Ground Faults

Ground faults in and around control panels: what happens on grounded 120 VAC circuits, on grounded and ungrounded 24 VDC systems, and on drive outputs; where they hide, from chafed wire to flooded boxes; and the divide-and-conquer method that finds them.

10 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Ground Faults

A ground fault is an unintended connection between an energized conductor and ground. On a grounded 120 VAC control circuit it blows the fuse or trips the breaker immediately, which at least says where to look. On a grounded 24 VDC system a fault on the positive side blows a fuse; on an ungrounded system the first fault causes no symptom at all and the second one shorts the supply. A drive detects a fault on its output and trips. Faults hide where insulation meets metal or water: chafed wire at an enclosure edge, a pinched conductor under a cover, moisture in a float switch, a flooded conduit or junction box, a wet motor. They are found by dividing the circuit with fuses and disconnects until the fault is in one branch, and by insulation testing only after the electronics are disconnected.

Key points

  • Grounded circuit: the fault clears a fuse and announces itself. Ungrounded circuit: the first fault is silent, and a monitor is the only warning.
  • Divide and conquer: pull fuses and disconnect branches until the fault is in one, then follow the wire.
  • Water is the usual cause in the field: floats, junction boxes, conduits, motors. Chafing is the usual cause in the panel.
  • Insulation testers destroy electronics; disconnect controllers, drives, and transmitters before applying test voltage.
  • A ground fault that comes and goes with rain, level, or vibration is still a ground fault; find it before it becomes a short.

What happens depends on the system

SystemFault onWhat happensHow you find out
120 VAC control circuit, grounded neutralHot conductorFault current returns on the ground; fuse or breaker opensBlown control fuse, tripped breaker, loss of control power
24 VDC, common bonded to groundPositive conductorFault current returns on the ground; supply fuse or branch fuse opens, or the supply current-limitsBlown DC fuse, supply in overload
24 VDC, common bonded to groundCommon conductorNothing; the common is already at groundNot visible; a second fault on a positive then shorts
24 VDC, ungroundedEither conductorNothing on the first fault; the system is now effectively grounded on that sideGround fault monitor alarm, or a mysterious short when the second fault occurs
Drive outputMotor lead or windingDrive detects output current imbalance and trips on ground faultDrive fault code
480 V feeder to the panelPhase conductorBreaker trips on fault current or on ground fault protection where fittedTripped feeder breaker

Where they hide

Enclosure edges and cutouts
A conductor pulled through a knockout without a bushing, or resting on a sharp edge, chafes through with vibration and thermal cycling. Look at every entry.
Under covers and mounting plates
A wire pinched when a wireway cover or a sub-panel was reinstalled. The fault appeared the day after the work.
Float switches and submersible devices
Cable jackets crack, seals fail, and water reaches the conductors. The fault comes and goes with level.
Junction boxes and conduits
Condensation and flooding fill boxes and low points in conduit; the fault follows the weather.
Motors and heaters
Winding insulation fails from age, heat, or moisture; a motor that has sat wet faults on the first start.
Solenoid valves and coils
Coil insulation breaks down, often after an overvoltage or from heat in a dead-headed valve.
Field devices with metal housings
A transmitter or switch whose wiring touches the housing inside the terminal compartment.
Temporary and abandoned wiring
A conductor left energized and capped, or not capped, in a box somebody forgot.

Finding a fault on a grounded circuit

  1. 1

    Confirm the fault

    With the circuit de-energized and locked out, measure resistance from the faulted conductor to ground. A low reading confirms a fault; a normal reading with a blown fuse means an overload or a short between conductors instead.

  2. 2

    Divide the circuit

    Pull the fuses or open the disconnects that split the circuit into branches, and measure each branch to ground. The fault is in the branch that reads low. Keep dividing: field wiring from panel wiring, one device from the next, until one conductor between two points reads low.

  3. 3

    Follow the conductor

    Inspect the path of that conductor for the places above. Water and chafing account for most faults; look for them first.

  4. 4

    Check the device at the end

    Disconnect the device and measure it alone to ground. A coil, a float, a heater, or a motor that reads low is the fault.

  5. 5

    Repair and verify

    Replace the damaged cable or device, protect the path that caused the damage, and measure to ground again before restoring the fuse. Then energize with the branch isolated first.

Finding a fault on an ungrounded DC system

An ungrounded 24 VDC system gives no fuse to follow. A ground fault monitor, which measures the resistance of each pole to ground continuously, alarms on the first fault and shows which pole. Without one, the fault is found by measuring the voltage from each pole to ground: on a healthy floating system both read some wandering intermediate value; with a fault on one pole, that pole reads near zero to ground and the other reads the full supply voltage. The faulted pole is then divided by pulling branch fuses one at a time and watching the reading return to normal. Intermittent faults are found by leaving the monitor in place and logging when it alarms against level, rain, and equipment operation.

Drives and ground faults

A drive trips on ground fault when the sum of its three output currents is not zero, which means current is leaving through a path other than the motor leads. A real fault in the motor or cable is found by disconnecting the motor at its terminal box and testing the cable and the motor separately with an insulation tester. A nuisance trip comes from the leakage current of a long shielded motor cable, from an output filter, or from moisture in a motor that will clear when the motor is run warm; the drive manual describes the settings and the cable limits. A drive that trips on ground fault at the first start after a wet period, and runs after the motor is dried, has told you the motor needs attention.

Preventing them

  • Bushings on every knockout and grommets on every edge a conductor crosses.
  • Conductors dressed away from covers and mounting plates, and covers checked for pinched wires before they are closed.
  • Drains in low points of conduit and in junction boxes that can collect water; sealed fittings where the code requires them.
  • Submersible cables inspected on a schedule and replaced when the jacket shows cracking.
  • Ground fault monitors on ungrounded DC systems, with the alarm on the HMI.
  • Insulation testing of motors and long cables on a schedule, trended, so the fault is predicted rather than found.

Frequently asked questions

The control fuse blows only when it rains. What is that?
A ground fault in a field device or a junction box that fills with water. Divide the circuit during the rain, or measure each field branch to ground while it is wet, and expect to find a float switch cable, a box without a drain, or a conduit low point.
Should the 24 VDC common be grounded or not?
Either is permitted. Grounded systems make faults visible immediately by blowing a fuse and keep every signal at a known reference. Ungrounded systems tolerate a single fault and keep running, which some plants prefer for critical circuits, but only with a ground fault monitor and a policy of fixing the first fault promptly. Choose one for the plant and apply it consistently.
The insulation tester shows a low reading but the circuit works. Is it a fault?
A reading of a few megohms on a long field circuit with older cable is normal deterioration; a reading in the kilohms is a fault waiting for enough voltage or moisture to become a short. Trend the readings; a value that falls each year is the cable telling you when to replace it.
Can a ground fault on one circuit affect another?
On a grounded system the fault current returns through the ground conductors and can raise the potential of the grounding system enough to disturb instrument signals while it flows. On an ungrounded system a fault on one pole effectively grounds that pole for every circuit on the supply, and a second fault anywhere on the other pole shorts the whole supply. Both are reasons not to leave a known fault in place.

Direct contact