The short answer
Short-Circuit Current Rating (SCCR)
The short-circuit current rating (SCCR) of an industrial control panel is the maximum fault current the assembly can withstand without creating a hazard, and it must be marked on the panel under NEC Article 409. It is determined by the lowest-rated component in the power circuit, following UL 508A Supplement SB. It is not the rating of the main breaker, and it must be equal to or greater than the available fault current where the panel is installed.
Key points
- SCCR is a property of the whole assembly, set by its weakest power-circuit component, not by the main disconnect.
- NEC 409.110 requires the SCCR on the panel nameplate; NEC 110.10 requires it to be adequate for the available fault current at the installation.
- Components without a marked rating are assigned low default values under UL 508A Supplement SB, which drags the panel rating down.
- Raising the rating means changing components or using a tested combination, such as a current-limiting fuse or breaker protecting a listed downstream device.
- The available fault current at the site is the number the panel rating is compared against, and somebody has to calculate it.
What the rating means
When a bolted fault occurs downstream of a panel, the current that flows for the few cycles before a protective device clears it is limited only by the impedance of the utility, the transformer, and the conductors. At a small site that might be a few thousand amperes. Close to a large transformer it can be fifty thousand or more. Every component in the power path of the panel has to survive that current for those cycles without exploding, arcing to the enclosure, or welding closed.
The short-circuit current rating is the assembly-level statement of what the panel can survive. It is expressed in kiloamperes, symmetrical RMS, at a voltage. A panel marked 10 kA at 480 V has been evaluated to withstand a 10,000 A fault at that voltage. Installed where the available fault current is 22,000 A, it is a code violation and a hazard, regardless of what the main breaker is rated to interrupt.
What the code requires
NEC Article 409 covers industrial control panels. Section 409.110 requires the panel to be marked with its short-circuit current rating, based on one of the listed methods, of which UL 508A Supplement SB is the one panel shops use. Section 110.10 requires that the overcurrent protection, the impedance, and the component short-circuit current ratings be selected so that a fault can be cleared without extensive damage to the electrical equipment, which is the requirement that the panel rating be adequate for the installation.
Section 110.24 requires service equipment to be field marked with the maximum available fault current and the date it was calculated. That marking, or the calculation behind it, is where the number to compare against comes from. Industrial machinery panels are covered by NEC Article 670 and NFPA 79, which carry equivalent marking requirements.
How the rating is determined
UL 508A Supplement SB gives the procedure. Reduced to its essentials: identify every component in the power circuit, find the short-circuit current rating of each, and the assembly rating is the lowest of them. The power circuit is everything from the incoming terminals through the disconnect, the branch protection, the contactors, overload relays, drives, terminal blocks, and the feeders to the loads. Control circuit components fed through a control transformer or a limited supply are generally excluded.
- 1
List the power-circuit components.
Disconnect, main overcurrent device, power distribution blocks, branch breakers or fuse holders, contactors, overload relays, soft starters, drives, power terminal blocks, and busbars.
- 2
Find each rating.
From the component listing or datasheet. Many components carry a marked SCCR that depends on the type and size of the protective device ahead of them; a contactor might be 5 kA on its own and 65 kA when protected by a specified class of fuse.
- 3
Apply the default where nothing is marked.
Supplement SB assigns default ratings to unmarked components by category. The defaults are low, in the range of a few kiloamperes for most categories, and a single unmarked terminal block can set the whole panel to that value.
- 4
Take the lowest.
The assembly SCCR is the smallest rating in the list. It is common for a first pass to land at 5 kA because of one component.
- 5
Raise it where needed.
Replace the limiting component with a higher-rated one, or protect it with a device it is listed in combination with. Current-limiting fuses and breakers let a downstream component be rated at the combination value rather than its standalone value, but only for the exact combinations that were tested.
