UL Standards for Controls

The UL listings behind the components and the panels: UL 508A for industrial control panels and its SCCR supplement, UL 508 and UL 60947 for the components in them, UL 489 and UL 1077 for breakers and supplementary protectors, UL 248 fuse classes, UL 50 and 50E for enclosures, UL 698A for hazardous-location panels, and what a listing, a recognition, and a mark actually mean.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

UL Standards for Controls

UL standards define the safety requirements that products and panels are tested against, and a UL listing is the evidence an inspector accepts that equipment is safe for its intended use. For control systems the central document is UL 508A, the standard for industrial control panels, under which a panel shop builds and labels panels using listed and recognized components: breakers to UL 489, fuses to UL 248, enclosures to UL 50, contactors and starters to UL 508 or UL 60947, and power supplies to UL 508 or UL 61010. A listed component may be used as intended; a recognized component may be used only in the conditions of its recognition; and the panel SCCR is calculated under UL 508A Supplement SB from those components.

Key points

  • UL 508A is the standard a panel shop builds to; the panel label is the evidence the inspector accepts.
  • Listed components are used as intended. Recognized components are used only under their conditions of acceptability.
  • UL 489 breakers protect branch circuits; UL 1077 supplementary protectors do not.
  • The SCCR of a panel comes from Supplement SB and the ratings of its components.
  • A mark from another nationally recognized testing laboratory to a UL standard is equivalent; the standard is what matters.

What UL is

Underwriters Laboratories writes safety standards and tests products to them, and it is one of several nationally recognized testing laboratories that OSHA accepts for that purpose. The NEC requires that much electrical equipment be listed, and the inspector looks for the mark of a recognized laboratory on the equipment and on the panel. UL standards are also American National Standards and are increasingly harmonized with IEC documents, which is why a UL 60947 contactor and an IEC 60947 contactor are the same device with two certificates.

Listing, recognition, and the mark

Listed
The product has been tested to the standard for its category and may be installed as intended by anyone, under the NEC, with no further evaluation. A listed breaker, a listed enclosure, a listed drive.
Recognized
The component has been evaluated for use inside other equipment, under stated conditions of acceptability, and is not for field installation on its own. Relays, terminal blocks, and power supplies are often recognized; the panel builder must use them within their conditions.
Classified
Evaluated for specific properties only, such as a fire rating.
The mark
The UL mark, or the mark of another recognized laboratory such as CSA, ETL, or TUV, applied to the product or the panel, is the evidence. A panel with a UL 508A label was built by a shop UL has authorized under its program, from components used within their listings, to the standard.

The standards a panel depends on

StandardCoversNote
UL 508AIndustrial control panelsThe panel standard: construction, spacing, wiring, marking, and Supplement SB for the short-circuit current rating; the UL 508A page
UL 508Industrial control equipmentThe legacy component standard for starters, contactors, relays, and controllers, being replaced by UL 60947 for switchgear and controlgear
UL 60947 seriesLow-voltage switchgear and controlgearThe harmonized IEC-based standard for contactors, starters, and related devices
UL 489Molded-case circuit breakers and circuit breaker enclosuresBranch circuit breakers; the circuit breakers page
UL 1077Supplementary protectorsNot branch circuit protection; the circuit breakers page
UL 248 seriesLow-voltage fusesThe fuse classes: 248-8 for Class J, 248-4 for Class CC, 248-12 for Class R; the fuses page
UL 50 and UL 50EEnclosures for electrical equipmentConstruction and environmental type ratings, the NEMA types; the enclosure selection page
UL 698AIndustrial control panels relating to hazardous (classified) locationsPanels with intrinsically safe circuits or purged and pressurized enclosures for classified areas
UL 61010-1 and UL 61010-2-201Safety of measurement, control, and laboratory equipment; control equipmentThe listing basis for many controllers, power supplies, and instruments
UL 1449Surge protective devicesThe type 1, 2, 3, and 4 SPD ratings used in panels and at services
UL 1012 and UL 1310Power units and Class 2 power unitsOlder power supply listings; Class 2 outputs that permit power-limited wiring
UL 508C and UL 61800-5-1Power conversion equipment; adjustable speed drivesDrive listings and their SCCR conditions
UL 1059Terminal blocksUse groups and ratings; the terminal blocks page
UL 497 seriesProtectors for communication circuitsSignal and data line surge protection listings

How a panel shop uses them

  1. 1

    Select listed components

    Every component in the power and control circuits is listed or recognized to the applicable standard, and the panel shop keeps the certificates. A component with no listing may not be used in a listed panel, whatever its quality.

  2. 2

    Use them within their conditions

    A recognized relay has conditions of acceptability, a maximum ambient, a mounting orientation, a spacing; the panel is built to them. A drive listed with specific upstream fuses is protected by those fuses.

  3. 3

    Build to UL 508A

    Spacings between live parts, wire sizes and colors, wireway fill, bonding, control transformer and power supply protection, and the marking requirements are in the standard, and the shop follows a procedure UL audits.

  4. 4

    Calculate the SCCR

    Under Supplement SB, from the component ratings and the published combinations, as the SCCR page describes, and mark it.

  5. 5

    Label the panel

    The UL 508A label with the shop file number, the SCCR, the voltage and current ratings, and the enclosure type. The label is what the inspector reads.

Reading a certificate

The UL online certification directory lists every listed and recognized product by category code, file number, and model, with the standard and, for recognized components, the conditions of acceptability. A panel shop looks up the components it uses; an engineer reviewing a submittal looks up what the vendor claims. A product that is not in the directory is not listed, whatever the catalog says.

Frequently asked questions

Is a panel built by an electrician in the field a UL 508A panel?
No. UL 508A panels are built by shops authorized under the UL program and labeled with the shop file number. A field-assembled panel is inspected by the AHJ as an installation and may be required to have a field evaluation by a laboratory before it is accepted. Many jurisdictions require the UL 508A label for any industrial control panel.
Can I use a component with a CSA or ETL mark in a UL 508A panel?
Yes, if it is certified to the applicable UL or harmonized standard by a recognized laboratory. The standard and the certification are what matter, not which laboratory issued them. The panel shop records the certificate.
What is the difference between UL 508A and UL 698A?
UL 508A is for industrial control panels in ordinary locations. UL 698A adds the requirements for panels that connect to intrinsically safe circuits in hazardous locations, or that are purged and pressurized to sit in one. A lift station panel with intrinsically safe barriers for the wet well floats may be built under 698A.
Does a UL listing mean the equipment will work?
It means the equipment met the safety requirements of the standard in the tests. Performance, accuracy, and suitability for the application are not part of a safety listing. A listed transmitter can still be the wrong transmitter for the job.