Water & Wastewater

Tank and Basin Volume

Volume of a cylindrical or rectangular tank at a given level, in gallons, cubic feet, and cubic metres, with the volume per foot of depth.

Inputs

Calculated reference results

Volume at this level
63,452gal
Volume at this level
8,482.3cu ft
Volume at this level
240.19cu m
Full capacity
126,904gal

At 24.00 ft

Percent full
50.0%
Volume per foot of depth
5,288gal per ft

Useful for turning a level change into a volume for a drawdown test.

Volume per inch of depth
440.6gal per in
Plan area
706.86sq ft

The arithmetic

  1. Area = pi x (15.00 ft) squared = 706.86 sq ft
  2. Volume = 706.86 sq ft x 12.00 ft = 8,482.3 cu ft
  3. Gallons = 8,482.3 x 7.48052 = 63,452 gal

What this does not account for

  • Assumes vertical walls and a flat bottom. Coned, dished, or benched bottoms hold less than this near the floor, which matters most at the low levels a pump-off setpoint uses.
  • A drawdown test using the volume per foot figure is one of the few practical ways to verify a pump rate in the field, and it is worth doing at commissioning.

How this is calculated

A cylindrical tank holds pi multiplied by the radius squared, multiplied by the liquid depth. A rectangular basin holds length multiplied by width multiplied by depth. Multiply cubic feet by 7.48 to get US gallons.

Formulas

Cylindrical volume = pi x radius squared x depth

Rectangular volume = length x width x depth

Gallons = cubic feet x 7.48052

Assumptions and limitations built into this calculator

  • Vertical walls, flat bottom, uniform cross-section.

Frequently asked questions

How do I verify a pump rate in the field?
Isolate the inflow if you can, run the pump, and time a known level change. Volume per foot multiplied by the level change, divided by the run time, gives the actual pumping rate.