Building an OT Asset Inventory

The list of everything in the control system with a network interface or a program, and how to build one that is right: what counts, the fields to record, the site walk, the switch tables and passive listening that find the rest, and keeping it current.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Building an OT Asset Inventory

An OT asset inventory lists every controller, remote unit, HMI, server, workstation, switch, firewall, radio, modem, drive, instrument, and appliance in the control system, with its make, model, serial number, firmware or software version, network addresses, location, role, owner, criticality, and support status. It is built by walking every site and opening every panel, because drawings are out of date and network scans miss what is serial or switched off, then checked against the switch address tables, the SCADA device list, and passive listening on the network, and it is kept current by making the inventory update a mandatory step of every change. It is the foundation for matching advisories to equipment, planning patches and firmware, knowing what to back up, and knowing what was touched in an incident.

Key points

  • If it has a network interface or a program, it is an asset, including the vendor box nobody remembers and the cellular modem in the enclosure.
  • Walk every site and open every panel; the drawings are the starting point, not the answer.
  • Cross-check with the switch address tables, the SCADA driver list, and passive listening; each finds what the others miss.
  • Record the fields that will be used: version for advisories, address for segmentation, criticality for priority, support status for replacement.
  • The inventory update is the closing step of every change record; an inventory without that habit is out of date in a year.
  • Start with what touches the network and what runs the critical processes; perfection comes later.

What counts

  • Controllers, remote terminal units, I/O adapters and remote racks, safety controllers.
  • HMI panels, operator workstations, engineering laptops, servers, virtual machines and the hosts under them.
  • Switches, routers, firewalls, wireless access points, media converters, serial-to-Ethernet gateways.
  • Radios, cellular modems, leased line modems, satellite terminals.
  • Drives, soft starters, and motor protection relays with communication ports.
  • Instruments and analyzers with Ethernet, fieldbus, or configurable interfaces; HART-capable transmitters.
  • Uninterruptible power supplies, power monitors, and generators with network cards.
  • Cameras, access control panels, intrusion systems on the control network.
  • Vendor appliances: remote support boxes, historian gateways, licensing servers, time servers.
  • Printers, and anything else with a cable into a control network switch.

The fields

FieldWhy it matters
Asset tag and descriptionThe name used on drawings and in the SCADA, so that everything cross-references
Site, building, panel, and positionWhere to find it, physically
Make, model, and part numberAdvisories and lifecycle notices are issued by model
Serial number and hardware revisionWarranty, recall, and the exact unit affected by a hardware advisory
Firmware, operating system, and application versions, with the date readAdvisories name versions; patch status starts here
Network addresses, MAC addresses, VLAN, and the switch port it connects toSegmentation, firewall rules, and finding it during an incident
Protocols and connectionsWhat it talks to and how; the basis of the conduit list
Role and process servedWhat stops if it fails
CriticalityA rating from the risk assessment that sets the priority for everything else
Owner and support contactWho decides about it and who to call
Support status and end of lifeWhen it must be replaced
Backup statusWhether a configuration or program backup exists and when it was taken
Physical securityLocked panel, locked room, fenced site, intrusion alarm
NotesDefault credentials changed, known issues, spares held

Building it

  1. 1

    Start from the paper

    The drawings, the IP schedule, the SCADA device list, the integrator handover documents, and the purchase records. Assemble a first list and expect it to be wrong in both directions.

  2. 2

    Walk every site

    Open every panel and every enclosure, including the ones at the well and the tank, and record what is there: nameplates, labels, firmware from displays, cables into switches. Photograph the panel interior. This is the step that finds the vendor modem and the unmanaged switch.

  3. 3

    Read the switches

    The address tables of every managed switch list every device that has talked through them, with the port. Compare with the walk; anything on a switch and not in the walk is found and identified.

  4. 4

    Listen

    A passive capture at the core switch shows who talks to whom with what protocol and often reveals firmware versions from the protocol identification. It confirms the connections and finds devices that were missed.

  5. 5

    Reconcile

    Every device found by any method is in the list once, with its fields filled from the best source. Unknown devices are traced to a cable and a purpose, or removed from the network.

  6. 6

    Rate criticality

    From the risk assessment: what the loss or compromise of each asset does to the process, on a scale the utility defines.

  7. 7

    Publish and protect

    The inventory is a sensitive document: it is the attacker map. It lives where the security documentation lives, with access control and a backup.

Keeping it current

Inventories are accurate the day they are finished and decay from then on. The habit that keeps them alive is the change record: no change closes without the inventory updated, and a like-for-like replacement of a failed module is a change record for exactly that reason. A quarterly comparison of the switch address tables with the inventory catches what the habit missed, and the annual walk of the sites, which is needed for other reasons, re-verifies the physical layer. Passive monitoring, where it is installed, alerts on a new address the day it appears.

What it is for

  • Matching security advisories to the equipment actually installed, by model and version.
  • Planning patches and firmware updates, and knowing what cannot be patched.
  • Knowing what to back up, and checking that it was.
  • Designing segmentation: the zones are drawn around the assets and their connections.
  • Answering the first questions in an incident: what is on this network, what does this address belong to, what did the compromised machine talk to.
  • Planning replacements before end of life rather than after failure.
  • Satisfying the risk assessment requirements that expect a utility to know what it has.

Frequently asked questions

Can we just scan the network?
Active scanning finds networked devices that answer and can crash older controllers and instruments that do not expect unsolicited traffic; it is used with care, on a schedule, with the process in a suitable state, and never as the first method. The walk finds what is not on the network or is switched off, and passive listening finds what is on the network without touching anything. Scanning is a supplement for the machines that tolerate it.
How long does the first inventory take?
A day per plant and an hour per remote site for the walk, plus a few days to reconcile, for a typical utility. It is the largest single effort in the first year of a security program and the one that pays back most, because everything else depends on it.
What about the devices with no network connection?
A standalone controller with a serial programming port is still an asset: it has a program to back up, firmware with advisories, and a panel someone can open. Include it, mark it as not networked, and it drops out of the segmentation work while staying in the backup and firmware work.
Who owns the inventory?
The control system owner, with a named person maintaining it. It is not an IT asset register, although the IT register may want a copy of the server entries; the fields and the criticality ratings are operational.

Direct contact