How a utility calibrates its instruments consistently: the as-found and as-left discipline, tolerance from the loop rather than the data sheet, the reference standard and its traceability, the five-point check with hysteresis, adjusting only when needed, intervals set from history, and the procedure written once per instrument type.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Calibration Procedures

A calibration procedure compares an instrument against a reference of known accuracy at several points across its range, records what it read before any adjustment, decides from a tolerance whether adjustment is needed, adjusts if so, records what it reads after, and files the result. The tolerance comes from what the loop needs, the reference is traceable and at least four times more accurate than the tolerance, the points include both directions to show hysteresis, and the interval is set from how the instrument has drifted in the past. Written once per instrument type and followed every time, the procedure is what makes a calibration record mean something.

Key points

  • As-found before touching anything. The as-found record is the reason to calibrate.
  • Tolerance is what the loop needs, decided before the test, not the accuracy on the data sheet.
  • The reference is traceable and at least four times better than the tolerance.
  • Five points, up and down. Adjust only when a point is out of tolerance.
  • Set the interval from the as-found history: extend it when the instrument passes, shorten it when it drifts.

Why a procedure

Calibration done differently by each technician produces records that cannot be compared: one adjusts every instrument to zero error, one checks two points, one uses a gauge that was last checked in the previous decade. The value of a calibration program is the history it builds, and the history is only useful if every entry was produced the same way. A procedure per instrument type, a page or two, followed by everyone, is the whole difference.

The elements

Tolerance
The maximum error acceptable for the loop the instrument serves, expressed as a percent of span or in engineering units. A wet well level for pump control may tolerate 1 percent; a compliance flow meter or a chlorine residual analyzer tolerates what the permit and the method allow. The tolerance is decided by the engineer and written on the instrument list before the first calibration. It is not the accuracy printed on the transmitter data sheet, which is what the instrument can do, not what the loop needs.
Reference standard
The calibrator, test gauge, or standard solution the instrument is compared against. It is traceable, meaning its own calibration is documented back to a national standard through an unbroken chain, and it is at least four times more accurate than the tolerance, ten times where practical. Its calibration due date is checked before use and recorded on the sheet.
Test points
Five points across the range, 0, 25, 50, 75, and 100 percent, applied increasing and then decreasing, so that hysteresis and linearity show. Three points for a simple loop where the procedure says so; more for a compliance instrument. Analyzers are calibrated at the points their method prescribes, usually one or two standards.
As-found
The readings at every point before any adjustment. This is the record of how the instrument had drifted since the last calibration, and it is what sets the interval and what a regulator reads.
The decision
If every as-found point is within tolerance, the instrument passes and is not adjusted. If any point is out, it is adjusted per the instrument procedure, zero and span or the sensor trim, and the points are repeated.
As-left
The readings after adjustment, or a copy of the as-found readings where no adjustment was made, with every point within tolerance.
The record
Tag, date, technician, reference standard and its due date, tolerance, as-found, as-left, adjustment made, pass or fail, and the next due date.

A procedure by type

InstrumentReferencePointsNotes
Pressure transmitterPressure calibrator or deadweight tester; milliammeter for the outputFive, up and downIsolate and vent; sensor trim and output trim separately; the pressure transmitter page
Level transmitter, hydrostaticPressure calibrator or a known head of waterFive, up and downSpecific gravity in the calculation; vent tube on submersibles
Level transmitter, radar or ultrasonicTape measure or a target at known distancesTwo or three levelsConfiguration verification more than calibration; the radar page
Flow meter, magneticManufacturer verification tool for the electronics; a volumetric or a comparison meter for the whole meterVerification of coil and electrode values; two or three flows where a comparison is possibleMost mag meters are verified electronically and compared against a reference flow periodically
Flow, differential pressurePressure calibrator on the DP transmitterFive points on DP, checked through the square rootThe element is inspected, not calibrated; the DP flow page
TemperatureA dry block or a bath with a reference thermometerThree points across the rangeImmersion depth and stabilization time matter
pHBuffers, two points bracketing the processTwoSlope and offset recorded; the pH page
Chlorine residualDPD grab sample on a calibrated bench instrumentOne point at the process residual, zero on chlorine-free waterCompare before adjusting; the chlorine page
TurbidityPrimary formazin standard for calibration; secondary sealed standard for verificationPer the instrument methodCompliance records; the turbidity page
Analog input channelMilliamp source at the panel terminalsThree or fiveA card channel is calibrated like an instrument when the loop tolerance is tight

Setting the interval

An instrument that has passed as-found at every calibration for two years is not drifting, and its interval can be extended. One that fails every six months is drifting and its interval is shortened, or it is replaced. The starting interval is set from the manufacturer guidance and the criticality, commonly six months for compliance and control-critical instruments and a year for the rest, and the as-found history moves it. Regulatory instruments have minimum frequencies the permit sets, and those are the floor.

The written procedure

  • Scope: the instrument type and the tags it applies to.
  • Safety: isolation, process notification, lockout, chemical handling.
  • Equipment: the reference standard by type and the accuracy required.
  • Preparation: how to isolate, vent, connect, and stabilize.
  • Test points and the order.
  • Tolerance and the decision rule.
  • Adjustment method, by instrument model where it differs.
  • Return to service and the live check.
  • Record: the form and where it is filed.
  • Revision and approval, so the procedure itself is under control.

Frequently asked questions

What accuracy ratio between the reference and the instrument is required?
Four to one is the widely used minimum: the reference uncertainty is no more than a quarter of the tolerance being checked. Ten to one is comfortable. Below four to one, the reference error is a significant part of what is being measured, and the result cannot be trusted at the tolerance.
Do we need to send our calibrators out for calibration?
Yes, on a schedule, to a laboratory that provides a traceable certificate, typically annually. A calibrator with no current certificate is not a reference, and every calibration done with it is undermined. The certificate and the due date are part of the calibration record.
Can a calibration be done in place without isolating the instrument?
A comparison against a reference at the operating point can be done in place and is valuable as a check between calibrations. It does not exercise the range and it is not a calibration for the record unless the procedure for that instrument says a single-point comparison is acceptable, which is the case for some analyzers.
What do we do with an instrument that fails as-found badly?
Record the failure, adjust or replace it, and ask what the loop did with the wrong value between the last calibration and this one. A compliance instrument that was out of tolerance for months may require reporting; a control instrument may explain a process problem. The as-found record is what makes that question answerable.