Networking

SCADA Polling Bandwidth

Bandwidth a polling scheme consumes across a set of remote sites, and whether the communication path can carry it.

Inputs

Request plus response plus protocol overhead. TCP adds roughly 40 bytes per packet.

Licensed radio is often 9.6 to 19.2 kbps. Cellular is far higher but usually metered.

Protocol overhead, retries, and headroom. Designing to 100% of a link does not work.

Calculated reference results

Required bandwidth
3.20kbps
Link utilization
16.7%

Against a 19.2 kbps link with 50% usable

Fits the link
Yes
Sites this link supports
120

At this interval and payload size

Data per day
34.6 MB
Data per month
1.04 GB

Relevant on a metered cellular plan, per site if each has its own SIM.

Per site, per month
25.9 MB

The arithmetic

  1. Bytes per second = 40 sites x 300 bytes / 30.0 s = 400.0 B/s
  2. Bits per second = 400.0 x 8 = 3,200 bps = 3.20 kbps
  3. Usable capacity = 19.2 kbps x 50% = 9.60 kbps

What this does not account for

  • Designing to the full link speed does not work. Protocol overhead, retries, and contention mean a path is effectively full well below its nominal rate.
  • Report by exception, where a site transmits only when a value changes beyond a threshold, uses a fraction of this bandwidth. It is why DNP3 suits distributed utilities better than continuous polling.
  • Alarm and event bursts during an upset are far above the steady-state figure, and that is exactly when the path matters most.
  • On cellular, the monthly figure drives cost. Keepalives, VPN overhead, and retries all add to it and are easy to overlook.

How this is calculated

Polling bandwidth is the number of sites multiplied by the bytes exchanged per poll, divided by the poll interval, converted to bits per second. On a constrained path such as licensed radio or a metered cellular plan, this figure decides whether the poll rate is achievable, and it is why report by exception suits distributed utilities better than continuous polling.

Formulas

kbps = (sites x bytes per poll / interval) x 8 / 1000

Assumptions and limitations built into this calculator

  • Uniform polling of every site at the same interval.
  • Payload size includes protocol overhead, which you supply.
  • Does not model retries, contention, or burst traffic.

Frequently asked questions

How fast should I poll a lift station?
Fast enough that an operator can act on a change, slow enough that the path stays healthy. Every fifteen to sixty seconds for analog values, with immediate reporting of alarms and state changes, is typical on licensed radio.