Terminals

Designing the terminal strips of a control panel: grouping by voltage and function, numbering that matches the drawings, fused and disconnect terminals for instrument loops, shield and ground terminals, spares, ferrules and torque, and the terminal schedule.

7 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Terminals

The terminal strips are where the panel meets the field, and their design decides how long every commissioning and every troubleshooting session takes. Terminals are grouped by voltage class and function, with power, 120 volt control, 24 volt discrete, analog, and network each on its own strip and each strip separated and labeled; every terminal carries a number that appears on the schematic and in the terminal schedule; instrument loops use fused or disconnect terminals so that a loop can be isolated and tested without lifting wires; shields land on their own terminals or a bar with a defined ground; and a fifth to a quarter of each strip is spare. The terminal schedule, which lists every terminal, its wire numbers, and what is on the other end, is the document that turns a cabinet of wires into something a technician can read.

Key points

  • Group strips by voltage class and function, and separate them physically and by label.
  • Number terminals to match the schematic and the terminal schedule; the number is the address of the wire.
  • Fused or disconnect terminals on instrument loops make testing possible without lifting wires.
  • Shields land on dedicated terminals or a bar with one defined ground point.
  • Reserve spares on every strip and record them in the schedule.

Grouping

StripContentsNotes
PowerIncoming supply, motor leads, and feedersSized for the conductors; barriers between phases where required; often power distribution blocks instead
120 volt controlControl transformer secondary distribution, field switches, and 120 volt outputsFused terminals for branch distribution; a neutral bar if the circuit is grounded
24 volt discreteField inputs and outputs at 24 voltsTwo-level or three-level terminals save space; commons on the lower level
AnalogLoop positive and negative, and the shieldFused or disconnect terminals, one per loop, with shield terminals alongside
Network and serialEthernet and fieldbusEthernet usually on patch panels or couplers rather than screw terminals; serial on shielded pairs
Intrinsically safeBarrier field sideSeparate, identified, and spaced per the control drawing
GroundEquipment grounds and shield drainsGround bars bonded to the enclosure; the instrument ground bar with its single bond

Numbering

Each terminal strip has a designation, typically the letters TB and a number or the voltage class, and each terminal a number within the strip. The schematic shows the strip and the terminal at every field connection, the wire number is on both ends of the wire, and the terminal schedule lists strip, terminal, wire number, device, and field destination. The convention is chosen once for the plant and used on every panel, so that a technician who knows one panel knows them all. Renumbering an existing panel is a project with a wire-by-wire check, and the reason to get it right at the start.

Instrument loops

A 4 to 20 milliamp loop lands on a pair of terminals with the shield beside them. A fused terminal on the positive side protects the loop supply and gives a place to isolate the loop; a disconnect or knife terminal on the negative side gives a place to open the loop for a meter in series or to insert a signal source, without lifting a wire. Test points on the terminal accept meter probes. A panel with plain terminals for its loops is a panel where every loop check means a loosened screw, and every loosened screw is a future intermittent.

Shields and grounds

  • Shield drains land on shield terminals or a shield bar, not on a signal terminal or a random ground screw.
  • The shield bar is bonded to the instrument ground bar, which is bonded to the enclosure ground at one point; the design drawing shows the point.
  • The shield is grounded at one end only, which for panel-to-field cables is the panel end; the field end is insulated and folded back.
  • Shield continuity through junction boxes is carried on a terminal, insulated from the box.

Workmanship

Ferrules
Stranded conductors get ferrules, crimped with the right tool, one conductor per ferrule unless a twin ferrule is used for a documented purpose.
One wire per terminal
Or two where the terminal is rated for it and the drawing shows it; jumpers use the terminal jumper bars, not extra wires.
Torque
Screw terminals torqued to the manufacturer value; spring terminals used where vibration or many connections argue for them.
Labels
Terminal markers on every terminal, strip designations on the end brackets, and wire labels readable at the terminal.
Spares
At least a fifth of each strip spare, labeled as spare in the schedule, and left empty.

Frequently asked questions

Screw or spring terminals?
Both are acceptable in a listed panel. Spring terminals are faster, vibration resistant, and need no torque check; screw terminals accept a wider range of conductors and are what many field electricians expect. Pick one per plant and use ferrules with either.
Where should the field wires land, on the terminal strip or directly on the I/O module?
On the terminal strip. Direct landing on a module saves terminals and costs every module replacement, every loop test, and every schematic that then has to show module terminals as field terminals.
How many spares?
A fifth to a quarter of each strip, plus a spare strip section in the wireway plan. Spares cost little at build and a great deal at retrofit.
Should I use multi-level terminals?
For discrete I/O, yes: a three-level terminal carries signal, common, and ground in one width, and the strip is a third the length. Label the levels and show them on the schematic; a three-level strip drawn as single terminals is a trap.

Direct contact