Symptom
A control fuse opens, is replaced, and opens again: immediately, on the next start of a particular device, at the next power-up, at random, or the next time it rains.
The short answer
Fuse Blows Repeatedly
A fuse that blows repeatedly is protecting the circuit from something real, and the pattern of when it blows says what: on energizing a particular output, a shorted coil or a ground fault on that circuit; on any power-up, transformer or solenoid inrush against a fast-acting fuse or an undersized rating; at random or with vibration, a chafed wire or a loose connection; when it rains, a wet field device; over weeks with no fault found, an overloaded circuit or a fuse holder heating from a loose contact. The fault is found by dividing the circuit at its branch fuses and terminals with the power off and an ohmmeter, or with the power on and the branches added one at a time, and it is fixed at its cause, never by a larger fuse.
Key points
- The timing of the failure is the diagnosis: on a command, on power-up, at random, in rain, or slowly.
- Divide the circuit: branch by branch with an ohmmeter to ground and between conductors, or energized one branch at a time.
- Check the fuse type and rating against the load: inrush needs a time-delay fuse of the right rating.
- A fuse holder that is warm has a loose contact that heats the fuse and opens it without a fault.
- A larger fuse is never the fix; it moves the failure to the wire.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Shorted coil on a relay, contactor, or solenoid | Fuse opens when that device is commanded. Measure coil resistance against the nameplate; a shorted coil reads very low. |
| Ground fault in field wiring or a field device | Fuse opens when the circuit is energized, often in wet weather. Ohmmeter from each field conductor to ground with the circuit isolated; divide at junction boxes. |
| Transformer or solenoid inrush against a fast-acting fuse | Opens at power-up or on energizing with no fault found afterward. Check the fuse class and rating against the transformer manufacturer table; use the time-delay type specified. |
| Overloaded circuit | Opens under peak load after minutes; loads added over the years. Clamp the circuit current with everything running and compare with the fuse rating. |
| Intermittent short from a chafed or pinched wire | Opens at random, with vibration, or when a door or cover is moved. Inspect the wiring at edges, covers, and where it enters devices. |
| Failed surge suppressor | A metal oxide varistor that has shorted after surges. Disconnect the suppressor and see if the fuse holds; replace it. |
| Loose fuse holder or terminal heating the fuse | The holder is warm or discolored; the fuse opens with no fault and normal current. Clean or replace the holder and torque the terminals. |
| Wrong fuse rating installed as a replacement | The rating on the drawing against the fuse in the holder; a smaller fuse from the wrong bin opens on normal load. |
| Heater, motor, or other load failing | A load whose current has risen with age or damage. Measure the load current against its nameplate. |
When does it blow
| Timing | Likely cause | First check |
|---|---|---|
| Immediately, every time | Solid short or ground fault | Ohmmeter across the circuit and to ground with the power off |
| When a particular output is commanded | Shorted coil or a fault on that branch | Coil resistance; the branch wiring |
| At power-up or energizing, then fine | Inrush against the wrong fuse type or rating | Fuse class and rating against the manufacturer table |
| After minutes or hours of running | Overload, or a loose connection heating the fuse | Circuit current; the temperature of the holder |
| At random, or when something is moved | Intermittent short | Inspect wiring at edges and under covers; wiggle test with the power off and an ohmmeter |
| In rain or after washing down | Ground fault in a field device or a box | Field branches to ground while wet |
| After a storm | Failed surge suppressor or a surge-damaged device | Disconnect the suppressor; check devices on the circuit |
Dividing the circuit
- 1
Isolate
Power off and locked out; the circuit disconnected from its source at the fuse.
- 2
Measure the whole
Ohmmeter from the load side of the fuse to the neutral or common, and to ground. A low reading confirms a short or a ground fault; a normal reading points at inrush, overload, or a heating holder.
- 3
Split
Open the branch fuses or lift the wires at the terminal strip so the circuit is in halves; measure each half. Keep splitting toward the low reading.
- 4
Find the device
Disconnect the device at the end of the low branch and measure it alone: a coil, a solenoid, a float, a heater.
- 5
Repair
Replace the device or the damaged wire, fix what caused the damage, and measure again before restoring the fuse.
- 6
Restore
The correct fuse type and rating per the drawing, and watch the circuit through a full cycle of operation.
Fuse type and inrush
A control transformer draws an inrush of many times its rated current for a few cycles when energized, and a solenoid or a contactor coil draws a pull-in current several times its holding current. A fast-acting fuse rated for the running current opens on that inrush, and the panel appears to have a fault that nobody can find. The transformer manufacturer publishes the fuse class and rating for each transformer size, and the answer is a time-delay fuse of that rating, which carries the inrush and still protects the transformer. The same applies to circuits that energize several coils at once.
Frequently asked questions
- The fuse blows only when the well pump starts. What is it?
- If the fuse is on the control circuit, the pump start energizes a contactor coil that has shorted or a circuit with a ground fault, or the start drags the control voltage down enough that several coils draw pull-in current together. Measure the coil, then the branch to ground, then the control voltage during the start.
- The megger shows nothing wrong but the fuse keeps blowing.
- Then the fault is not a steady short: inrush against the wrong fuse, an overload that develops under load, a loose holder heating the fuse, or an intermittent short that the ohmmeter did not catch at rest. Check the fuse type, clamp the running current, feel the holder, and wiggle the wiring with the meter connected.
- Can I use a breaker instead?
- A supplementary protector or a breaker of the correct rating and curve can replace a fuse where the design allows and the short-circuit rating permits, and it makes resetting easier, which is exactly why the cause still has to be found first. Repeated resets of a breaker into a fault are as bad as repeated fuses.
- The fuse holder is discolored. Is that the cause?
- Often. A holder whose contacts have lost tension heats the fuse under normal current until the element fatigues and opens, and the discoloration is the evidence. Replace the holder, torque the terminals, and the fuse stops blowing.
Related topics
- Fuses in Control PanelsFuse classes, time-delay and fast-acting types, current limitation and what it does for the panel short-circuit rating, semiconductor fuses for drives, control circuit and DC fusing, and the habits that make a blown fuse a diagnosis instead of a mystery.
- Ground FaultsGround faults in and around control panels: what happens on grounded 120 VAC circuits, on grounded and ungrounded 24 VDC systems, and on drive outputs; where they hide, from chafed wire to flooded boxes; and the divide-and-conquer method that finds them.
- Ground Fault PresentThe ground fault indicator is on, the monitor alarms, or a fuse opens when a field circuit is energized: how to find which conductor touches ground and where, by dividing the circuit with the monitor or an insulation tester, and where faults hide.
- No Control Power in PanelThe panel is dead: no pilot lights, no controller, no HMI. The order of checks from the disconnect through the control transformer and its fuses, the control breaker, the emergency stop chain, and the DC supply, with the readings that locate the break.
- Control RelaysThe interposing and logic relays in a control panel: why a controller output drives a relay instead of a starter coil, contact ratings and the difference between resistive and inductive loads, coil suppression, ice cube relays versus terminal relays versus solid-state, and the failure modes that make a relay the first suspect in a dead circuit.
- Surge Protection for Signal CircuitsProtecting 4-20 mA loops, discrete inputs, network cables, and radio feeds from lightning and switching surges: where surges enter, the device types and how they clamp, the grounding that makes them work, the resistance and capacitance they add, and where to put them at a remote site.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.