Default Credentials

The passwords printed in the manual: where they hide in a control system, why they are the first thing an attacker tries, how to find every one on site, and the procedure for changing them without locking yourself out.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Default Credentials

Default credentials are the factory usernames and passwords that ship on controllers, HMIs, switches, radios, drives, analyzers, and cameras, and they are published in every manual and collected in public lists. They are the most common way into a control system that is reachable at all. Removing them means inventorying every device with a login, changing each default with the new credential recorded in a managed store, verifying the change, and making the check part of commissioning so that new and replaced devices do not reintroduce them.

Key points

  • Every device with a web page, a console, or a protocol login shipped with a default. Assume it is still there.
  • Public lists index default credentials by vendor and model. An attacker does not need to guess.
  • Change them one device at a time, record the new credential in the store first, and verify before leaving.
  • Network switches, radios, and embedded web servers are the ones inventories miss.
  • Add the check to the commissioning checklist so a replaced device does not arrive with its defaults.

Why they matter

An attacker who reaches a device login page has two choices: try to exploit a vulnerability, or type the default. The default works often enough that it is tried first. Public databases list default credentials by vendor and model, scanning tools test for them automatically, and the exposure surveys of internet-reachable control devices find the same defaults year after year. A device on a control network with its default password is not protected by that password; it is protected only by whatever keeps the attacker off the network, and that is one layer where two were intended.

Where they hide

DeviceTypical default loginNote
Managed Ethernet switchesWeb and console management with a well-known admin accountOften installed by the electrical contractor and never touched; the management interface is on the control VLAN
Serial and cellular radiosWeb configuration pageVendor-installed; the same password across the whole fleet
PLC and RTU web serversDiagnostic and configuration pages enabled by defaultDisable the server if unused; change the password if used
HMI panelsRuntime login levels with default passwords, and a maintenance or engineering levelThe engineering level often has a documented default that lets a user exit the runtime to the operating system
Drives and soft startersKeypad parameter lock codes and network web pagesRarely changed; a lock code of zero is the default on many
Analyzers and smart instrumentsConfiguration menus and web interfacesAlso HART and other protocols with write protection off
SCADA softwareBuilt-in administrator accounts and default project usersThe installation guide lists them
Windows and Linux serversLocal administrator, service accounts created by installersVendor installers create accounts with documented passwords
Cameras, UPS cards, environmental monitors, power metersWeb managementEvery one has a network card and a login; most inventories miss them
SNMP community stringsPublic and private on nearly every network deviceA read-write community string is a password to the device configuration

Finding every one

  1. 1

    Start from the asset inventory

    Every device with a network address, and every device with a keypad or console login even without one. If the inventory does not exist, this is the reason to build it.

  2. 2

    Add the devices inventories miss

    Walk the panels. Switches, radios, cellular modems, UPS network cards, camera systems, power meters, and anything with an RJ-45 port.

  3. 3

    Identify the login surfaces on each

    Web page, console, SSH or Telnet, SNMP, vendor protocol, keypad lock. A single device may have four.

  4. 4

    Check each against the default

    Log in with the documented default. If it works, the device is on the list.

  5. 5

    Rank the list

    Devices reachable from outside the control zone first, then network infrastructure, then controllers and servers, then the rest.

Changing them

Changing a password on a device that runs a process is a change, and the risk of locking yourself out is real. The procedure is deliberate.

  1. 01Decide the new credential according to the password policy: unique per device, long, recorded in the credential store before it is set on the device.
  2. 02Confirm the recovery method for that device: a physical reset, a console port, a master password, a vendor procedure. Know it before changing anything.
  3. 03Change the credential, then log out and log back in with the new one. Do not trust the change until the new login has worked.
  4. 04Where the device supports named users, create them and disable the default account rather than only changing its password. A disabled account cannot be guessed.
  5. 05Change the SNMP community strings, or disable SNMP, on every network device. Treat a read-write community string as an administrator password.
  6. 06Record the change: device, date, person, the store entry, and the recovery method. Not the password itself, anywhere but the store.
  7. 07Update the anything that used the old credential: a SCADA driver that logs into a device, a monitoring tool that polls it, a backup script.

Keeping them changed

  • Add a default credential check to the commissioning checklist for every new and replaced device. A replaced switch arrives with its defaults.
  • Include the check in the periodic vulnerability review: scan for known defaults with a tool, on a schedule, from inside the control network.
  • Write the requirement into integrator and vendor contracts: no device is handed over with a default credential, and the credentials are delivered to the utility store.
  • When a person who knew credentials leaves, rotate what they knew. Named accounts make this a short list; shared credentials make it everything.

Frequently asked questions

The device only has one account and no way to disable it. What then?
Change its password, restrict which addresses can reach the device with a firewall or an access list, disable the interface if it is not needed, and record the limitation. Many older devices are in this category, and network restriction is the compensating control.
What if changing the password could break the SCADA connection?
It might, if the SCADA driver or a monitoring tool logs into the device with that credential. Find those dependencies first from the driver configuration, schedule the change with operations, and update the dependent configuration in the same window with a rollback ready.
Is a lock code on a drive keypad worth setting?
Yes, where the drive is in a location people other than trained staff can reach, and always on the network web interface. A keypad lock prevents a casual or mistaken parameter change; the network credential prevents a remote one.
How do we handle vendor default accounts in SCADA software?
Rename or disable the built-in administrator where the product allows, set a long unique password where it does not, and create named accounts for every person. Vendors document their built-in accounts; treat that documentation as a list of what an attacker knows.