Data Diodes

Hardware that lets data flow one way only, from the control network outward, with no physical return path: what a data diode and a unidirectional gateway are, where they belong, what they can and cannot carry, and when a firewall is enough instead.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Data Diodes

A data diode is a hardware device with a transmitter on one side and a receiver on the other and no return path, so that information can leave the control network and nothing can enter it, not a packet, not an acknowledgment, regardless of any configuration or compromise. A unidirectional gateway pairs a diode with software on each side that replicates a historian, a file share, a database, or a protocol server from the control side to the outside, where users connect to the replica. It fits the boundary where the consequence of an inbound compromise is highest and the traffic is inherently one way: the historian and reporting path from the control network to the DMZ or the office, and the feed to a cloud or a regional operations center. It cannot carry anything that needs a reply, so remote access, vendor support, and any command from outside are excluded by design, which is the point. For most utilities a firewall with one-way rules is proportionate at most boundaries; the diode is chosen for the boundary where the utility wants physics rather than configuration.

Key points

  • One direction, enforced by hardware: no return path exists, so no configuration error or compromise can open one.
  • The gateway software replicates a historian, a file share, or a protocol server to the outside; users connect to the replica.
  • It fits the historian and reporting path outward, and the cloud feed; it excludes remote access by design.
  • Protocols that need acknowledgments are handled by the gateway proxies on each side, not across the diode.
  • A lost frame cannot be retransmitted by the receiver asking; the gateway uses redundancy and sequence checks instead.
  • A firewall with one-way rules is proportionate at most boundaries; the diode is for the one where the consequence justifies hardware.

What it is

A firewall is software with a rule that says traffic may flow one way, and the rule can be changed, bypassed by a vulnerability, or misread by an administrator. A data diode is a fiber transmitter on the control side and a fiber receiver on the outside, with no transmitter on the outside and no receiver on the control side. Light goes one way. There is no rule to change and no path to exploit; an attacker with complete control of every machine outside the diode has no physical means of sending a single bit inward. That property is why diodes are used at the boundaries of nuclear and military systems, and why a utility considers one for the boundary it worries about most.

How data crosses

Network protocols expect replies: a request is acknowledged, a lost packet is retransmitted on request, a connection is negotiated. None of that works across a diode. A unidirectional gateway solves it with software on each side. On the control side, a proxy connects to the historian, the file share, the database, or the protocol server as an ordinary client, reads the data, and sends it through the diode as a stream with sequence numbers and error correction. On the outside, a proxy receives the stream and rebuilds a replica: a second historian that outside users query, a mirrored file share, a database that reports read, a protocol server that outside systems poll. The outside sees a normal server; the control side sees a normal client; the diode in between carries a stream that nothing can answer.

Carried outwardHowNote
Historian dataThe control historian replicated to an outside historianThe standard use; the outside historian serves the office and the reports
FilesA file share on the control side mirrored outwardReports, exports, logs, backups leaving the control network
Database tablesSelected tables replicatedReporting databases
Protocol serversA Modbus or OPC server on the control side replicated as a server outsideOutside systems poll the replica; their polls never reach the control side
Logs and syslogStreamed outward to a collectorSecurity monitoring from the outside of the diode
Screen imagesPeriodic captures of displays replicated outwardView-only situational awareness for the office

What it cannot do

  • Remote access, vendor support sessions, and any interactive connection into the control network; those need a reply path and go through the jump host instead.
  • Commands or setpoints from outside into the control network; a diode that carries them is not a diode.
  • Retransmission on request; the receiver cannot ask, so the gateway sends redundantly and checks sequence, and a gap is reported rather than filled.
  • Time synchronization inward; the control network has its own time source.
  • Antivirus updates and patches inward; those arrive through a separate controlled path, or through a second diode pointing inward with its own scrutiny, which some vendors offer.

Where it belongs

BoundaryDiode or firewallReasoning
Control network to DMZ, historian and reporting pathDiode where the consequence justifies it; firewall with one-way rules otherwiseTraffic is inherently outward; the diode removes the inbound path entirely
DMZ to officeFirewallThe DMZ is the buffer; a firewall is proportionate
Control network to cloud or regional operations centerDiode, or a broker in the DMZ fed one wayOutward publish only; nothing from the cloud reaches a controller
Safety system to control networkDiode from the safety system outward, or nothingThe safety system reports status; nothing writes to it
Remote access into the control networkFirewall, VPN, jump host, multi-factor authenticationA diode cannot carry it; the path is designed with its own controls
Between control zones inside the plantFirewallTwo-way traffic between zones is normal; rules define the conduits

Operating one

A diode installation is monitored like any link: the gateway reports the stream health, the sequence gaps, and the replica lag, and the outside historian is compared with the inside one on a schedule. The proxies on each side are servers that are hardened, patched, and backed up. A change on the control side, a new tag, a new file share, is mirrored by a change in the gateway configuration under change management. And the organization accepts the consequence: when someone outside wants to send something in, the answer is the controlled path through the jump host, not a hole in the diode.

Frequently asked questions

Is a diode required by any regulation for water utilities?
No regulation requires it; the industrial security standards describe it as a means of achieving the highest security levels at a zone boundary, and some insurers and assessors regard it favorably. It is a design choice for the boundary where the utility decides that configuration is not enough.
What happens when the outside historian falls behind?
The gateway reports lag and gaps; the outside replica catches up from the stream if the gateway buffers, and a persistent gap is filled by a re-send initiated from the control side, because only the control side can initiate anything. Monitoring of the gateway is part of the installation.
Can a diode replace the DMZ?
It changes what the DMZ is for. With a diode carrying the historian and files outward, the DMZ still hosts the replicas, the jump host for the remote access that the diode cannot carry, and the update path inward. The diode removes the inbound risk on the data path; the DMZ remains for everything else.
How much do they cost?
The hardware is modest; the gateway software licensed per replicated application is the larger part, and the total is comparable to a redundant pair of enterprise firewalls. Against the cost of the incident it prevents on the boundary it protects, utilities that have chosen one consider it reasonable.