Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
ReferenceInstrumentationDesignWaterWastewater

Impulse Lines

The tubing between the process tap and the pressure or DP transmitter, and everything that goes wrong in it: slope and routing for liquid and gas, elevation head and how to correct for it, air and condensate, blocking and manifold valves, freezing, plugging on dirty service, and the diaphragm seal alternative.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Impulse Lines

An impulse line carries process pressure from the tap to the transmitter through a small tube, and it works only if the fluid in it is known and stable: full of liquid on liquid service, full of gas on gas service, with the same fluid at the same temperature in both legs of a differential transmitter. Lines slope so gas rises out of liquid legs and liquid drains out of gas legs, they are as short as practical, they have a manifold at the transmitter for isolation and zeroing, and where the process is dirty, freezing, or corrosive, they are replaced by diaphragm seals or purged. Most pressure and DP measurement problems are impulse line problems.

Key points

  • The line must be full of a known fluid. A bubble in a liquid leg or condensate in a gas leg is a false reading.
  • Liquid service: taps at the side or below center, lines sloping down to the transmitter. Gas service: taps on top, lines sloping up.
  • A transmitter above or below the tap reads the elevation head. Correct for it deliberately, once.
  • A manifold at the transmitter: block, equalize, vent, drain. Zero with the equalizer open.
  • Dirty, freezing, or corrosive service: diaphragm seals or a purge, not a longer line.

What the line does

A pressure transmitter measures the pressure at its own sensing diaphragm. The impulse line connects that diaphragm to the process tap, so that the pressure at the tap appears at the transmitter. If the line is full of the process liquid, the transmitter reads the tap pressure plus or minus the head of that liquid column between the two elevations, a fixed offset. If the line contains something else, air in a water line or water in an air line, the offset is unknown and changes. Every impulse line rule is about keeping the line full of a known fluid at a known elevation.

Routing by service

ServiceTap locationLine slopeTransmitter locationWhy
LiquidSide of the pipe, or below the centerline; never the bottom, where sediment collects, nor the top, where gas collectsContinuously downward from the tap to the transmitter, at least 1 in 12Below the tapGas bubbles rise back to the pipe; the line stays liquid-full
GasTop of the pipeContinuously upward from the tap to the transmitterAbove the tapCondensate drains back to the pipe; the line stays gas-full
SteamSide of the pipe, with a condensate potDownward to the transmitter from the potBelow the tap, with both legs filled to the same levelThe line is filled with condensate at a fixed level so the transmitter sees a known head
Dirty liquid, slurry, wastewaterSide, with a diaphragm seal at the tap, or a purgeNot applicable with a sealWherever convenientSolids plug an open impulse line

Where the ideal cannot be met, a liquid transmitter above the tap for instance, the line runs up to a high point with a vent, and the vent is used to bleed gas out at commissioning and on a schedule. It works, and it is a maintenance item; the ideal routing is not.

Elevation head

A transmitter mounted below its tap on liquid service reads the tap pressure plus the head of the liquid column between them; mounted above, it reads minus that head. The offset is fixed and it is corrected once, by a zero elevation or suppression setting in the transmitter, or in the controller scaling, and it is recorded on the loop sheet so that the next calibration does not remove it.

Offset = h × SG × 0.433 psi per foot

  • h = vertical distance from the tap to the transmitter diaphragm, in feet, positive when the transmitter is below the tap
  • SG = specific gravity of the fluid filling the line, 1.0 for water
  • 0.433 = psi per foot of water column

On a differential transmitter with both legs full of the same fluid and the transmitter at any elevation, the two heads cancel and no correction is needed; that is the reason both legs must be full of the same fluid at the same temperature. A leg that has partially drained or is warmer than the other has a different head, and the transmitter reads a differential that is not there.

The manifold

Two-valve, pressure
A block valve to isolate the transmitter from the process and a vent or drain to release the pressure and bleed the line. The minimum for a gauge pressure transmitter.
Three-valve, differential
Two block valves, one per leg, and an equalizing valve between the legs. Opening the equalizer with one block closed puts the same pressure on both sides for a zero check without removing the transmitter.
Five-valve, differential
Three-valve plus a vent or drain on each leg, for bleeding the legs and for calibration connections. The standard for DP flow.
Operation order
Into service on a DP: open the high-side block, close the equalizer, open the low-side block. Out of service: close the low-side block, open the equalizer, close the high-side block. The order prevents a full differential across the transmitter during the transition.

Problems and fixes

ProblemSymptomFix
Gas in a liquid legReading low or unstable; changes when the line is tapped; recovers after bleedingBleed; re-route to slope continuously; add a high-point vent if the route cannot slope
Condensate in a gas legReading high or drifting; worse in cold weatherDrain; re-route to slope up; add a drip leg and drain at the low point
Unequal legs on a DPStanding differential with no flow; zero shifts with temperatureBleed both legs; route them together; insulate them together
Plugged tap or lineReading slow or frozen; does not respond to process changesRod out or blow down; on dirty service, a seal or a purge
Frozen lineReading frozen in winter, often at full scale or zeroHeat trace and insulate; move the transmitter to a heated enclosure; a seal with a fill fluid rated for the temperature
Leak at a fittingReading low; wet fitting; on gas, hissingTighten or remake the fitting; check the tubing for damage
Line too longSlow response; more places for the other problemsShorten; move the transmitter to the tap
Wrong tap locationReads sediment or gas; noisy in turbulenceRelocate the tap to the side of the pipe, away from elbows and pumps

Diaphragm seals and purges

Where the process would plug, corrode, freeze, or contaminate an open impulse line, the line is replaced by a diaphragm seal: a flexible diaphragm at the tap, a capillary filled with a stable fluid, and the transmitter reading the fill fluid pressure. The process never enters the line. Seals bring their own rules: the fill fluid has a temperature and a specific gravity that affect the zero, the capillary length adds response time, and a damaged diaphragm is a transmitter that reads wrong without leaking. Alternatively, a purge of clean water or air flows continuously through the line into the process, keeping it clear; the purge flow rate is regulated and the pressure drop across the purge is part of the reading. Wastewater pressure and DP measurements are seal or purge applications almost without exception.

Frequently asked questions

Why does my DP flow meter read a flow at zero flow?
The two legs are not balanced: a bubble in one, condensate in one, one leg warmer than the other, or one partially drained. Close both blocks, open the equalizer, and check the zero; if it is off with the equalizer open, bleed the legs and repeat.
How long can an impulse line be?
As short as the installation allows, and rarely more than a few meters. Every meter adds volume, temperature effects, places for gas to collect, and response time. If the transmitter cannot be near the tap, a diaphragm seal with a capillary or a remote-mounted transmitter with a short line at the tap is better than a long line.
Should impulse lines be insulated?
Where they can freeze, yes, with heat tracing; where the two legs of a DP could reach different temperatures from sun or a nearby heat source, yes, together in one insulation. On a plain gauge pressure line indoors on water, no.
Can I use a pressure transmitter on a wastewater force main with an impulse line?
Not an open one; it plugs within days. A diaphragm seal flush-mounted at the tap, or a transmitter with an integral flush diaphragm and a full-bore isolation valve, is the standard. The seal is chosen with a diaphragm material for the service and a fill fluid for the temperature.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.