The short answer
Lift Station Generator Operation
A lift station generator starts on utility failure, the automatic transfer switch moves the load to it after a short delay, and the pumps restart in a staggered sequence sized for what the generator can carry. The controls ride through the transfer on a UPS or by a defined restart, the generator status and transfer position are alarmed to SCADA, the set is exercised on a schedule under load, and stations without a permanent generator have a manual transfer switch and a receptacle for a portable set.
Key points
- The transfer switch, not the generator, decides when the station is on standby power. Alarm both.
- Stagger pump starts on the generator. Two motors starting together can stall a set sized for the running load.
- The PLC rides through the outage on a UPS or restarts cleanly. Either is designed, never assumed.
- Exercise under load, not just a no-load run. A generator that starts is not a generator that pumps.
- Stations without a generator need a manual transfer switch, a receptacle, and a documented time to overflow.
The sequence
- 1
Utility fails
The transfer switch senses loss of voltage on the utility source, waits a short delay to ride through momentary dips, typically one to three seconds, then signals the generator to start.
- 2
Generator starts
The set cranks, runs up, and reaches rated voltage and frequency. Ten to fifteen seconds is typical for a diesel set; the transfer switch waits until the generator source is within limits.
- 3
Transfer to generator
The switch opens the utility contacts and closes the generator contacts. Where the switch is open-transition, the station is dark for a fraction of a second. Where it is closed-transition, which is rare at lift stations, the sources are briefly paralleled.
- 4
Loads return
Control power is restored, the PLC boots or resumes, and the pump sequence restarts. The pumps that were running before the outage are called again, staggered.
- 5
Utility returns
The switch senses utility voltage, waits a return delay of several minutes so a brief return does not cause a transfer back and forth, then retransfers. The generator runs unloaded for a cooldown period and stops.
Every step has a timer, and every timer is a setting on the transfer switch or the generator controller that should be recorded. A retransfer delay that is too short causes repeated transfers during a flickering utility restoration; a start delay that is too long lets the well rise before the pumps come back.
Starting pumps on a generator
A generator has a limited ability to supply the inrush current of a motor start. A set sized for the station running load will stall, or trip on underfrequency, if two motors start together or a large motor starts across the line without margin. The controls therefore stagger the restarts.
- After transfer, the PLC delays the first pump start a few seconds to let the generator settle, then starts the lead, waits for it to reach speed and for the generator to recover, and only then allows the lag if the level calls for it.
- The delay between starts on generator power is longer than on utility power, and the program knows which source it is on from the transfer switch position input.
- Soft starters and drives reduce the inrush and let a smaller generator start a larger pump; the generator manufacturer sizing tool accounts for the starting method.
- Loads that are not needed during an outage, such as heaters and receptacles, can be shed by the PLC or by the transfer switch load management when on generator.
- On a generator with limited capacity, the program may hold the station to one pump and accept a higher level until utility returns. That decision is in the control narrative and is alarmed.
The controls during the transfer
Between the utility failing and the generator carrying the load, the station has no power for ten to twenty seconds. What the PLC and the instruments do during that gap is a design choice.
| Approach | Behavior | Note |
|---|---|---|
| UPS on control power | The PLC, the radio, and the level transmitter ride through; the program sees the transfer switch change state and manages the pump restarts; SCADA sees the whole event | The usual choice for a station with a permanent generator; the UPS needs to be sized for the transfer time plus margin, and its battery is a maintenance item |
| Clean restart | The PLC boots when power returns, initializes from retentive memory, and restarts the sequence; the transfer is invisible to it except by the power-cycle event | Acceptable where the program handles a restart deliberately: alternation state retained, timers reset, outputs off until the sequence decides |
| Float backup during the gap | Irrelevant during the gap, since there is no power; matters if the PLC does not come back | The float relay path is on control power and works as soon as the generator carries the load |
What SCADA should see
- Utility power available, from the transfer switch or a voltage monitor.
- Transfer switch position: normal or emergency. This is the alarm that says the station is on standby power.
