RAS and WAS Control

Return and waste activated sludge: what each flow does for the process, RAS control by influent flow ratio or by blanket level, WAS control to a target sludge age or a target mixed liquor concentration, the flow and solids measurements each needs, and the pump and valve arrangements that make the setpoints achievable.

10 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

RAS and WAS Control

Return activated sludge carries settled biomass from the secondary clarifier back to the aeration basin so the process keeps its population; waste activated sludge removes the growth so the population stays at the intended age. RAS is usually controlled as a ratio to influent flow, commonly 50 to 100 percent, trimmed by the clarifier sludge blanket. WAS is controlled to hold a target solids retention time or a target mixed liquor suspended solids, from a daily calculation or a continuous solids measurement, and it is the setting that shapes the whole biological process. Both need a flow measurement, a way to modulate the pump or the valve, and a solids concentration where the calculation depends on it.

Key points

  • RAS keeps the biomass in the process. WAS sets how old the biomass is.
  • RAS as a ratio to influent flow, trimmed on the clarifier blanket, is the standard control.
  • WAS to a sludge age target is a slow loop: a daily calculation, a small adjustment, and patience.
  • Both need flow meters. WAS also needs the solids concentration, measured or sampled.
  • The operator sets the targets. The control system holds the flows and does the arithmetic.

The two flows

An activated sludge process is a population of microorganisms that eat what arrives in the wastewater. They are grown in the aeration basin, separated from the treated water in the secondary clarifier, and most of them are pumped back to the basin as return activated sludge so that the population is maintained. They also multiply, and a portion equal to the growth is removed as waste activated sludge to thickening and digestion, so that the population does not keep increasing. The rate of removal decides the average age of the population, the solids retention time, and the solids retention time decides what the process can do: a young sludge removes organic matter, an older one nitrifies, an older one still does more, at the cost of more air and more clarifier load.

RAS control

ModeHow it worksNotes
Constant flowThe RAS pumps run at a fixed rate set by the operatorSimple; over-returns at low flow and under-returns at peak; the fallback mode
Influent flow ratioRAS flow is held at a set percentage of plant influent flow, commonly 50 to 100 percent, by a flow controller on the RAS pumps or a valveThe standard; keeps the clarifier solids loading proportional and the blanket stable through the daily cycle
Blanket level trimThe ratio is adjusted within limits to hold the clarifier sludge blanket at a target depthThe refinement; needs a blanket sensor per clarifier and a limit so the trim cannot run away
Constant concentrationRAS flow adjusts to hold a RAS solids concentrationLess common; needs a solids sensor on the RAS line

The RAS pumps are often on drives with a flow meter on the common RAS line or one per clarifier, and the controller holds the flow setpoint that the ratio produces. Where the pumps are constant speed, a modulating valve on each clarifier draw-off splits the flow, and the number of pumps running sets the total. The RAS flow split between clarifiers is proportional to their influent split, and a clarifier with a rising blanket gets more; the blanket trim per clarifier does that automatically where the piping allows it.

WAS control

WAS is a small flow with a large effect. A plant wasting a few percent of its influent flow as thick sludge sets the sludge age of the whole process, and the effect of a change appears over days. The control is therefore a calculation and a slow adjustment, not a fast loop.

SRT = (V × MLSS) / (Q_WAS × X_WAS + Q_eff × X_eff)

  • SRT = solids retention time, or sludge age, in days
  • V = aeration basin volume
  • MLSS = mixed liquor suspended solids concentration in the basin
  • Q_WAS and X_WAS = waste sludge flow and its solids concentration
  • Q_eff and X_eff = effluent flow and its solids concentration, often small enough to neglect
Target SRT
The operator sets the sludge age the process needs, for example 8 to 15 days for nitrification in a temperate plant. The controller computes the WAS flow that holds it from the basin volume, the MLSS, and the WAS concentration, and adjusts the WAS pump rate or run time daily. The MLSS and WAS concentration come from online solids sensors or from daily lab samples entered into the system.
Target MLSS
The operator sets a mixed liquor concentration; the controller wastes more when MLSS is above target and less below it. Simpler, and the common practice at plants without online solids measurement; it drifts with the influent load in a way the SRT method does not.
Constant WAS flow
A fixed daily wasting volume set by the operator from the weekly calculation. The fallback and the practice at many small plants.
Wasting from the mixed liquor
Wasting directly from the aeration basin instead of from the RAS line, which makes the WAS concentration equal to the MLSS and removes one measurement from the calculation, at the cost of a larger volume to thickening.

Instruments

  • RAS flow, by a magnetic flowmeter on the RAS line, total or per clarifier. Sludge is conductive and a mag meter reads it well; the meter is sized for the velocity that keeps it clean.
  • WAS flow, by a mag meter on the WAS line, with a totalizer that is the wasting record.
  • Sludge blanket level per clarifier for the RAS trim.
  • MLSS by an online suspended solids sensor in the basin, cleaned automatically, and verified against lab samples; or lab samples entered daily.
  • RAS and WAS solids concentration by a suspended solids sensor on the line, or lab samples.
  • Influent flow, from the headworks, for the ratio.

Pumps and valves

RAS pumps move a thick, ragging liquid at a moderate head, and they are usually non-clog centrifugal or screw pumps on drives. WAS pumps move a small flow of the same liquid, on a drive or on a timer, and they need the same clog and dry-run protection as any sludge pump. Where the RAS is split among clarifiers by valves, the valves are modulating with position feedback, and the control keeps every clarifier draw-off open enough that sludge never sits in a hopper long enough to go septic and rise. A clarifier whose RAS valve is closed while it is in service is a clarifier that will lose its blanket over the weir within hours.

Frequently asked questions

What RAS rate should we run?
The process engineer sets it from the settling characteristics and the clarifier design, typically 50 to 100 percent of influent flow, sometimes higher during poor settling. The control system holds the ratio the operators set and shows the blanket that results.
Why is the WAS calculation different from what the lab computes?
The inputs: the online solids sensor and the lab sample rarely agree exactly, and the calculation is sensitive to the WAS concentration. The controller calculation uses the values it is given, and the daily review compares them with the lab. When they diverge, the sensor is checked and the lab value is entered.
Can WAS be automated fully?
The calculation and the daily adjustment can, with the target SRT set by the operator and limits on the rate of change. Most plants keep the operator in the loop for the daily review, because the process changes in ways the calculation does not see: a temperature drop, a toxic slug, a change in the influent character. Full automation with limits and a daily report is reasonable at a plant with reliable online solids measurement.
What happens to RAS control when the influent flow meter fails?
The ratio has no basis and the controller falls back to a constant RAS flow at the last good value, with an alarm. The blanket trim continues if the blanket sensors are healthy. The influent meter is also the compliance flow, so its failure is already a high priority alarm.