Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
ReferenceCybersecurityDocumentationSCADAStandardsPLC

Session Logging

Recording every remote session into the control system: who connected, from where, when, to what, and what they did, from the VPN log through jump host session recording to the SCADA audit trail and controller change log, stored off the systems and reviewed.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Session Logging

Session logging captures every remote session at each layer it passes through: the VPN or remote access service logs the account, the source address, the time, and the factor used; the jump host logs the login and, on a jump host that supports it, records the session as video or a keystroke transcript; the SCADA audit trail logs what the user viewed, commanded, and changed; the controller programming software and the controller itself log downloads, online edits, and mode changes; and the firewall logs the connections the session made. All of it is forwarded to a log collector that the session cannot reach, retained for a period the policy sets, reviewed on a schedule for sessions that were not scheduled and actions that were not expected, and matched against change records. When a program change is detected or an incident occurs, the logs are the record of who was in the system and what they did.

Key points

  • Every layer logs: VPN, jump host, SCADA, controller, firewall. Together they say who, from where, when, to what, and what happened.
  • Session recording on the jump host turns a login entry into a replayable record of the work.
  • Logs go to a collector the session cannot touch; a log on the machine being used is a log the intruder can edit.
  • Review weekly for the unscheduled and the unexpected; every vendor session is checked against its change record.
  • Retain long enough for an investigation to look back months; a year is common.
  • Tell the people they are recorded; it is policy, it is in the contract, and it changes behavior.

The layers

LayerWhat it logsWhere it goes
VPN or remote access serviceAccount, source address, connection and disconnection time, authentication result, factor used, data volumeCollector
Jump host operating systemLogins and logouts, processes started, files transferredCollector
Jump host session recordingA video or transcript of the session: every screen and keystroke, replayableRecording store, indexed by account and time
SCADA audit trailDisplays opened, alarms acknowledged, commands issued, setpoints changed, configuration edited, with the account and the stationThe audit database, forwarded to the collector
Controller programming softwareConnections to controllers, downloads, online edits, mode changes, with the workstation accountCollector where the software supports it; otherwise the workstation log
ControllerChange counter, program signature, audit log on platforms that keep one, mode changesPolled by the SCADA and alarmed; the log forwarded where supported
FirewallConnections permitted and denied between the jump host and the control network, with ports and timesCollector
VaultCredentials retrieved during the session windowVault audit log

Session recording

A login entry says that an account connected at a time; a session recording shows what they did. Jump hosts built for privileged access record every session as a video of the screen, a transcript of the commands, or both, indexed so that a reviewer can find the session for a given controller on a given day and watch it. The recording is what turns a detected program change into an answer in minutes: the change was made in this session, by this account, and here is the edit. It is also what makes vendor sessions reviewable by someone who was not watching in real time. Recording is announced to the user at login, written into the vendor contract and the staff policy, and stored where the user cannot reach it.

Off the box

A log that lives on the machine that produced it can be edited or deleted by anyone who controls that machine, and an intruder controls it. Logs are forwarded as they are written to a collector on a separate hardened server, in the supervisory zone or the DMZ with a one-way path, with its own accounts and its own backup. The collector is the record of last resort: when the jump host is rebuilt after an incident, the collector still has every session. It is also where review happens, in one place, across every layer.

Review

  1. 1

    Weekly

    A named person reads the sessions of the week: each against the schedule and the change records. Unscheduled sessions, sessions from unexpected addresses or hours, failed authentications in volume, and sessions by accounts that should be disabled are investigated.

  2. 2

    Every vendor session

    The recording is reviewed against the change record: did they do what was approved and nothing else. A review that takes ten minutes per session catches the undocumented change while it is fresh.

  3. 3

    On every detection

    A program change alarm, a firewall denial, or a new device is matched against the session logs for the window; the session that explains it closes the alert, and the absence of one opens an incident.

  4. 4

    Quarterly

    The accounts with remote access against the staff and vendor lists; the retention against the policy; the collector health.

  5. 5

    Annually

    A test that the logs from each layer actually arrive at the collector, that a recorded session can be replayed, and that a query across the layers for one account on one day produces a coherent story.

Retention and privacy

Logs are kept long enough for an investigation to look back to the beginning of an intrusion, which is often months; a year online and longer in archive is a common policy, with recordings of vendor sessions kept for the life of the change record. The logs and recordings contain what people typed, including mistakes and, sometimes, credentials; they are access-controlled, retained per policy, and destroyed per policy. Staff and vendors are told in writing that sessions are logged and recorded, which is required in some jurisdictions and is the right thing to do in all of them.

Frequently asked questions

Our jump host is a plain remote desktop server. Can it record?
Not natively, in most cases. Privileged access products and some remote access services add session recording; a plain server can at least forward its logins and process logs to the collector and the SCADA audit trail covers what was done in the SCADA. Recording is the upgrade to plan for; the collector and the review are the habit to start now.
Do we log the operators in the control room too?
The SCADA audit trail logs their actions by their individual account, which is the record that matters. Session recording is for remote and privileged access, where the person is not in the room and the actions are configuration rather than operation.
What if the vendor objects to being recorded?
It is a condition of remote access, written in the contract, and most vendors accept it because it protects them too: the recording shows they did what was agreed. A vendor that will not be recorded is escorted on site instead.
How much storage do recordings need?
Session video compresses well; a typical engineering session is tens of megabytes, and a year of vendor sessions at a small utility fits on a modest disk. Transcripts are smaller still. The collector for text logs needs more planning than the recordings.

Direct contact

Have a controls question?