Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
ReferenceInstrumentationSignals4-20 mAGroundingDesign

Signal Isolation

Isolating analog signals: loop isolators and their variants, splitters that feed two receivers, converters, the common-mode problem isolation solves, ratings, accuracy and response costs, and when an isolated input module makes the isolator unnecessary.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Signal Isolation

A signal isolator passes a 4 to 20 milliamp or voltage signal from one circuit to another with no electrical connection between them, so that a ground potential difference, a common-mode voltage from a drive, or a fault on one side does not appear on the other. It comes in several forms: a loop-powered isolator that takes its power from the receiving loop and passes a transmitter signal into it; an output-powered isolator that powers a two-wire transmitter on its input side and drives the output from the panel supply; a four-wire isolator with its own supply that isolates input, output, and power from each other; a splitter that takes one signal and produces two isolated outputs for two receivers; and converters that also change the signal form. Each adds a small error and a small delay, needs mounting, power, and fusing, and has an isolation rating that must exceed the voltage it will see. Where the controller input module has isolated channels, the isolator is unnecessary for the ground loop case; it remains the answer for feeding two receivers, for a grounded transmitter into a non-isolated input, and for signals from drives and other panels.

Key points

  • An isolator passes the signal and blocks the ground path; it cures ground loops, common-mode voltage, and fault propagation.
  • Choose the form by who powers what: loop-powered, output-powered for a two-wire transmitter, or four-wire with its own supply.
  • A splitter feeds two receivers from one transmitter without putting them in series.
  • Isolation adds error and delay; check the accuracy and response time against the loop needs.
  • Isolated input channels remove the need for an isolator in the simple ground loop case.

Forms

TypePowerUse
Loop-powered isolatorFrom the receiving loop; no separate supplyA transmitter signal from a field or another panel into a panel loop; simplest to install
Output-powered isolatorPanel supply on the output side; provides loop power to a two-wire transmitter on the input sideA grounded or remote two-wire transmitter feeding a non-isolated input
Four-wire isolatorIts own supply, isolated from input and outputSignals from drives and instruments with their own power; full three-way isolation
Signal splitterPanel supplyOne transmitter feeding a controller and a chart recorder, or two controllers, each isolated
ConverterPanel supplyCurrent to voltage, voltage to current, or a range change, with isolation
Intrinsically safe isolatorPanel supplyGalvanic isolation and energy limiting for a hazardous area loop

What it solves

Ground loops
A transmitter grounded at its mounting and a receiver grounded at the panel share a ground path through the earth; the potential difference drives a current that adds to the signal. The isolator breaks the path.
Common-mode voltage
A signal from a drive or a device with its own electronics sits at a voltage above the panel common; a non-isolated input reads the voltage as signal or is damaged. The isolator floats the input side.
Fault propagation
A surge or a short on the field side stays on the field side; the isolator sacrifices itself before the input module.
Two receivers
Putting two receivers in series on one loop works until the loop voltage runs out or one receiver is grounded; a splitter gives each its own isolated loop.
Signal form
A device with a voltage output feeding a current input, or the reverse, through a converter that isolates as well.

Costs

  • Accuracy: a tenth of a percent of span is typical; check it against the loop tolerance, and include it in the loop error budget.
  • Response time: milliseconds to tens of milliseconds; irrelevant for level and flow, relevant for a fast pressure loop.
  • Power: a supply and a fuse per isolator, and heat in the panel.
  • Failure: one more device that can fail open, short, or drift; a calibration point on the schedule.
  • Isolation rating: the voltage between sides the isolator withstands; specify above the worst common-mode voltage or surge it will see.

Installation

  1. 1

    Where

    At the panel where the signal enters, on the rail, near the terminal strip of the loop, after the surge protector if the loop leaves the building.

  2. 2

    Which side is grounded

    Decide and draw it: one ground per side, and the isolator between. An isolator with both sides grounded at the same point isolates nothing.

  3. 3

    Power

    From the panel 24 volt supply through a fused terminal; the loop it powers is then a panel loop.

  4. 4

    Range

    Configure or order the input and output ranges; a 4 to 20 into 4 to 20 isolator is the common case, a range change is a converter.

  5. 5

    Calibrate

    Two points through the isolator, with a calibrator on the input and a meter on the output, at commissioning and on the loop schedule.

  6. 6

    Document

    The isolator on the loop drawing and the I/O list, with its type, its power source, and which side is grounded.

Diagnosing an isolator

  • Output at 4 milliamps with the input live: the isolator has no power or has failed; check the fuse and the supply.
  • Output tracks the input with an offset: calibration, or the isolator drifting; recalibrate and watch.
  • Output correct on the bench and wrong in the panel: the isolation is bypassed by a second ground, or the common-mode voltage exceeds the rating.
  • Output noisy: the input side is picking up noise the isolator passes; the isolator does not filter, and the cable and shield are the fix.

Frequently asked questions

Do I need an isolator on every loop?
No. Loops powered from the panel, grounded only at the panel, into a non-isolated module with all channels on the same common, work without one. Isolate the loops that cross grounds, come from drives or other panels, or need two receivers.
Can I put the isolator at the transmitter end?
A field-mounted isolator or an isolated transmitter output does the same job at the other end and is used where the panel cannot be changed or the common-mode problem originates at the panel. It needs power and an enclosure in the field.
What is the difference between an isolator and a surge protector?
A surge protector clamps transients to ground and is connected to ground on purpose; an isolator blocks the ground path. A loop that leaves the building has both: the protector at the entrance, the isolator after it.
Why does the reading change when I ground the shield at the field end?
The shield became the ground loop path; a shield is grounded at one end only, and the reading change proves the loop needs isolation or a correct shield ground rather than a second one.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.