Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
ReferenceInstrumentationSignalsGrounding

Ground Loops in Instrumentation

Two grounds at different potentials, one signal circuit between them, and a reading that will not sit still. How to find it and how to prevent it.

8 min readUpdated Aug 8, 2026Published Feb 25, 2026By Eric Sullivan

The short answer

Ground Loops in Instrumentation

A ground loop occurs when a signal circuit is connected to earth at more than one point and those points sit at slightly different potentials. The difference drives current through the signal wiring, adding an error that typically appears as noise, drift, or an offset that changes when nearby equipment runs. The fix is to establish a single ground reference for each signal circuit.

Key points

  • Two earth connections at different potentials drive current through your signal path.
  • Ground a cable shield at one end only, normally the panel end.
  • Symptoms often correlate with a VFD, a large motor, or welding nearby.
  • Isolators break the loop when you cannot remove the second ground.
  • Never lift a protective equipment ground to fix a signal problem.

Why two grounds are a problem

Earth is not a single equipotential surface. The ground at a lift station two hundred feet from the plant is not at the same potential as the ground at the motor control center, and the difference varies with load, soil moisture, and whatever else is drawing current. It may be millivolts. During a fault or a large motor start it can be volts.

Connect a signal circuit to earth at both ends and you have created a conductive path between two points that disagree about what zero is. Current flows through the signal wiring to equalize them, and that current is superimposed on your measurement.

How to recognize one

SymptomPoints toward a ground loop when
Reading noisy or wanderingNoise appears or worsens when a nearby drive or motor runs
Fixed offset errorThe instrument reads correctly on a bench but not when installed
Error changes with weatherWet soil changes ground resistance and shifts the reading
Multiple loops affected at onceSeveral signals from the same remote panel misbehave together
Improves when a wire is liftedDisconnecting one end of a shield changes the reading
Worse on long runsDistant panels have the largest ground potential difference

Finding it

  1. 1

    Characterize when it happens

    Trend the signal and correlate it against drive run status, motor starts, and time of day. A noise source that switches on and off is far easier to identify than one you observe only once.

  2. 2

    Measure potential between grounds

    With a meter on AC volts, measure between the panel ground bar and the ground at the far end of the circuit. Anything more than a few hundred millivolts is worth pursuing. Do this carefully and treat both points as potentially energized.

  3. 3

    Look for the second ground

    Trace the signal circuit end to end. Common culprits: shield landed at both ends, a transmitter case bonded to a grounded pipe while its signal common is also grounded, a surge protector referencing local ground, or a spare conductor bonded at a junction box.

  4. 4

    Test by removing, not by adding

    Lift the suspected second ground on the signal circuit and watch the reading. If it settles, you have found it. Never lift a protective equipment ground as part of this test.

  5. 5

    Confirm the fix under load

    The condition that caused the problem has to be running. A loop that is quiet with the drive stopped proves nothing.

Preventing it in design

  • Ground each cable shield at exactly one end, normally the panel end where the reference is established. Insulate and terminate the far end so it cannot contact anything.
  • Establish a single signal reference point per panel, and land analog commons there rather than at scattered points.
  • Keep instrument cable out of trays and conduits carrying drive output conductors. Cross at right angles where crossing is unavoidable.
  • Use twisted shielded pair for analog signals. The twist rejects magnetically coupled noise; the shield handles capacitive coupling.
  • Specify isolated analog input channels where the signal originates in a remote panel with its own ground system.
  • Use signal isolators on any circuit crossing between separately grounded structures.

Isolators

A loop isolator galvanically separates the input side from the output side, usually with an optical or transformer coupling, and passes the 4-20 mA value across without a shared conductive path. There is no ground loop because there is no continuous circuit.

Use one where the second ground cannot be removed: a transmitter bonded to a grounded process pipe, a signal arriving from another building, or equipment supplied by a vendor whose internal grounding you do not control. They are inexpensive relative to the time spent chasing an intermittent reading, and they should be on the standard bill of materials for any signal leaving the building.

Frequently asked questions

Should a cable shield be grounded at one end or both?
One end, for analog instrumentation signals, normally the panel end. Grounding both ends creates exactly the path this article is about. High-frequency network cabling follows different rules; do not apply this guidance to Ethernet.
Which end should the shield be grounded at?
The end where the signal reference is established, which for a loop-powered transmitter is the panel supplying the loop. Be consistent across the site and document it, because mixed practice is worse than either convention.
Can a ground loop damage equipment?
Usually it degrades a reading rather than causing damage. During a fault or a lightning event, however, the same path can carry very large current and destroy analog inputs. Surge protection and isolation on circuits leaving a building are worthwhile for this reason.
How do I tell a ground loop from induced VFD noise?
They often occur together and both correlate with drive operation. Induced noise couples into the cable and responds to routing, distance, and shielding. A ground loop responds to how many points the circuit is earthed at. Lift one shield end: if the reading settles, it was a loop.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.