Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
How-ToHow-ToCybersecuritySCADANetworkingStandards

How to Configure Remote Access

Give operators and engineers a way into the SCADA system from outside that does not give it to anyone else: a virtual private network with multi-factor authentication terminating in a demilitarized zone, and a test that proves the path works and that the.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

How to Configure Remote Access

To configure remote access, terminate a virtual private network with multi-factor authentication at a firewall in a demilitarized zone, not on the control network; put a jump host in that zone as the only destination remote users can reach, running the SCADA client and the engineering tools; give each person a named account with the least role that does the job, view-only for most; log every session with a recording where the platform supports it; enable vendor access per request for a limited time with an escort; block every other path, including cellular routers with public addresses and desktop remote tools; and test it from outside: the authorized path works, an account without the second factor fails, a session from the jump host cannot reach anything but what it should, and the audit log shows all of it. Then review the accounts quarterly and remove the ones that have left.

Key points

  • A virtual private network with multi-factor authentication ending in a demilitarized zone; nothing terminates on the control network.
  • A jump host is the only reachable destination; the SCADA client and the tools run there.
  • Named accounts with least privilege; view-only by default; control for the few who need it.
  • Session logging and, where possible, recording; vendor access per request with an escort and an expiry.
  • Test the path and the blocks from outside, and review accounts on a schedule.

What you need

  • A firewall with a virtual private network and a demilitarized zone interface
  • A multi-factor authentication service
  • A jump host, physical or virtual, hardened and patched, with the SCADA client and engineering tools
  • The user list with roles from the security policy
  • A laptop and a phone outside the plant network for testing

Procedure

  1. 1

    Draw the path

    Internet to the firewall virtual private network to the demilitarized zone to the jump host to the control network by the specific protocols the jump host needs. Nothing else. The drawing is the design and the test plan.

  2. 2

    Configure the tunnel

    A virtual private network on the firewall with strong encryption, certificate or key based, terminating in the demilitarized zone interface, with multi-factor authentication required for every user.

  3. 3

    Build the jump host

    A hardened machine in the demilitarized zone with the SCADA client and the engineering software, patched, with no local administrator for users, host firewall on, and session recording if available. Users log in with their named account and their second factor.

  4. 4

    Write the firewall rules

    Remote users to the jump host only, on the remote desktop protocol only. Jump host to the SCADA server on the client protocol; jump host to the engineering workstation or the controllers on the engineering protocols only where engineers need it. Deny everything else and log the denies.

  5. 5

    Define the roles

    View-only for operators who monitor from home, control for on-call operators who must act, engineering for the few who program, and a vendor role that is disabled by default. Map each to an account group.

  6. 6

    Create accounts

    Named accounts, no shared logins, in the directory with the multi-factor enrollment; the SCADA roles tied to the same identities; a removal process tied to departures.

  7. 7

    Set up vendor access

    A vendor account enabled per request by a named plant person for a set duration, with an escort watching the session, and disabled automatically afterward; every vendor session logged.

  8. 8

    Block the bypasses

    No cellular routers with public addresses, no desktop remote tools on control machines, no port forwards on the plant router, no modems on controllers. Scan for them and remove them.

  9. 9

    Test from outside

    The authorized user reaches the jump host and the SCADA client and can do their role and no more; a user without the second factor is refused; from the jump host, a ping or connection to anything outside the rules fails; the firewall log shows the denies; the session log shows the session.

  10. 10

    Operate it

    Quarterly account review, patching of the jump host and the firewall on the schedule, log review, and an annual test of the whole path.

LayerControlProves
TunnelVirtual private network with multi-factor authenticationOnly enrolled people get in
LandingDemilitarized zone, not the control networkA compromised tunnel lands outside the plant
DestinationJump host onlyOne hardened machine to defend
ProtocolsFirewall rules per roleA remote user cannot reach a controller directly
IdentityNamed accounts, least privilegeAccountability and limited damage
VisibilitySession and firewall logsEvery action attributable
VendorsPer-session enablement with escortNo standing back doors

Frequently asked questions

Can operators use the SCADA web client from home directly?
Through the virtual private network and the demilitarized zone, yes; exposed to the internet, no, whatever the vendor says about its security. The web client is served from the demilitarized zone or reached through the jump host.
Why a jump host instead of connecting the client straight through the tunnel?
A laptop at home is not a hardened machine, and the tunnel would carry whatever is on it into the control network. The jump host is one machine the plant controls, patches, and records.
What about the integrator who needs to program controllers from their office?
The vendor role: enabled per request for a set time, through the same tunnel and jump host, with the engineering protocols permitted from the jump host to the specific controller, and a plant person watching. Standing vendor access is a back door.
How do I know the bypasses are gone?
An external scan of the plant public addresses, an inventory of every cellular device and modem, and a look at every router configuration for port forwards. Then a policy and a periodic repeat.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.