signal only get noisy when a pump runs?
Either the drive output cable is coupling into the signal cable, or the motor current is exciting a ground loop. Check cable routing and separation first, then shield grounding, then add an isolator if the second ground cannot be removed.
How much filtering is acceptable?
Enough to remove measurement noise without hiding a real process change the control loop needs to see. On a wet well level a few seconds is usually harmless. On a pressure loop controlling a pump, heavy filtering will destabilize the control.
Can a bad power supply cause an unstable analog signal?
Yes. A loop supply with excessive ripple or one operating near its current limit puts that variation directly into the loop. Measure the supply output with a meter on AC volts to check for ripple, and confirm it is not overloaded.
The reading is stable at the panel but jumps on the HMI. What now?
The field is fine. Look at the controller scaling, any filtering, the update rate between controller and SCADA, and the SCADA tag configuration. A slow poll rate showing a fast-changing value can look like instability that is not there.