Ladder Logic Fundamentals

Rungs, contacts, coils, and the relay conventions the language inherited — plus the patterns you will meet in almost every industrial program.

10 min readUpdated Aug 11, 2026Published Feb 3, 2026By Eric Sullivan

The short answer

Ladder Logic Fundamentals

Ladder logic is a graphical PLC programming language drawn to resemble relay ladder diagrams. Each rung reads left to right: input conditions on the left, an output on the right. If a continuous path of true conditions exists across the rung, the output energizes. It is defined in IEC 61131-3 as Ladder Diagram (LD) and remains the most widely used language in industrial controls.

Key points

  • A rung is true when a continuous logical path exists from the left rail to the output.
  • Series contacts are AND. Parallel branches are OR.
  • Examine-if-closed tests whether a bit is on; examine-if-open tests whether it is off.
  • The seal-in (latching) rung is the single most common pattern in industrial code.
  • Readability is a real engineering requirement, because a technician will read this at 2 a.m.

Reading a rung

Two vertical rails frame the program. Power, conceptually, flows from the left rail to the right. A rung is a horizontal path between them containing conditions and an output. If the conditions form an unbroken true path, the output on the right end energizes.

A basic rung: run the pump when called and not faulted
   Pump_Call    Pump_Fault                      Pump_Run
|-----] [---------]/[--------------------------( )----|
   (examine       (examine                    (output
    if closed)     if open)                     coil)

Reads as: if Pump_Call is ON and Pump_Fault is OFF, energize Pump_Run.

The instructions you will use constantly

Examine if closed -] [-
True when the referenced bit is on. Often called a normally-open contact, which is a description of the drawing, not of the field device.
Examine if open -]/[-
True when the referenced bit is off.
Output coil -( )-
Sets the bit on when the rung is true and off when it is false. Non-retentive.
Latch and unlatch -(L)- -(U)-
Set and reset a bit that holds its state when the rung goes false. Powerful and easy to misuse. Every latch needs a clearly identified unlatch.
Timers TON / TOF / RTO
On-delay, off-delay, and retentive timers. TON is by far the most used, for start delays, failure-to-start windows, and debouncing.
Counters CTU / CTD
Count up or down on a false-to-true transition. Used for pump starts, batch counts, and retry limits.
Comparison EQU / GRT / LES / LIM
Compare values. The backbone of analog logic: level above start setpoint, pressure below alarm limit, and so on.
Move and math MOV / ADD / SUB / MUL / DIV
Move and compute values. Scaling arithmetic usually lives here.
One-shot ONS / OSR
True for exactly one scan on a false-to-true transition. Essential when you want an action to happen once, not every scan a condition is true.

Series, parallel, and the shape of logic

Contacts in series form a logical AND: every one must be true. Contacts in parallel form a logical OR: any one being true is enough. Almost all industrial logic is built from these two shapes, and the visual layout of a rung is a direct picture of the boolean expression behind it.

Parallel branch: any of three calls will start the pump
   Hand_Call                                       Pump_Run
|-----] [----+------------------------------------( )----|
             |
   Auto_Call |
|-----] [----+
             |
   Remote_Call
|-----] [----+

Reads as: Hand_Call OR Auto_Call OR Remote_Call energizes Pump_Run.

The seal-in rung

This is the pattern you will see in nearly every program ever written. A momentary start button energizes an output, and a contact from that output is placed in parallel with the button so the rung stays true after the button is released. A normally-closed stop condition in series breaks the path.

Seal-in with a stop and a fault
   Start_PB     Stop_PB      Fault                    Motor_Run
|-----] [-------]/[--------]/[--------+-------------( )----|
                                      |
   Motor_Run                          |
|-----] [-----------------------------+

Release Start_PB and the Motor_Run contact holds the rung true.
Stop_PB or Fault breaks the path and the output drops.

Writing ladder someone else can maintain

  • Name tags for what they are, not where they are wired. Pump_1_Run_Cmd survives a rewire; N7:12/3 does not.
  • One clear purpose per rung. Long rungs with five branches are impossible to troubleshoot online.
  • Comment the intent, not the syntax. "Prevents restart until discharge pressure decays" is useful; "turns on the pump" is not.
  • Group logic into routines that match how the plant is organized: one per pump, one per process area.
  • Avoid duplicating the same output coil in more than one place. The last rung solved wins, and it will confuse everyone including you.
  • Put interlocks in a consistent position so a technician can scan a program and see the conditions at a glance.

When ladder is the wrong choice

Ladder is excellent for discrete interlocking and for logic that technicians must troubleshoot online. It is poor at math-heavy work, string handling, and complex looping. Structured text handles those cleanly. Most mature programs mix them: ladder for the interlocks and device control that maintenance needs to read, structured text for the calculations underneath.

Frequently asked questions

Is ladder logic still used?
Yes, heavily. It remains the dominant language in water, wastewater, and most discrete manufacturing, largely because the people who maintain these systems can read it online while the process is running.
What is the difference between a normally-open contact in the field and in the program?
A field contact is a physical device state. A program instruction examines a memory bit. If a normally-closed field contact is wired to an input, the input bit is on when the device is at rest. Whether you use examine-if-closed or examine-if-open in the program depends on what you want to detect, and getting it backwards is a very common commissioning error.
Why does my output flicker?
Usually because the same output address is written by more than one rung, or because the condition driving it is oscillating around a threshold with no deadband. Search the whole program for duplicate destructive writes to that address first.
What is a one-shot and when do I need one?
A one-shot is true for a single scan when its condition transitions from false to true. You need one any time an action should happen once per event rather than continuously: incrementing a counter, sending a message, or capturing a value at the moment something happened.

Direct contact