Nanofiltration

Nanofiltration from the controls side: how it differs from reverse osmosis in pressure, recovery, and what it removes, the softening and color removal applications where it dominates, and trends that are shared with reverse osmosis and the ones that differ.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Nanofiltration

Nanofiltration is a membrane process a step looser than reverse osmosis: it passes most monovalent ions and removes divalent ions, organics, color, and pathogens, at operating pressures a fraction of what reverse osmosis needs. Its municipal home is groundwater softening and the removal of color and disinfection byproduct precursors from organic-rich sources, often at recoveries higher than reverse osmosis achieves, and the limiting factor is almost always scaling by calcium carbonate and sulfate salts in the concentrate. The skid, the instruments, the loops, and the sequences are those of reverse osmosis at lower pressure: a feed pump on a drive, stages of vessels, a concentrate valve, antiscalant and acid feed, and the normalized trends. What differs is the emphasis: pH and antiscalant control decide the recovery, the permeate needs stabilization by degasification and pH adjustment before it is pipeable, and the permeate quality is judged on hardness and color rather than on conductivity alone.

Key points

  • Looser than reverse osmosis: removes hardness, organics, and color; passes most monovalent ions; runs at lower pressure.
  • Recovery is set by scaling; antiscalant and pH control are the loops that protect it.
  • Permeate stabilization, degasification, pH adjustment, and corrosion control follows the membranes and has its own controls.
  • Instruments, sequences, normalization, and trips are shared with reverse osmosis.
  • Quality is judged on hardness, color, and total organic carbon as well as conductivity.

Compared with reverse osmosis

AspectNanofiltrationReverse osmosis
RemovesDivalent ions, organics, color, pathogens; partial monovalent removalNearly all dissolved solids
Operating pressureLow; often well under 150 psi on groundwaterHigher; brackish water often 150 to 400 psi, seawater far more
Typical recoveryHigh, often 80 to 90 percent on suitable waterModerate, often 75 to 85 percent
Limiting factorScaling by calcium carbonate and sulfatesScaling and osmotic pressure
Main usesSoftening, color and organics removal, disinfection byproduct precursor controlDesalination, total dissolved solids reduction, specific contaminants
PermeateSoft, low alkalinity, aggressive; needs stabilizationVery low dissolved solids; needs stabilization

Scaling control

As the feed is concentrated, calcium carbonate and the sulfates of calcium, barium, and strontium approach and exceed their solubility in the concentrate, and they precipitate on the last elements of the last stage. Antiscalant dosing keeps them in solution for the residence time of the water in the skid, acid dosing lowers the pH so that carbonate stays as bicarbonate, and the recovery is chosen so that the concentrate stays within what the chemicals can hold. The controls flow-pace the antiscalant to the feed flow and alarm on low dosing; control the feed pH to a setpoint with the acid feed and trip on high pH; and hold the recovery with the concentrate valve. The trend that catches scaling is a rising normalized differential pressure on the last stage with a rising salt passage, and the answer is a low pH clean and a review of the dosing.

Permeate stabilization

Nanofiltration permeate has lost its hardness and much of its alkalinity, carries dissolved carbon dioxide from the acid feed, and may carry hydrogen sulfide from the groundwater; it will corrode pipe and stain fixtures until it is stabilized. Degasification strips the carbon dioxide and sulfide in a tower with a blower and a scrubber; caustic or lime raises the pH; a corrosion inhibitor is added; and in many plants a bypass of raw or partially treated water is blended back to restore some alkalinity and hardness. The controls for this section are a pH loop on the caustic feed, a blend ratio loop on the bypass, blower and scrubber sequences and interlocks, and the alarms on pH, sulfide odor control, and inhibitor feed. The finished water quality targets, pH, alkalinity, and a corrosion index, are the setpoints.

What is shared with reverse osmosis

  • The instruments: pressures per stage, permeate and concentrate flows, conductivities, pH, temperature, oxidant check.
  • The loops: permeate flow by pump speed, recovery by concentrate valve, flow-paced dosing.
  • The sequences: flush, ramp, run, flush; the cleaning sequences.
  • Normalization of permeate flow, salt passage, and differential pressure, and the cleaning triggers.
  • The trips: pressure, conductivity, oxidant, pH, chemical feed.

Quality measurements

  • Permeate conductivity for a continuous trend; less sensitive than on reverse osmosis because monovalent ions pass.
  • Online or laboratory hardness on the permeate and the blended water; the softening target.
  • Color and ultraviolet absorbance where color or organics removal is the purpose; total organic carbon by laboratory.
  • pH, alkalinity, and a corrosion index on the finished water.
  • Sulfide and odor at the degasifier where the groundwater carries it.

Frequently asked questions

Why nanofiltration instead of lime softening?
It removes organics and color as well as hardness, produces no lime sludge, and is easier to automate; it costs energy, membranes, chemicals, and a concentrate to dispose of. The choice is a treatment study; the controls are simpler for the membrane plant.
The last stage differential pressure keeps rising.
Scaling on the last elements, where the concentrate is most saturated. Check the antiscalant dose and the feed pH against the design, verify the recovery is not above design, and clean at low pH.
How aggressive is the permeate?
Aggressive enough to corrode iron and copper and to leach lead from old fittings; the stabilization section is not optional. The corrosion index of the finished water is a control target with limits.
Can a reverse osmosis skid be converted to nanofiltration?
The vessels and much of the piping are the same; the elements, the pump sizing, the recovery, and the chemical program change. The membrane supplier projection for the new elements decides the operating point.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.