Biological Treatment

The biological process from the controls side: activated sludge and its common forms, conventional, extended aeration, oxidation ditch, sequencing batch reactor, and membrane bioreactor, and the alarms that give an operator time.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Biological Treatment

Biological treatment uses a population of microorganisms to consume the organic matter and the nitrogen in wastewater, and the controls exist to keep that population healthy and working: enough oxygen where it is needed and none where it is not, enough time in the system, the right amount of biomass, and the recycle streams that hold it all in balance. The forms differ in geometry and sequence, a conventional plant flows through zones, an oxidation ditch circulates, a sequencing batch reactor does everything in one tank by turns, a membrane bioreactor replaces the clarifier with membranes, but the variables are the same: dissolved oxygen, ammonia and nitrate, mixed liquor suspended solids, sludge age, and the return and waste sludge rates. The instruments that read them, the loops that act on them, and the sequences that time them are what a control system contributes; the process decisions, the sludge age target and the wasting plan, stay with the operators and the controls make them easy to carry out and hard to get wrong.

Key points

  • The controls hold oxygen, time, biomass, and recycle; the process forms differ in how those are arranged.
  • Dissolved oxygen is the fast loop, ammonia and nitrate the slow ones, sludge age the slowest; each has its instrument and its cadence.
  • Mixed liquor solids and sludge age are set by wasting, which the controls schedule and totalize from measured flow and solids.
  • Cyclic processes, sequencing batch reactors and oxidation ditch cycles, are sequences with timers, level, and analyzers deciding the phases.
  • Alarms are about trends: rising effluent ammonia, falling dissolved oxygen at full blower output, a rising sludge blanket.

Forms and what the controls do

FormArrangementWhat the controls run
Conventional activated sludgeAeration basins in series or zones, then clarifiersDissolved oxygen per zone, return and waste sludge, sometimes internal recycle
Extended aerationLong detention, low loading, often small plantsDissolved oxygen, wasting schedule, simple sequences
Oxidation ditchA loop channel with surface or diffused aerationAerator on and off or speed cycles for anoxic and aerobic periods, dissolved oxygen, return and waste
Sequencing batch reactorOne or more tanks that fill, react, settle, decant, and idle in turnThe phase sequence with timers, level, and analyzers; decanter control; wasting during settle or idle
Membrane bioreactorAeration basins with membrane tanks instead of clarifiersDissolved oxygen, membrane permeate flow and transmembrane pressure, air scour, backpulse and cleaning sequences, wasting
Biological nutrient removalAnaerobic, anoxic, and aerobic zones with recyclesZone dissolved oxygen, internal recycle on nitrate, return sludge, carbon and chemical feeds

The variables

Dissolved oxygen
Held by aeration control at a setpoint per zone, often one to two milligrams per liter in aerobic zones and near zero in anoxic zones; the fast loop, in minutes. Too much wastes energy and can hurt nutrient removal; too little stops nitrification.
Ammonia and nitrate
Read at the end of the aerobic zone and in the anoxic zone; they say whether nitrification and denitrification are complete, and they set the dissolved oxygen setpoints and the internal recycle in advanced control. Slow loops, in tens of minutes.
Mixed liquor suspended solids
The biomass concentration, read by a suspended solids probe or by laboratory; held by the wasting rate. Changes over days.
Sludge age
The average time solids stay in the system, computed from the solids inventory and the solids wasted per day; the operator target that decides nitrification. Changes over weeks.
Return activated sludge
The flow from the clarifier underflow back to the basin, often a ratio of influent flow, holding the biomass in the system and the sludge blanket down.
Waste activated sludge
The flow removed to solids handling, scheduled and totalized to hit the sludge age target.

SRT (days) = (V × MLSS) ÷ (Q_was × X_was + Q_eff × X_eff)

  • V = aeration volume; MLSS = mixed liquor suspended solids
  • Q_was, X_was = waste sludge flow and its solids concentration
  • Q_eff, X_eff = effluent flow and its solids; often small
  • The controller computes it daily from measured flows and solids, and the wasting plan targets it

Instruments

  • Dissolved oxygen probes, optical, one per control zone, cleaned by air blast and verified against a portable meter.
  • Ammonia and nitrate probes or analyzers at the zone ends where advanced control is used.
  • Suspended solids probes in the mixed liquor and the return sludge, verified against laboratory results.
  • Sludge blanket level in the clarifiers.
  • Flow on influent, return sludge, waste sludge, and internal recycle.
  • Oxidation-reduction potential in anoxic and anaerobic zones where the process is cyclic.
  • Air flow per zone and blower power for the aeration loop.

Sequences

A sequencing batch reactor runs a cycle of fill, react, settle, decant, and idle, with the phase changes driven by timers, by the tank level, and increasingly by analyzers that end the react phase when ammonia is gone and start decant when settling is complete. The sequence is a chart with a step for each phase, a timeout on each, a defined response to a high inflow that shortens the cycle, and a decanter that never opens with the mixers or the aeration running. An oxidation ditch cycles its aerators on and off, or between speeds, to alternate anoxic and aerobic periods, with the durations set by the dissolved oxygen and nitrate readings. A membrane bioreactor runs a permeate cycle with relaxation or backpulse and a maintenance clean on a schedule, all as sequences with interlocks on transmembrane pressure.

Alarms

  • Effluent or end-of-basin ammonia rising: nitrification failing; hours of warning.
  • Dissolved oxygen below setpoint with blowers at maximum: a load beyond the air supply, a diffuser problem, or a toxic event.
  • Dissolved oxygen high with blowers at minimum: over-aeration; a turndown limit or a diffuser or valve problem.
  • Sludge blanket rising in the clarifier: return sludge too low, a settling problem, or a hydraulic overload.
  • Mixed liquor solids drifting from target: the wasting plan is not being executed.
  • A sequence step past its timeout: a stuck batch reactor.
  • Membrane transmembrane pressure rising: fouling; clean before it is forced.

Frequently asked questions

Can wasting be automated?
The execution can: a waste pump run on a schedule to a computed daily volume from the sludge age target and the measured solids, with the total displayed and the operator approving the target. Many plants do it; the target remains a human decision.
What ends the react phase in a sequencing batch reactor?
A timer in simple designs; an ammonia or dissolved oxygen profile in advanced ones, which ends the phase when nitrification is complete and saves aeration. The timer stays as the limit.
How many dissolved oxygen probes does a basin need?
One per zone that has its own air control, placed where the reading represents the zone, usually toward the end of it. Two probes in one zone give a check on each other at the cost of a second probe to clean.
Why does the ammonia rise every morning?
The morning load arrives faster than the aeration control ramps, or the dissolved oxygen setpoint is too low for the peak, or the sludge age is at the edge of what nitrification needs in the current temperature. The trend against the influent flow says which.

Direct contact