Color in HMI Design

How color is used on a high performance HMI: a gray palette for normal operation so that color means something, alarm colors reserved by priority, equipment state by fill and text rather than red and green, color-blind safe choices, and the palette table.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Color in HMI Design

On a well-designed HMI, color is information, not decoration: the background and the normal process depiction are grays, so that the few colors on the screen are the things that need attention. Alarm colors are assigned by priority in the alarm philosophy and used for nothing else, equipment running and stopped states are shown by fill contrast and a text label rather than green and red, bad quality and manual mode have their own distinct indications, and every color choice is paired with a shape, a text, or a position cue so that operators who cannot distinguish the colors still get the message. All of it is written in a style guide with a palette table that every display follows.

Key points

  • Gray for normal. If everything is colored, nothing stands out.
  • Alarm colors by priority, from the philosophy, used only for alarms.
  • Running and stopped by fill and text, not green and red; red is an alarm color.
  • Every color has a second cue: a shape, a label, a border, a position. Color-blind operators exist in every utility.
  • One palette table in the style guide; the display that deviates is wrong, however pretty.
  • Consistency across displays, sites, and years matters more than any single choice.

Why gray

The purpose of a control display is to let an operator see what is abnormal quickly. A display that draws every pipe in blue, every running pump in bright green, every tank in cyan, and every heading in red has spent its colors on things that are normal, and the one thing that is wrong is one colored object among a hundred. A display drawn in grays, with process lines in mid gray, equipment outlines in dark gray, and text in near black, is calm when the plant is calm. An alarm colored red or yellow on that display is the only saturated color on the screen and the eye goes to it without searching. That is the reasoning behind the high performance HMI palette, and it is the single most effective change a utility can make to its displays.

A palette

ElementColorSecond cue
Display backgroundLight or medium grayNone needed
Process lines and vesselsMid gray, thinLine weight for the main flow path
Text and valuesNear blackFont size by importance
Equipment runningLight fill, or white, with the outlineText: RUN, and a state label on the faceplate
Equipment stoppedDark gray fillText: STOP or OFF
Equipment in manual or localA distinct marker, often a small tag or border in a reserved colorText: HAND, LOCAL, MAN
Highest priority alarmRedA symbol such as a filled triangle, and the priority number
High priority alarmOrange or amberA different symbol, and the priority number
Medium priority alarmYellowA different symbol
Low priority or advisoryBlue or cyan, mutedA different symbol
Bad quality or communication lostMagenta, or a hatched fill, with the value replaced by a markerThe value itself shows a symbol, never a stale number
Interlocked or permissive blockedA reserved marker color on the deviceA symbol and a faceplate entry
Selected or focused itemA thin highlight borderBorder only
An example; the alarm colors and the number of priorities come from the alarm philosophy

Running and stopped

Green for running and red for stopped is the convention from panel pilot lights, and it fails on a display for two reasons. Red is the color that must mean the highest alarm, and a screen full of stopped pumps in red is a screen full of false alarms. And green and red are the two colors that the most common color vision deficiency cannot tell apart. On the display, a running device is a light or white fill and a stopped one a dark fill, with a text label on or beside the symbol; the contrast is visible to everyone and leaves the alarm colors alone. A plant that is not ready to give up its pilot light colors can at least keep red off the running and stopped states and use the alarm colors only for alarms.

Color vision

Roughly one man in twelve has a color vision deficiency, most commonly a weakness in distinguishing red from green, and a utility with a few dozen operators has some. A display that conveys state only by color is unreadable to them, and they will not always say so. The rule is that every color carries a second cue: an alarm has a shape and a number as well as a color, a state has a text label as well as a fill, a bad value has a symbol as well as magenta. Testing a display in a grayscale rendering, or with a color-blindness simulator, shows whether the cues are enough.

Consistency

Whatever the palette, it is applied the same way on every display, at every site, by every integrator, for the life of the system. A pump that is drawn one way in the plant and another way at the lift stations, or an alarm color that means high at one site and medium at another, makes the operator translate, and translation under stress is where errors happen. The style guide holds the palette table, the symbol library, and the rules, and it is a deliverable that every project uses. A system with three generations of displays in three styles is due for a style guide and a migration.

Frequently asked questions

Operators like the colors. Why change?
Because the purpose of the display is to make the abnormal obvious, and the evidence from process industries is that gray displays with reserved alarm colors let operators detect and respond to abnormal conditions faster and with fewer errors. The preference for color fades after a few shifts with a calm display; the first time an operator spots a problem across the room, the argument is over.
Which colors go with which priority?
The alarm philosophy decides, and the platform implements it. A common assignment is red for the highest priority, orange or amber for high, yellow for medium, and blue or cyan for low. The colors must not be used for anything else on the display, and each must come with a distinct symbol.
How do I show a value that is bad quality?
Replace the number with a marker such as dashes or a question mark, color the field magenta or hatch it, and show the same marker on any trend or bar that uses the value. A stale number in a normal color is the worst outcome, because the operator will believe it.
What about the colors on the physical panel?
Panel pilot lights follow their own conventions and standards, with green often meaning running and red meaning stopped or fault depending on the site standard. The HMI does not need to match the panel; it needs to be consistent with itself. Where an operator uses both, a note in the style guide about the difference is worth writing.