Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
How-ToInstrumentationLevelHow-ToCommissioning

How to Configure a Radar Level Transmitter

Commission a non-contact radar on a wet well or tank: mount it, set the reference and range from measured elevations, map false echoes with the vessel empty, set damping and the output, and verify against a tape at two levels before the controller uses it.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

How to Configure a Radar Level Transmitter

To configure a radar level transmitter, mount it with a clear view of the surface away from walls, inflows, and obstructions, enter the distance from its reference point to the vessel bottom and the span you want as 4 to 20 mA, run a false echo mapping with the level as low as possible so the transmitter ignores fixed reflections, set damping for the application, confirm the output direction, and verify the reading against a tape measure at two levels. Record every setting and the elevations they were derived from.

Key points

  • The reference point is on the transmitter, and every distance is measured from it. Find it in the manual first.
  • Range settings come from a tape measure, not from the drawing.
  • Map false echoes with the well as empty as it will get. A map made at high level hides the obstructions below.
  • Damping smooths the reading and delays it. A few seconds on a wet well; less on a fast process.
  • Verify at two levels. A one-point check cannot find a span error.

What you need

  • The transmitter manual, with the reference point drawing and the menu structure
  • A HART communicator, the manufacturer software, or the local display
  • A tape measure long enough to reach the bottom, with a weight
  • A loop calibrator or milliammeter for the output check
  • The instrument list with the intended range and the controller scaling
  • The mounting hardware: a flange or bracket that places the antenna where it needs to be

Procedure

  1. 1

    Find the reference point

    The manual shows where on the transmitter the measured distance starts: the flange face, the antenna tip, or a mark on the housing. Every range setting is a distance from that point. Getting this wrong offsets every reading by the difference.

  2. 2

    Check the mounting

    The antenna perpendicular to the surface, with a clear cone of view to the lowest level. Away from the wall by the distance the manual gives, away from the inflow stream and the pump discharge turbulence, and not above a ladder, a pump cable, a guide rail, or a float that swings through the beam. A nozzle or standpipe must be the size and length the manual allows, or the echo comes from the nozzle.

  3. 3

    Measure the distances

    With the tape, from the reference point to the vessel bottom or to the lowest point you want to measure. Note the elevation of the reference point against a site datum if elevations are used. Measure the current level at the same time, from the reference point to the surface.

  4. 4

    Enter the empty and full distances

    Empty distance, the distance from the reference point to the 4 mA point, usually the bottom or the low-level cutoff. Full distance, or span, the distance from the reference point to the 20 mA point, usually near the top of the range with margin below the antenna dead band. These two settings define the output. Copy them from the tape, and copy the resulting range to the instrument list and the controller scaling.

  5. 5

    Set the application parameters

    Medium type, liquid; vessel type, open or closed; surface condition, calm or turbulent; and for wastewater, the fast-changing or agitated surface option if offered. These tune the echo processing.

  6. 6

    Run the false echo mapping

    With the level as low as it can safely go, so that as much of the well as possible is in view, run the mapping function. The transmitter records the fixed echoes from the walls, the pumps, the rails, and the inflow pipe and ignores them thereafter. Mapping with the well full records nothing useful and leaves the obstructions below the surface unmapped.

  7. 7

    Set damping

    The time constant applied to the reading. Two to five seconds on a wet well smooths turbulence without hiding a real change. Less on a tank with fast fill and draw; more on a very turbulent surface. Damping delays every change by about its value, so keep it short enough for the control.

  8. 8

    Set the output and failure behavior

    Direction, 4 mA at empty and 20 mA at full unless the loop is designed otherwise. Failure current on lost echo, high or low per the site standard, so the controller can detect it. Echo-lost timeout, the seconds the transmitter holds the last value before declaring a fault.

  9. 9

    Verify at two levels

    At the current level, compare the transmitter reading with the tape. Then at a second level, after the pumps have moved the well or by pumping down deliberately, compare again. Both should agree within an inch or two. A consistent offset at both is the reference point; a difference that grows with level is the span or the empty distance.

  10. 10

    Check the loop and the controller

    Read the output current with the calibrator at the panel and confirm the controller shows the tape reading in engineering units. Confirm the low-level cutoff and the pump setpoints in the controller correspond to the elevations intended.

  11. 11

    Record

    Reference point location, empty and full distances, mapping level, damping, failure current, the two verification readings, and the date, on the loop sheet and the instrument list.

Settings that cause trouble

SettingSymptom when wrongFix
Empty distance from the drawing, not the tapeConstant offset at all levelsMeasure and re-enter
Mapping done at high levelReading jumps to a fixed value as the well pumps down past an obstructionRe-map at the lowest level
Dead band ignoredReading stuck at full when the surface rises near the antennaLower the 20 mA point below the dead band, or raise the transmitter
Damping too longLevel lags; pumps overshoot the stop setpointShorten damping; check the controller filter too
Failure current same as a valid readingLost echo looks like a real levelSet failure current outside 4 to 20 mA and validate in the controller
Nozzle too long or too narrowReading fixed at the nozzle endShorten the nozzle, use the correct antenna, or map it if the manual allows

Verification

  • Transmitter reading agrees with the tape at two levels at least a foot apart.
  • The controller displays the tape reading in engineering units.
  • The reading follows a pump-down smoothly through the full range without jumps at obstructions.
  • A blocked or lost echo produces the configured failure current and the controller alarms it.
  • All settings and the measured distances are recorded on the loop sheet.

Frequently asked questions

Why does the level jump to a fixed value part way through a pump-down?
An unmapped fixed echo, usually a pump, a rail, or the inflow pipe, that the transmitter starts tracking as the surface passes it. Re-run the false echo map with the level below the obstruction.
Can I configure the transmitter with the well full?
You can enter the distances and set the output, but you cannot map the false echoes usefully, and the two-point verification needs a second level. Enter the settings, then finish the mapping and the verification at low level, even if that means a return visit.
What about foam and grease on the wet well surface?
Radar reads the top of foam poorly and a grease mat inconsistently. Higher frequency radars with narrow beams do better; the application settings help; and where the surface is regularly covered, a submersible pressure transmitter as the second measurement with cross-checking in the controller is the practical answer.
Should the empty distance be the bottom of the well?
It should be the point you want to read as 4 mA, which is usually the bottom or a little above it, below the low-level cutoff. Setting it at the cutoff loses the ability to see the well below that level, which is useful for a dry-run diagnosis. Setting it far below the bottom wastes range.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.