IP Subnet Calculator

Network address, broadcast, usable host range, and host count for an IPv4 address and prefix, with the notes that matter on a control network.

Inputs

Calculated reference results

Network address
192.168.10.0
Broadcast address
192.168.10.255
Subnet mask
255.255.255.0
Wildcard mask
0.0.0.255
Usable host range
192.168.10.1 to 192.168.10.254
Usable hosts
254

256 total addresses

CIDR notation
192.168.10.0/24
Address type
Private (RFC 1918)
Address is the network or broadcast
Usable host address

The arithmetic

  1. Address 192.168.10.45 as 32 bits: 11000000.10101000.00001010.00101101
  2. Mask /24: 11111111.11111111.11111111.00000000
  3. Network = address AND mask = 192.168.10.0
  4. Broadcast = network OR inverted mask = 192.168.10.255
  5. Host bits = 32 - 24 = 8, giving 256 addresses

What this does not account for

  • A device answering on a 169.254 address did not get a DHCP lease. On a control network that usually means a static address was expected and never configured.
  • Two devices with the same address produce intermittent, confusing symptoms on both. Check for ARP conflict messages before chasing anything else.
  • Sizing a subnet generously is cheap; renumbering a live control network is not. Leave room for the devices that will be added later.

How this is calculated

An IPv4 subnet is defined by an address and a prefix length. The prefix marks the network bits; the remaining bits address hosts. A /24 has 8 host bits, giving 256 addresses, of which 254 are usable because the all-zeros address identifies the network and the all-ones address is the broadcast.

Assumptions and limitations built into this calculator

  • IPv4 with classless addressing.
  • Assumes the network and broadcast addresses are not usable for hosts, which holds on ordinary equipment.

Frequently asked questions

How many hosts fit in a /24?
254. There are 256 addresses, and the first is the network address while the last is the broadcast address.
What does a 169.254 address mean?
The device asked for a DHCP lease, did not get one, and assigned itself a link-local address. It will not communicate with anything on the intended subnet.