CISA Guidance as a Reference

How the federal cybersecurity agency publications serve as reference standards for a utility: the performance goals as a baseline for policy and procurement, the water sector goals, secure-by-design principles for vendors, and the advisories.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

CISA Guidance as a Reference

The federal cybersecurity agency publishes guidance that a utility can adopt as a reference standard: the cross-sector cybersecurity performance goals, a prioritized, numbered list of practices with cost and impact ratings that a utility can write into its policy as the baseline and into its specifications as requirements; the water and wastewater sector goals that map them to utility systems; the secure-by-design principles that state what a buyer should expect of a product, which belong in a procurement specification; and the advisories and the exploited vulnerabilities catalog that are the references a vulnerability management process cites. The goals are aligned with the institute framework and cross-referenced to it, so a utility that adopts them can report against the framework, and they sit beside the industrial standard series as the practical baseline where the standard series gives the design method.

Key points

  • The performance goals are numbered, prioritized, and rated; they can be cited in policy and in specifications.
  • The water sector goals say what each goal means for a utility; they are the version to hand to operations.
  • Secure by design is the list of what to demand of a vendor: no default passwords, logging, secure defaults, support commitments.
  • The advisories and the exploited catalog are the references for vulnerability decisions.
  • The goals cross-reference the institute framework, so adopting them is also progress against it.
  • The sector resources and services are covered on the cybersecurity resources page; this page is about citing the documents.

The performance goals as a baseline

The cross-sector cybersecurity performance goals are a set of practices grouped by the framework functions, each with an identifier, a statement of the outcome, a rating of cost, complexity, and impact, and a reference to the institute framework outcomes it supports. They were written for organizations that need a place to start and a way to prioritize, which describes most utilities. Because they are numbered and specific, they can be adopted as the utility baseline: the policy says the utility implements the goals, the annual assessment reports against each goal, and a procurement specification requires a vendor or an integrator to deliver systems that meet the goals that apply to them. The water and wastewater sector goals restate each goal in utility terms with examples, and are the document to give to operations and management.

Goal areaExamples of goalsWhere a utility applies it
Account securityChange default passwords; minimum password strength; unique credentials; revoke credentials of departing staff; separate user and privileged accountsThe password policy, the account lifecycle, the vendor account procedure
Device securityHardware and software approval process; asset inventory; prohibit connection of unauthorized devices; document network topology; secure log storageThe inventory, the third-party software policy, the network drawings, the log collector
Data securityLog collection; secure sensitive data; encrypt data in transitThe collector, the historian security, the VPN design
Governance and trainingA named security leader; basic training; improving incident response; vendor and supplier requirementsThe security owner, the training plan, the incident plan, the procurement clause
Vulnerability managementMitigate known exploited vulnerabilities; vulnerability disclosure; deploy security-by-design tools; no exploitable services on the internet; limit operational technology connections to the public internetThe advisory triage, the risk-based patching, the external scanning
Supply chainVendor incident reporting; vendor vulnerability disclosure; supply chain risk in procurementThe contract clauses
Response and recoveryIncident reporting; incident response plans; system backups; document network topology; recovery planningThe reporting list, the plan, the offline copies
OtherNetwork segmentation; detecting relevant threats; email securityThe zones and conduits, the monitoring sensor, the office side
The goal areas and representative goals; the current published list is the reference

Secure by design in procurement

The agency and its partners have published principles that describe what a secure product looks like from the buyer side: it ships without default passwords, it logs security events by default, it supports multi-factor authentication, its secure configuration is the default rather than an option, its vendor publishes vulnerabilities and fixes them for a stated support life, and its vendor takes ownership of the security outcomes of its customers. A utility writes those into its specifications for controllers, SCADA software, network equipment, and integration services, and asks the vendor to state how the product meets each. The principles do not replace the industrial standard series product requirements, which are more detailed; they are the short list a purchasing department can hold a vendor to.

The vulnerability references

  • The industrial control systems advisories: coordinated disclosures with affected versions, severity, and mitigations, cited in the utility vulnerability records by their identifiers.
  • The known exploited vulnerabilities catalog: the list a utility checks first, and the reference for the urgency tier in risk-based patching; federal agencies are directed to remediate entries by a due date, and utilities use the same dates as a benchmark.
  • Joint advisories with the federal investigative agency and other partners on threat actors targeting the water sector, which the threat landscape assessment cites.
  • The binding operational directives, which apply to federal agencies and are read by utilities as an indication of what the government considers urgent.

Citing beside the others

ReferenceRoleCitation use
Performance goalsThe practical baselinePolicy baseline; assessment checklist; specification requirements
Institute frameworkThe program structureThe annual assessment and the report to management
Institute operational technology guideThe control system design referenceDesign basis for segmentation and control adjustments
Industrial standard seriesThe design method and the vendor and product requirementsZone and conduit design; integrator and product requirements in specifications
Sector center fundamentalsThe water sector summaryOrientation and management communication
Environmental agency checklistThe regulator view of the same baselineThe assessment the regulator may inspect against

Frequently asked questions

Are the performance goals a standard?
They are voluntary guidance, not a standard in the formal sense, and they say so. They function as a baseline standard because they are specific, prioritized, and widely referenced, and a utility can adopt them as its own standard by policy, which is what makes them binding on the utility and its contractors.
How do the goals relate to the water infrastructure act assessment?
The act requires an assessment and a plan that address cybersecurity without prescribing a method. The sector guidance points to the goals and the environmental agency checklist as the way to do the cyber portion; a utility that assesses against the goals has the cyber content of its assessment.
Can we require a vendor to meet the goals?
The goals that apply to products and services can be written into a specification as requirements: unique credentials, no default passwords, logging, multi-factor support, vulnerability disclosure, and so on. The secure-by-design principles and the industrial standard series product requirements give more detail for the product itself.
Where are the services, the advisors, the scanning?
On the cybersecurity resources page for the agency. This page is about the documents as references; the services are how a utility gets help using them.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.