Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
ReferenceWaterLevelControlPumpsSCADA

Ground Storage Tanks

Controls for ground storage tanks: level measurement and its datum, filling from wells and treatment by pump control or altitude valve, and the telemetry that ties the tank to the system.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Ground Storage Tanks

A ground storage tank sits between supply and demand: wells or a treatment plant fill it, high service pumps draw from it, and its level is the variable that runs both. The controls are a level measurement referenced to a documented datum, a fill control that starts sources at a low band and stops them at a high band or throttles an altitude valve, a low level cutoff that protects the high service pumps from running dry, high level and overflow alarms that arrive before the overflow, and a telemetry link that gives the operators and the SCADA system the level and the alarms. Behind those basics are the concerns of a stored water: turnover so that the water does not age and lose its residual, a level cycle that exercises the full volume, mixing where stratification is a problem, and freeze protection in cold climates. The tank is also where a system finds out whether its sources and its pumps are matched, because a tank that trends down in summer says the sources cannot keep up.

Key points

  • Level to a documented datum, with a second independent high level switch for the overflow alarm.
  • Fill by pump control on level bands or by an altitude valve; either way the bands come from the tank volume and the source capacity.
  • Low level cutoff protects the high service pumps; an inhibit above it prevents restarts in a dying tank.
  • Cycle the level through enough of the volume to turn the water over; a full tank is an old tank.
  • Trend the level against time: a tank that loses ground reveals a source or a demand problem before anything else does.

Measurement

A submersible hydrostatic transmitter at the tank floor, a radar unit at the roof, or a pressure transmitter on the tank outlet reads the level, referenced to a datum that is written on the drawing, usually the tank floor. The transmitter range covers the full tank with margin above the overflow; the scaling in the controller matches the range; and a float switch or a second transmitter provides an independent high level alarm that does not depend on the primary. The level tag carries its unit and its datum in its description, because a level in feet above the floor and a level in feet above sea level are both feet.

Filling

MethodHow it worksNotes
Pump control on level bandsSources start at the lead-on level and stop at the off level; more sources at lower bandsThe usual arrangement for wells and treated water pumps; bands sized for starts per hour and source capacity
Altitude valveA hydraulic valve on the inlet throttles or closes as the tank approaches fullFills from a pressurized system without pump control; needs its own maintenance; a level signal still needed for telemetry
Treatment plant flowThe plant produces at a rate set from the tank level trendThe tank level or its rate of change sets the plant production setpoint
Timed or scheduled fillSources run in off-peak hours to reach a target level by morningCombined with level bands as limits

The bands are set from the tank geometry and the source capacity: the volume between off and lead-on decides how often the sources cycle and must keep starts per hour within the motor ratings, and the volume between lead-on and the low alarm decides how much time the operators have when a source fails. With several sources, they are staged at successive bands and alternated, and a source that fails is skipped. The bands are on the screen with limits and in the control narrative.

Drawing from the tank

High service pumps take suction from the tank and stop when it is too low, at a level that keeps the suction submerged and the pumps within their net positive suction head. Above the cutoff is an inhibit level below which a pump that has stopped may not restart, so that the pumps do not cycle in a tank that is barely refilling. The low level alarm sits above the inhibit, with enough volume to act. Where the tank is the only storage, the low level condition also drives the demand side: a pressure setpoint reduction, a notice to large users, or a purchase from a neighbor, according to the plan.

Alarms

  • High level from the primary transmitter, and an independent high-high from a switch, both before the overflow.
  • Low and low-low from the primary, with the cutoff below.
  • Rate of change: filling faster than any source can fill is a transmitter fault; falling faster than demand can explain is a leak or a main break.
  • Stale level: a level that has not moved in hours with pumps running is a failed transmitter or a frozen line.
  • Communication loss from the tank site, with the fill sources holding a safe state.

Turnover and age

Water in a tank loses its disinfectant residual with time and warms in summer, and a tank that is kept near full turns over only a small fraction of its volume each day. The control cycles the level through a deliberate range, deeper in summer, so that a meaningful fraction of the volume is replaced daily, and the operators track the calculated water age and the residual at the outlet. A mixing system, a jet or a mechanical mixer, is added where stratification or dead zones persist, with its own run logic and alarm. In cold climates the level cycle also breaks ice and the inlet and outlet arrangements keep the water moving; a tank left full and still in a hard freeze is a tank with an ice problem.

Turnover (days) ≈ V_tank ÷ V_cycled_per_day

  • V_tank = the operating volume of the tank
  • V_cycled_per_day = the volume drawn and refilled each day, from the level cycle and the tank geometry
  • Many utilities target a turnover of a few days; the residual trend says whether it is enough

Telemetry

The tank level is often the most important single signal in a small system, and it travels by radio or cellular from a site with no staff. The design gives the tank site a reliable link with a watchdog, a battery-backed transmitter and radio, a local high level alarm that does not depend on the link, and a fill control that behaves safely when the link is lost: sources at a remote site run on their own local level signal where possible, or hold their last command for a limited time and then go to a safe state.

Frequently asked questions

Where should the fill sources get the level from?
From the tank transmitter over telemetry for normal control, with a local backup at the source if the link can fail: a pressure transmitter on the source discharge that infers the tank level, or a timed fill with limits. The narrative states the behavior on communication loss.
How deep should the level cycle be?
Deep enough to turn the water over in a few days while keeping enough storage for fire flow and outages: the two constraints set the band, and the residual at the outlet says whether the cycle is deep enough.
The tank overflowed with no high level alarm.
The primary transmitter failed high or was stuck, and there was no independent high level switch, or the switch was there and not alarmed. Add the independent switch, alarm it, and add a rate-of-change and stale-value check on the primary.
Can the same level control the wells and the high service pumps?
Yes: the wells fill on the upper bands and the high service pumps are protected by the lower ones, and both read the same transmitter with the independent switch as the safety. The bands are separated so that the two functions never fight.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.