Permissives

The conditions that must be true before a device may start: how permissives differ from interlocks and trips, the list a pump or feeder usually needs, coding them so the HMI can say why a start was refused, and the rules for time delays and bypasses.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Permissives

A permissive is a condition that must be true for a start command to be accepted; it is evaluated when the start is requested and does not by itself stop the device once it is running. An interlock is a condition that must stay true for the device to keep running, and a trip is a hardwired protection that acts without the controller. Good practice codes each permissive as its own named bit, combines them into a single ready bit, shows the list on the HMI so an operator can see which one is blocking, applies short time delays to conditions that flicker, and allows bypasses only where the functional description says so, with the bypass alarmed and logged.

Key points

  • Permissive: checked at the start. Interlock: enforced while running. Trip: hardwired, independent of the controller.
  • One named bit per condition, combined into one ready bit; never a single anonymous rung of series contacts.
  • The HMI shows every permissive with its state, so the answer to why it will not start is on the screen.
  • Flickering conditions get a short on-delay; a level cutoff needs a deadband so it does not chatter at the threshold.
  • A permissive that is also a run interlock is coded in both places, deliberately, not by accident.
  • Bypasses only where the functional description allows, with an alarm while active and a record of who set it.

Permissive, interlock, trip

The three words are used loosely in the field and precisely in a functional description. A permissive gates the start: if the wet well is below the low-level cutoff, the pump may not start. An interlock stops or prevents running as long as the condition exists: a seal-fail or a motor high-temperature signal stops a running pump and keeps it stopped. A trip is protection that works whether or not the controller is running: the motor overload relay, the emergency stop, the high-high level float that drops the starter coil. The distinction matters because the response differs. A permissive that goes false after the pump starts does not necessarily stop the pump; if it should, the condition also belongs in the interlock logic.

TypeWhen evaluatedEffectTypical examples
PermissiveAt the moment of the start requestStart refused; no effect once runningLevel above cutoff, drive ready, valve position, minimum off time elapsed, in AUTO
Run interlockContinuously while runningDevice stopped and held off; usually latched with a resetSeal fail, high temperature, low suction pressure after a delay, discharge valve failed to open
TripContinuously, in hardwareStarter or drive de-energized regardless of controllerOverload relay, emergency stop, high-high float, drive fault contact

What a pump start usually needs

  • Level: wet well or suction level above the low-level cutoff, with a deadband so the condition does not chatter.
  • Drive or starter ready: no fault, control power present, the drive reporting ready, the starter not tripped.
  • Selector: the hand-off-auto switch in AUTO for an automatic start; HAND starts bypass the automatic permissives by design and should still respect the trips.
  • Valves: suction valve open by limit switch where one exists; discharge valve at the position the sequence expects.
  • Anti-cycle: the minimum off time since the last stop has elapsed, and the starts-per-hour count is below the motor limit.
  • Maintenance: no lockout tag in the system and no out-of-service flag on the HMI.
  • Process: for a chemical feed pump, carrier water flow proven and the day tank not at low level.

Coding pattern

Each permissive is its own bit with a name that says what it is. The bits are combined into one ready bit, and the start command is accepted only while the ready bit is true. Nothing else in the program looks at the individual bits except the HMI, which displays them. This pattern is the same in ladder, structured text, and function block; the structured text version is the shortest to read.

Structured text; ladder uses one rung per bit and one rung for the ready bit
// Pump 1 start permissives, one bit each
P1_Perm_Level  := LT_101_PV > P1_LowLevelCutoff + P1_LevelDeadband;
P1_Perm_Drive  := VFD1_Ready AND NOT VFD1_Faulted;
P1_Perm_Valve  := ZSO_101;                 // suction valve open limit
P1_Perm_Seal   := NOT P1_SealFail;
P1_Perm_MinOff := P1_MinOffTimer.Q;        // minimum off time elapsed
P1_Perm_Auto   := P1_HOA_Auto;
P1_Perm_Maint  := NOT P1_OutOfService;

// One ready bit; the HMI shows the individual bits
P1_Ready := P1_Perm_Level AND P1_Perm_Drive AND P1_Perm_Valve
            AND P1_Perm_Seal AND P1_Perm_MinOff AND P1_Perm_Auto AND P1_Perm_Maint;

// Start accepted only while ready; run interlocks are handled separately
IF P1_AutoStartRequest AND P1_Ready THEN
    P1_RunCmd := TRUE;
END_IF;

The level permissive uses the cutoff plus a deadband, so the pump can start only when the level is comfortably above the point where the interlock would stop it. Without that margin a pump starts, draws the level down through the cutoff on the first stroke, stops, and repeats.

Time delays

Some conditions are true almost all the time and false for a moment: a pressure switch that bounces as a valve opens, a drive ready contact that drops for a scan as the drive changes state, a level reading that dips for one sample. A permissive built directly on such a signal refuses starts for no reason the operator can see. Give those conditions an on-delay of a second or two before they count as true. Do not delay the conditions that protect equipment, and do not delay the trips at all.

On the HMI

The most useful thing a permissive list does is answer the question the operator asks at two in the morning: why will it not start. Put the list on the pump faceplate or a detail popup, one line per permissive with its current state, in the same words the functional description uses. The ready bit drives the start button availability. When a start is refused, the line that is false is the reason, and nobody needs to open the program.

Bypasses

A bypass lets a start proceed with a permissive false: a level bypass to pump a wet well down below the cutoff for cleaning, a valve position bypass when a limit switch has failed and the valve is verified open by hand. Bypasses exist because plants have to keep running, and they are dangerous because they get forgotten. Allow them only where the functional description names them, require a supervisor level login, alarm continuously while any bypass is active, log who set it and when, and clear them automatically on a time limit or on the next stop.

Frequently asked questions

Should a permissive that goes false while running stop the pump?
Only if the functional description says so, and then it is coded as a run interlock as well. A drive ready contact that drops out while running should stop the pump; a minimum off time or an AUTO selector already satisfied at the start should not. Decide condition by condition and write it down.
Where does the anti-cycle timer belong?
In the permissives. The minimum off time and the starts-per-hour limit protect the motor from heating; they are conditions that must be true before a start and have nothing to do with a running pump. A permissive display that shows the remaining off time saves a lot of radio calls.
Should a HAND start respect the permissives?
A HAND start is the operator taking responsibility, so it usually bypasses the automatic permissives such as level and AUTO. It never bypasses the trips, and a plant may choose to keep a few protective conditions, such as seal fail, in force in HAND. Say which in the functional description; the HOA logic is where accidents are designed in.
How do I keep a long permissive list from being a maintenance burden?
Use a standard pump block with a fixed list of permissive bits, and leave the unused ones forced true with a configuration flag. Every pump then has the same list in the same order on the same faceplate, and a new pump is configured rather than programmed.