Why the number is usually smaller than expected
People see a 65 kA breaker at the top of a panel and assume the panel is 65 kA. The breaker is; the panel is whatever the cheapest component in the power circuit is. Power distribution blocks, terminal blocks, and small drives are the usual culprits, and a general-purpose terminal block that was never evaluated for short circuit gets the default. A panel shop that does not do the calculation ships panels marked at the default, and a panel marked at the default is only legal at the small fraction of sites where the available fault current is that low.
| Component | Typical situation | What raises it |
|---|---|---|
| Power distribution block | Unmarked or marked at 10 kA | A block listed for higher SCCR, or a listed fuse combination |
| Power terminal blocks | General-purpose blocks with the default rating | Blocks with a marked SCCR for the wire size used |
| Contactor and overload | Low standalone rating, high combination rating | The specific fuse class or breaker the manufacturer tested with |
| Variable frequency drive | Rated with a specified fuse type and size | Using exactly that fuse, on the line side |
| Soft starter | Type 1 or type 2 coordination with a named fuse | Matching the coordination table in the listing |
| Main disconnect | Usually fine on its own | Rarely the limit |
Getting the available fault current
The panel rating is only meaningful against a number. The available fault current at the panel depends on the utility contribution, the transformer size and impedance, and the conductor length and size between the transformer and the panel. The utility will state its contribution at the service; the transformer nameplate gives the impedance; and a point-to-point calculation carries it down the feeders. Motors on the system contribute as well, briefly. The result is the number the panel rating must meet or exceed.
This calculation is engineering work and, where a stamp is required, it belongs to the engineer of record. A controls integrator should ask for it before designing the panel, because it is far cheaper to select 65 kA components at the start than to rebuild a 5 kA panel after inspection.
Frequently asked questions
- What SCCR do I need?
- At least the available fault current at the point where the panel is installed, from the calculation described above. Where that number is not yet known, designing to a common commercial value such as 65 kA at 480 V avoids the problem on most sites, at some cost in component selection.
- Does a 65 kA main breaker give the panel a 65 kA rating?
- No. The breaker can interrupt 65 kA. The panel rating is the lowest rating of any power-circuit component behind that breaker, and it is often far lower unless the components were selected for it.
- What is the default rating for unmarked components?
- UL 508A Supplement SB assigns defaults by component category, and for most categories they are a few kiloamperes. Any panel that contains one unmarked power-circuit component ends up at that default. The exact values are in the supplement and should be read from the current edition.
- Can the rating be raised after the panel is built?
- Sometimes, by replacing the limiting component or adding current-limiting protection in a listed combination, and the label must then be corrected. If the panel is UL listed, the change has to be made under the listing program, not just in the field.
Related topics
- UL 508A Industrial Control PanelsWhat the listing actually covers, what has to appear on the label, and the requirements that most often cause a panel to fail inspection.
- UL Standards for ControlsThe UL listings behind the components and the panels: UL 508A for industrial control panels and its SCCR supplement, UL 508 and UL 60947 for the components in them, UL 489 and UL 1077 for breakers and supplementary protectors, UL 248 fuse classes, UL 50 and 50E for enclosures, UL 698A for hazardous-location panels, and what a listing, a recognition, and a mark actually mean.
- NFPA Standards for ControlsThe National Fire Protection Association documents that reach into a control system: NFPA 70, the National Electrical Code, and the articles that govern panels, motors, and instrumentation; NFPA 70E for electrical safety at work; NFPA 79 for industrial machinery; NFPA 820 for wastewater plant hazardous area classification; and NFPA 110 where standby power meets the controls.
- UL 698AIndustrial control panels for hazardous locations: what UL 698A adds to UL 508A, a panel in a classified area or a safe-area panel with intrinsically safe circuits, barriers and isolators, the control drawing, and where utilities meet classified areas.
- NFPA 70 and the Control PanelThe National Electrical Code inside an industrial control panel: Article 409 and the listing it points to, the short-circuit current rating, overcurrent protection for control circuits, grounding and bonding, working space, and what an inspector asks.
- Enclosure SelectionChoosing the box: NEMA and UL 50 type ratings, materials for corrosive and outdoor sites, sizing for heat and wire bending space, and the details at the conduit entries and the door that decide whether the rating survives installation.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.