The historian is the most connected server in a control system and the most exposed: giving the office, reports, and the cloud the data they need without a path to the plant, with a collector in the control zone, a replica in the DMZ, and one-way flow.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Historian Security

The historian is where everyone outside the control room wants to connect, which makes it the natural bridge for an attacker from the office to the plant. The design that prevents that is two historians: one in the control zone that collects from the controllers and the SCADA, and a replica in the DMZ that receives data one way from it and serves the office, the reports, and any cloud connection. Nothing in the office connects to the control zone historian, the DMZ replica cannot write back, accounts on the replica are read-only, the data path from control zone to DMZ is a one-way replication or a unidirectional gateway where the risk warrants it, and the archives on both are protected, backed up, and logged as the regulatory records they are.

Key points

  • The historian is the server the office needs, which makes it the server the attacker wants.
  • Two historians: collect in the control zone, serve from a replica in the DMZ.
  • Data flows one way, control zone to DMZ; the replica cannot write back and the office cannot reach the collector.
  • Read-only accounts for everyone who reads; the collector service account has the minimum rights to write.
  • Archives are regulatory records: access controlled, backed up off site, and audited.
  • Cloud and enterprise connections attach to the DMZ replica through a broker or a gateway, never to the collector.

The exposure

Who wants historian dataTypical connectionRisk if connected to the control zone historian
Managers and office staffTrend and dashboard clients on office computersEvery office computer becomes a path into the control zone
Reporting and complianceReport servers, spreadsheets with database connectionsCredentials in spreadsheets; report servers reachable from the office
Maintenance and laboratory systemsDatabase connections, scheduled exportsEnterprise systems with their own vulnerabilities reaching inward
Cloud analytics and vendor servicesInternet connections from the historianThe control zone historian talking to the internet
Regulators and consultantsExports, occasionally remote accessRemote access to a control zone server

The design

The collecting historian lives in the control zone, or in the supervisory zone beside the SCADA servers, and collects from the controllers and the SCADA tag server. It is reached only by control zone clients and by the replication process. A second historian in the DMZ receives the data from the first through a one-way replication configured in the historian product, or through a unidirectional gateway or data diode where the utility has decided that the risk justifies hardware enforcement. The DMZ historian serves everything outside: office trend clients, report servers, database connectors, and the connection to any cloud service, which itself goes out through the DMZ. The firewall permits the replication from inside to the DMZ on its ports, permits the office to reach the DMZ historian, and permits nothing from the DMZ or the office into the control zone.

Accounts and access

  • The collector service account on the control zone historian has rights to write history and nothing else, with no interactive login.
  • The replication account has rights to read from the collector and write to the replica, and nothing else.
  • Every reader on the replica has a read-only account, individual where the product allows and otherwise a role with no write rights; report servers and connectors use service accounts that are read-only.
  • Engineering configuration of the historian is done from the control zone with an engineer account, not from the office.
  • Web interfaces of the historian are enabled on the replica only, with encryption and authentication, and disabled on the collector.
  • Vendor connectors and cloud agents run on the replica or on a separate DMZ host, never on the collector.

Archives as records

The archive files hold years of compliance measurements, and their integrity matters as much as their confidentiality. Access to the archive directories is restricted to the historian service and the backup process; administrators reach them through change management. The archives are backed up on a schedule, off the server and off site, with the backups themselves protected. Deletion and modification of archives are logged, and the historian audit log, where the product has one, is forwarded to the log collector. A retention policy says how long the records are kept, and a periodic export in a plain format provides a record that does not depend on the historian software at all.

Cloud and enterprise

A utility that sends data to a cloud analytics service, a regional operations platform, or an enterprise data lake does so from the DMZ, one way, through a broker or a gateway that publishes what has been selected and accepts nothing back into the control zone. Any inbound value from those systems, such as a demand forecast or an optimization setpoint, arrives in the DMZ, is validated, and is written to a designated SCADA tag by a controlled process, never directly to a controller. The connection uses encryption and certificates, the credentials live on the DMZ host, and the outbound firewall rule is specific to the destination.

Frequently asked questions

Is a data diode necessary?
For most water utilities a software replication through a firewall with one-way rules is proportionate. A unidirectional gateway is chosen where the consequences justify hardware enforcement, where a regulator or an insurer expects it, or where the utility wants to eliminate the possibility of a firewall misconfiguration. The two-historian design is the same either way; the diode replaces the firewall rule on that one path.
The reporting tool needs to write calculated results back. Where do they go?
Into the DMZ historian or a DMZ database, where the office and the reports can read them. If a calculated value must reach the SCADA for display, a controlled process in the control zone reads it from the DMZ through a one-way pull, validates it, and writes it to a designated tag. Nothing in the DMZ pushes into the control zone.
What about the historian web interface that the vendor promotes?
It is convenient and it is a web server on a control system machine. Run it on the DMZ replica only, with encryption, authentication, and the same patching as any DMZ server; disable it on the collector.
How is historian access audited?
By the historian audit log where the product provides one, by the operating system logon logs on the historian servers, and by the firewall logs for the connections that reach them, all forwarded to the log collector and reviewed on a schedule for readers who should not be there and for configuration changes.