Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
TroubleshootingTroubleshootingGroundingPanelsPowerPLC

Floating Reference Between Panels

Signals between two panels that misbehave because the panels do not share a DC reference: inputs that never turn on or half turn on, strange voltages to ground, and noise that comes and goes. How DC commons should be bonded and how to cross a panel boundary.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

Symptom

An input in one panel driven from another panel never turns on, turns on with a meter reading of a few volts across it, flickers, or turns on when nothing is commanded; voltage from a DC common to ground reads a strange value that changes when things are touched; a signal that worked on the bench fails in the field.

The short answer

Floating Reference Between Panels

A signal wired from one panel to another only works if both ends agree on where zero volts is. When each panel has its own 24 VDC supply and the commons are not connected, or one common is bonded to ground and the other floats, a discrete signal from one panel has no return path into the other, and an analog signal reads an offset equal to whatever potential the floating common has drifted to. The reliable fixes are to bond each supply common to its panel ground at one point so the earth is the shared reference for discrete signals, to carry a dedicated common conductor with the signal wires, and to cross the panel boundary with interposing relays for discrete signals and isolators or single-ground current loops for analog signals.

Key points

  • A discrete signal needs a return path. Two panels with separate supplies and no common connection have none.
  • A floating DC common drifts to whatever leakage sets; half-voltages and phantom inputs are the result.
  • Bond each supply common to the panel ground at one point, or bond none and monitor for ground faults; do not mix.
  • Interposing relays are the standard way to cross a panel boundary with discrete signals.
  • Analog signals cross the boundary as a current loop with one ground, or through an isolator.

Possible causes and what to check

Possible causeWhat to check
DC commons not connected between the panelsMeasure resistance between the two DC commons with both supplies off. Open means no shared reference. Check each panel for a common-to-ground bond.
One supply common bonded to ground, the other floatingMeasure DC volts from each common to ground. The bonded one reads zero; the floating one reads a wandering value, often several volts.
Signal wired without a return conductorA single wire from a contact in panel A to an input in panel B, with no common wire in the same cable. The circuit relies on the earth or is open.
Shared common carried on an undersized wire that also carries load currentMeasure DC volts between the two commons with the loads running. A volt or more means the common wire is carrying return current for something else and shifting the reference.
Wetting voltage from panel A into an input referenced to panel BThe contact in A switches A 24 V into B input, which expects B 24 V relative to B common. Check which supply each side of the input is referenced to.
Common conductor open in a multi-conductor cableContinuity of the common conductor end to end; a broken common turns every signal in the cable into a floating one.
Ground path between panels of high impedanceBoth commons bonded, but the panels are in different buildings or the bonding conductor is corroded. Measure resistance and AC volts between the two panel grounds.

What floating means

A 24 VDC control supply has a positive and a common. If the common is bonded to the panel ground, every voltage in that panel is measured relative to earth, and two such panels share the earth as a reference. If the common is not bonded, the whole supply floats: the difference between positive and common is 24 V, but the voltage from either to ground is set by leakage through the supply, the loads, and cable capacitance, and it can sit anywhere from zero to a few tens of volts and wander. A floating system is legitimate and is used deliberately in some plants with a ground fault monitor, because a single ground fault does not trip anything. The trouble starts when one panel floats and the other does not, or when signals are wired between two floating panels as if they shared a reference.

Why the input does not turn on

A discrete input turns on when current flows through it from its positive terminal to its common. A contact in panel A that applies panel A 24 V to an input in panel B provides the positive side. The current has to return from panel B common to panel A common, and if there is no wire and no shared ground between them, there is no circuit. The input sits at a voltage the meter can see but that drives no current, or a tiny leakage current turns it partly on. The result is the classic symptom: 20 V across the input and the input is off.

Diagnostic procedure

  1. 1

    Draw the circuit

    Trace the signal from the contact or output in one panel to the input in the other, and note which supply powers each side. If the drawing does not show a return path, that is the problem.

  2. 2

    Measure each common to ground

    DC volts from each panel DC common to its panel ground. Zero means bonded. A wandering value means floating. One of each is a mismatch.

  3. 3

    Measure between the commons

    DC and AC volts between the two DC commons, with loads running. Zero means they share a reference. A steady offset means a return current is flowing through the connection. A wandering value means they are not connected.

  4. 4

    Test the input locally

    Jumper the input from its own panel 24 V. If it turns on cleanly, the input and the card are fine, and the problem is the reference.

  5. 5

    Check the cable

    Continuity of every conductor in the interpanel cable, including the common if one exists. A broken common looks like a floating panel.

  6. 6

    Decide the fix

    Bond the commons and add a return conductor, or add interposing relays, or add isolators, per the table below. Then re-measure the commons and confirm the input switches with a clean 24 V or 0 V across it.

Crossing a panel boundary

SignalRecommended methodWhy
Discrete status or commandInterposing relay in the sending panel; its dry contact is wetted by the receiving panel supplyEach side stays inside its own reference; a supply fault in one panel cannot reach the other
Discrete, both panels bonded to the same ground busDirect wiring with a common conductor in the same cableAcceptable within one building on one grounding system; the common wire carries the return, not the earth
4-20 mAOne loop, powered from one panel, grounded at one pointCurrent is unaffected by a reference difference as long as there is one ground
0-10 V or other voltage signalSignal isolator, or convert to 4-20 mAA voltage signal is measured against a reference, and two panels do not share one
Serial dataIsolated converterCommon-mode voltage between panels corrupts data and damages transceivers
Any signal between buildingsFiber, radio, or isolators on every conductorBuildings have separate grounds by design; copper between them carries the difference

Bonding the common

Where the policy is bonded, connect the common terminal of each supply to the panel ground bus with a short, sized conductor, once. Do not bond it again at a terminal strip or at a load; a second bond puts return current on the ground conductors. Mark the bond on the drawing so the next person does not remove it as a mistake or add another. Where several supplies share a panel and feed common circuits, bond them at the same bus so their commons are at one potential.

Frequently asked questions

Is it wrong for a 24 VDC supply to be ungrounded?
No. A control circuit at that voltage may be grounded or ungrounded. Ungrounded systems tolerate one ground fault and need a ground fault monitor so that the fault is found before a second one causes trouble. The fault is inconsistency: one panel grounded and another not, with signals wired directly between them.
Why did it work on the bench?
On the bench both panels were fed from one supply or sat on one bench ground, and the earth or the shared supply provided the return. In the field each panel had its own supply and its own ground, or a ground path of high impedance, and the return disappeared.
Can I just run a common wire between the panels?
For discrete signals within one building on one grounding system, yes, if the commons are bonded at one point each and the wire carries only the signal returns, not load current. The cleaner answer that also protects each panel from the other is an interposing relay per signal.
The input reads 12 V and is off. What is that?
The signature of a floating reference or an open return: the input sees a voltage through leakage but no current flows through it. Measure from the input common to the sending panel common; the wandering or offset voltage you find is the missing reference.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.