PLC & Data
IEEE 754 Floating Point Inspector
Convert between a floating point value and its raw 32-bit representation, showing sign, exponent, mantissa, and the two Modbus registers in either word order.
Calculated reference results
- Value
- 12.5
- Raw hex
- 0x41480000
- Modbus registers, high word first
- 16712, 0
- Modbus registers, low word first
- 0, 16712
- Sign bit
- 0 (positive)
- Exponent
- 10000010 (130, unbiased 3)
- Mantissa
- 10010000000000000000000
- Full bit pattern
- 0 10000010 10010000000000000000000
0x4148, 0x0000 — often called big-endian or ABCD
Often called word-swapped or CDAB. Very common on field devices.
The arithmetic
- 32-bit pattern: 0 10000010 10010000000000000000000
- High word (first 16 bits) = 16712, low word = 0
- Value = 12.5
What this does not account for
- Modbus does not define word order for 32-bit values. If a float reads as a huge number, a near-zero number, or nonsense, try swapping the word order before assuming the device is faulty.
- Some devices additionally swap bytes within each word, giving four possible arrangements. Read a value you already know, such as a flow rate shown on the device display, to identify which one applies.
- Single precision carries about 7 significant decimal digits. Values above roughly 16.7 million stop resolving single units.
How this is calculated
An IEEE 754 single precision value occupies 32 bits: one sign bit, eight exponent bits, and 23 mantissa bits. Across a Modbus link it spans two 16-bit registers, and because the standard does not define which register comes first, the same 32 bits read as a completely different number if the word order is wrong.
Formulas
value = (-1)^sign x 1.mantissa x 2^(exponent - 127)
Assumptions and limitations built into this calculator
- IEEE 754 single precision, 32 bits.
- Register values are shown for the two common word orders. Byte-swapped variants exist and are not enumerated.
Frequently asked questions
- My Modbus float reads as garbage. What is wrong?
- Almost always word order. Swap the two 16-bit registers and read again. If it is still wrong, try swapping bytes within each word. Verify against a value the device displays locally.