Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
ReferenceWaterFlowInstrumentationControlSCADA

Raw Water

Controlling the front of a surface water plant: intake and screens, low-lift pumping, the raw water flow that paces the whole plant, the online quality instruments that warn of a changing source, and the alarms and ramp limits that keep the train stable.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Raw Water

Raw water control sets the plant production rate and delivers it steadily: the low-lift pumps and a flow control valve or drive hold a raw water flow setpoint that comes from the clearwell level or a production schedule, and that flow is the master signal for chemical flow pacing downstream. Raw water turbidity, pH, temperature, and conductivity are monitored continuously because a change in the source is the earliest warning the plant gets, and screen differential, intake level, and gate positions protect the intake. Flow changes are ramped rather than stepped so that coagulation and filtration see a stable load.

Key points

  • Raw water flow is the plant flow; nearly every chemical feed and every filter loading is paced from it.
  • The setpoint comes from the clearwell: falling level raises production, rising level lowers it, within ramp limits.
  • Online raw turbidity, pH, temperature, and conductivity are the early warning; alarm on rate of change, not only on limits.
  • Intake level, screen differential, and gate position protect the pumps and the structure.
  • A treatment train likes steady flow; ramp changes over minutes and stage pumps with the flow controller, not against it.

What the raw water system does

A surface water plant draws from a river, lake, or reservoir through an intake structure, screens it, and pumps it to the head of the treatment process with low-lift pumps. The rate at which it does that is the plant production rate. Every process downstream is sized and paced for it: the coagulant dose is a ratio to it, the flocculation and sedimentation basins have detention times that depend on it, the filters have loading rates set by it, and the disinfection contact time is computed from it. Controlling raw water well means delivering the rate the plant needs, changing it slowly, and knowing what is in it.

Flow control

The plant flow setpoint usually comes from finished water storage: the clearwell level, or the level of the distribution tanks that the clearwell feeds. Falling level calls for more production, rising level for less, within a band that keeps the plant running at a few discrete rates rather than hunting. Many plants run a production schedule instead, with operators setting a rate for the shift and the clearwell absorbing the difference. Either way, the raw water flow controller holds the setpoint with a control valve on the low-lift discharge, a drive on the pumps, or a combination, and the pumps stage up and down as the setpoint moves.

  • Ramp the setpoint. A step of 20 percent in raw water flow hits the flocculators and filters at once and shows up as a turbidity spike an hour later. Ramp at a rate the process engineer sets, often a few percent per minute.
  • Stage pumps by the controller output, not by flow alone. Start the lag pump when the lead is at maximum for a time and the flow is still below setpoint; stop it when the lead is at minimum for a time.
  • Protect the minimum flow. Filters have a minimum rate below which they do not work well, and some chemical feeds have a minimum. The controller has a floor.
  • Hold flow through a source change. Switching intake ports or wells changes the quality, not the rate; the flow controller keeps the plant steady while chemistry is adjusted.

Instruments

MeasurementWhereWhy
Raw water flowLow-lift discharge, magnetic meterPlant flow; the pacing signal for chemical feed and the basis of every rate
Intake or wet well levelIntake structurePump protection, screen submergence, and source level
Screen differentialAcross the traveling or bar screenScreen cleaning and blockage alarm
TurbidityRaw water sample lineSource quality; coagulant dose adjustment; storm and turnover warning
pH and alkalinityRaw water sampleCoagulation chemistry; alkalinity is usually a lab test
TemperatureRaw waterCoagulation and disinfection kinetics; seasonal changes
ConductivityRaw waterSource change, saltwater intrusion, and an easy continuous fingerprint
Gate and valve positionsIntake ports and isolationWhich port is in service; interlocks
Pump status, current, vibrationLow-lift pumpsStaging confirmation and protection

Watching the source

Raw water quality changes with storms, seasons, lake turnover, algae blooms, and upstream events, and the change usually arrives before anyone has seen it. The online instruments trend continuously on the SCADA system, and the useful alarms are on rate of change as well as on absolute value: turbidity that doubles in an hour is a storm plume arriving, whatever the number is. Operators respond by adjusting coagulant dose, changing intake ports where the structure allows drawing from a different depth, and slowing production so that the process has more time. A plant with several intake ports uses them deliberately: a deeper port during a bloom, a shallower one during turnover, and the port selection and its reason are recorded.

Protecting the intake

  • Low level: stop the pumps before they lose suction, and alarm early enough for the operator to reduce production first.
  • Screen differential: clean on a differential or a timer; alarm on high differential and on screen drive failure. A blinded screen starves the pumps.
  • Zebra mussel and biofouling control: chemical feed at the intake, paced to raw water flow, with feed failure alarms.
  • Ice and frazil: intake heating or port changes in cold climates, with temperature as the trigger.
  • Security: intrusion and door alarms on the intake structure, which is usually remote and unattended.

Frequently asked questions

Should the raw water flow follow the clearwell level automatically?
It can, with a slow controller and a ramp limit, and many plants do it. Others prefer the operator to set the rate for the shift so that the process is deliberately steady and the clearwell is allowed to swing. Either works; what does not work is a fast level loop that changes production every few minutes.
What is the earliest warning of a raw water quality event?
Usually turbidity rate of change, followed by conductivity for a source change and pH for an algae bloom. Upstream gauges and weather feeds, where available, come earlier still. Alarm on the rate and trend everything.
How much straight run does the raw water magnetic meter need?
The manufacturer figure, commonly five diameters upstream and two or three downstream, measured from the pump discharge or the nearest valve, and more after a pump. The raw water meter is the most important meter in the plant; give it a good installation and verify it against a clamp-on meter once a year.
What happens to chemical feed when the raw water pumps stop?
Every flow-paced feed should go to zero with the flow, and the feed pumps should be interlocked so that they cannot run without water flow. A feed pump that keeps dosing into a stopped pipe delivers a slug when flow resumes.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.