Intermittent Radio Path

A site that drops and returns by the hour, season, or weather: thin fade margin, foliage, a new obstruction, a loosened antenna, coax taking water, a corroding connector, interference, or a marginal supply. How to trend signal against time and weather.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

Symptom

A site alternates between online and offline over minutes or hours; retries climb before it drops; the received signal strength wanders well below the commissioning value; the drops track rain, fog, morning hours, summer, or a time of day; the site is fine after a visit and degrades again.

The short answer

Intermittent Radio Path

An intermittent radio path is a path whose margin has shrunk until ordinary variation pushes it below the threshold: rain, fog, and temperature inversions fade the signal; leaves in summer absorb it; a new building or a grown tree line blocks part of the Fresnel zone; an antenna turned by wind or loosened on its mount points away from the far end; water working into the coax or a connector adds loss that grows with time; interference on the channel raises the noise floor at certain hours; and a site power supply that sags drops the radio output. The diagnosis is a trend of received signal strength and retry counts at both ends against time of day, weather, and season, compared with the commissioning record, and the fix follows the pattern: restore margin with height, gain, and low-loss coax, replace the wet coax or the corroded connector, realign the antenna, clear or route around the obstruction, or filter the interference.

Key points

  • Trend the signal and the retries against time, weather, and season; the pattern names the cause.
  • A path that was marginal at commissioning fails first; check the margin against the record.
  • Water in coax and corroded connectors add loss slowly; a return loss test finds them.
  • Foliage, new construction, and antenna movement change the path; look along it.
  • Interference that comes and goes shows as a raised noise floor at those hours.

Possible causes and what to check

Possible causeWhat to check
Insufficient fade marginThe received signal at commissioning against the receiver sensitivity: a margin under about 20 decibels fails in rain and inversions. Compute the link budget.
Seasonal foliageDrops in summer and recovers in winter; trees in the path. Raise the antennas above the tree line or reroute through a repeater.
New obstructionA step change in signal after construction, a new tank, or a tree that grew into the Fresnel zone. Look along the path from each antenna.
Antenna moved or looseSignal changes with wind; the mount is loose or the antenna has turned. Realign to the far end and secure.
Water in the coax or a connectorSignal degrading slowly over months, worse after rain; a return loss or standing wave ratio test shows high reflection. Replace the coax and weatherproof the connectors.
Corroded connector or arrestorIntermittent with vibration or temperature; visible corrosion. Clean or replace and weatherproof.
Intermittent interferenceThe noise floor at the receiver rises at certain hours; retries climb without a signal drop. Listen with the transmitter off; find the source.
Site power supply marginalThe radio output drops when the supply sags, on generator or with a weak battery. Measure the radio supply during transmit.
Temperature inversion or ductingDrops in the early morning in certain seasons on long paths over flat terrain or water. More margin or a different path.
Repeater or master antenna problemSeveral sites intermittent at once; the shared end. Check the master or repeater antenna system.

Trend it

Most telemetry radios report received signal strength and retry or error counts, and the SCADA can historize them per site like any tag. A week of that trend against the weather and the clock is the diagnosis: a signal that sags at dawn and recovers by mid-morning is an inversion; one that is lower every day in July than in January is foliage; one that stepped down on a date is an obstruction or a moved antenna; one that drifts down over months is water in the coax; retries that climb at 9 a.m. and 5 p.m. with the signal steady are interference from something that keeps business hours. The commissioning record gives the baseline; the trend gives the departure.

PatternLikely causeFix
Sags in rain, fog, or at dawnFade margin too smallHeight, gain, low-loss coax, a repeater
Worse every summerFoliageAntennas above the trees; a different path
Stepped down on a dateNew obstruction or antenna movedLook along the path; realign
Drifts down over monthsWater in the coax or a connectorReturn loss test; replace and weatherproof
Retries up, signal steady, at certain hoursInterferenceNoise floor measurement; filter or change channel
Drops when the site is on generator or the battery is lowPower supplyFix the supply; a UPS for the radio
Several sites at onceThe master or the repeaterThe shared antenna system

Checking the antenna system

  1. 1

    Inspect

    Connectors for water and corrosion; the weatherproofing; the arrestor; the coax for kinks, cuts, and crushed sections; the antenna for damage and alignment; the mount for looseness.

  2. 2

    Test the coax and antenna

    A standing wave ratio or return loss measurement at the radio end, compared with the commissioning value; a distance-to-fault sweep if the analyzer supports it finds where the water is.

  3. 3

    Measure the signal at both ends

    The site received signal from the master, and the master received signal from the site, compared with the record. A drop at one end only is that end antenna system or transmitter.

  4. 4

    Realign

    Directional antennas peaked on the far end with a signal reading, then secured.

  5. 5

    Replace

    Coax that has taken water is replaced, not dried; connectors are replaced and weatherproofed properly.

Interference

A path that loses data while the signal stays strong is being interfered with. The radio noise floor, measured with the far end silent, rises when the interferer is on; a spectrum analyzer or the radio diagnostic shows the frequency. Sources include another system on the same frequency, a nearby transmitter overloading the receiver, a drive or a lighting system radiating broadband noise, and a radio somewhere with a stuck transmitter. The fixes are a bandpass or cavity filter, a directional antenna that nulls the source, a channel change or a different hop set, and, for a licensed frequency, the coordination process.

Frequently asked questions

The path study said the link was fine. Why is it intermittent?
Path studies model a clear path with assumed antenna heights and coax; the installed antenna may be lower, the coax longer and lossier, the trees taller, and the margin smaller than modeled. Measure the actual received signal at both ends and compare with the study; the difference is where the margin went.
Can I just increase the transmit power?
Within the license or the unlicensed limit, a few decibels, which rarely closes the gap and can worsen interference to others. Antenna gain and height, and lower coax loss, add margin at both ends and are the usual answer.
How much fade margin is enough?
Twenty decibels is a common minimum for telemetry paths, thirty for paths over water or flat terrain prone to ducting, and more for long paths. The number is set in the path study against the availability the utility wants.
The site is fine every time I visit.
It is intermittent, and the visit is not at the bad time. The trend is the tool: leave the signal and retry counts historized and look at them against the times it fails. Then visit at that time, or with the evidence of what changed.