Three-Phase Power Calculator
Apparent, real, and reactive power from line voltage, line current, and power factor, or the current a given load will draw.
Calculated reference results
- Apparent power
- 54.04kVA
- Real power
- 45.93kW
- Reactive power
- 28.47kVAR
- Real power
- 45,934W
- Approximate mechanical output
- 57.26hp
At 93.0% efficiency. A rough figure, not a motor rating.
The arithmetic
- Constant = 1.732 (three phase)
- kVA = 1.732 x 480 V x 65.0 A / 1000 = 54.04 kVA
- kW = 54.04 kVA x 0.85 power factor = 45.93 kW
- kVAR = sqrt(54.04 squared - 45.93 squared) = 28.47 kVAR
What this does not account for
- Assumes a balanced three-phase load. An unbalanced load needs to be evaluated per phase.
- Power factor varies with load. A motor at 30% load has a much worse power factor than the nameplate figure.
- The mechanical output figure is an estimate from electrical input and an assumed efficiency. It is not a substitute for the motor nameplate.
How this is calculated
For a balanced three-phase load, apparent power in kVA equals 1.732 multiplied by line voltage, multiplied by line current, divided by 1000. Real power in kW is that figure multiplied by the power factor. Reactive power in kVAR is the square root of kVA squared minus kW squared.
Formulas
kVA = (1.732 x V_line x I_line) / 1000
kW = kVA x power factor
kVAR = sqrt(kVA squared - kW squared)
Assumptions and limitations built into this calculator
- Balanced three-phase load with sinusoidal waveforms.
- Line-to-line voltage and line current.
- Ignores harmonic distortion, which inflates apparent power on drive-heavy systems.
Frequently asked questions
- Should I use line or phase voltage?
- Line-to-line voltage with line current, which is what the 1.732 constant assumes and what you measure at the panel.
- Why does my drive-fed motor not match this?
- A variable frequency drive draws non-sinusoidal current. Harmonic content raises the apparent power without raising the real power, so displacement power factor and true power factor differ and this formula understates the loading.