- Generator running, from the set controller.
- Generator fault or fail to start, from the set controller, as a high priority alarm because the station is now on the utility clock with no backup.
- Fuel level, for diesel sets, with a low alarm that gives time for delivery.
- Battery charger and starting battery voltage, because a dead starting battery is the most common reason a generator does not start.
- Not in auto: the generator controller or the transfer switch left in a manual or off position after service.
Many generator controllers speak Modbus and provide all of this on one connection; the hardwired minimum is transfer position, generator running, and generator fault.
Exercise and maintenance
Standby generators are run on a schedule so that they start when needed. A weekly or monthly no-load exercise proves starting, and a periodic exercise under load, either by transferring the station to the generator or by a load bank, proves the set can carry the pumps. Diesel sets exercised only at no load suffer wet stacking, where unburned fuel accumulates in the exhaust. The transfer switch usually provides the exercise timer, and the PLC can log the run and alarm a missed or failed exercise. Fuel age, battery condition, coolant heaters, and the transfer switch contacts are the maintenance items that decide whether the set works on the day.
Stations without a permanent generator
Small stations often have no generator and rely on a portable set brought by the crew. The design then includes a manual transfer switch that isolates the utility and connects a generator receptacle, sized and labeled for the set the utility owns, and a documented time to overflow at typical and wet weather inflow, so the utility knows how long it has. The high-level alarm and the power failure alarm at such a station are what start the clock, and both must reach someone through a path that does not depend on station power: a cellular dialer with its own battery, or the SCADA radio on a UPS.
Frequently asked questions
- Why did the station overflow with the generator running?
- Usually one of three things: the generator ran but the transfer switch did not transfer, the pumps restarted together and the set stalled or tripped, or the PLC did not restart the sequence after the power cycle. The transfer position, the generator alarms, and the pump run statuses in the SCADA history show which. Each is found by a load test that was not done.
- How big should the generator be?
- For the running load of the pumps that must operate during an outage, plus the starting inrush of the largest pump with the others running, plus the station auxiliaries, using the generator manufacturer sizing tool with the actual starting method. A soft starter or a drive on the pumps can reduce the set size substantially. Sizing for all pumps starting together is the mistake that oversizes the set, and sizing for running load only is the mistake that stalls it.
- Should the PLC be on a UPS?
- At a station with a permanent generator, yes, sized for the transfer time and the radio, so the utility sees the event as it happens and the program controls the restart. Without a generator, a UPS keeps the alarms and the radio alive long enough to report the outage and the high level, which is the point.
- What is the retransfer delay for?
- A utility restoration is often unstable for the first minutes. The delay keeps the station on the generator until the utility has been steady for a set time, commonly five to thirty minutes, so the station is not transferred back and forth. It is set on the transfer switch and recorded.
Related topics
- Lift Station Backup ControlHow a lift station keeps pumping when the transmitter, the PLC, or the SCADA link is gone: float backup logic, the control transfer relay, redundant-off protection, and how to test it with the controller actually dead.
- Lift Station High LevelThe alarm that stands between a lift station and an overflow: where the high-level float goes, what it must do on its own, how much response time the well provides, and how to diagnose a high level that should not be happening.
- Lift Station Lead/Lag ControlHow a duplex or triplex station decides when one pump is enough and when it is not: the setpoint ladder, cycle volume, the lag call, parallel pumping, and what to do when the lead pump fails.
- Soft StartersReduced-voltage solid-state starters: how they ramp a motor, what they do for inrush, water hammer, and mechanical stress, where they beat a drive and where they do not, bypass contactors, and the settings that matter on a pump.
- Retentive MemoryWhat survives a power cycle in a controller and what does not, how retention is backed up by battery, capacitor, or nonvolatile storage, what should be retentive, and how retained data gets lost.
- Alarm Notification and CalloutGetting the alarm to the person on call when no one is watching the screen: notification paths, escalation, acknowledgment from the field, which alarms qualify, and the failure modes that leave a station in high level with nobody paged.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.