Symptom
With the HOA in AUTO and the controller calling the pump, the drive shows ready and does not run, or runs at zero speed. In HAND or from the keypad it runs normally.
The short answer
Drive Will Not Start in AUTO
A drive that runs locally but not in AUTO is not receiving a valid start command, a valid speed reference, or both, from the automatic source. Check the drive command source parameter, confirm the drive sees the run input or the network control word, confirm the enable and safe torque off inputs are made in AUTO, confirm the speed reference is above the minimum, and confirm nothing in the drive is waiting for a reset. The drive display shows every one of these.
Key points
- The drive display shows the command source, the input states, the reference, and the fault. Read it before opening the program.
- A drive can be ready, commanded, and enabled, and still not run on a zero speed reference.
- Safe torque off and the enable input are separate from the run command and are often wired through a relay the controller does not know about.
- On a networked drive, the control word must be exactly what the drive expects, including the switch-on sequence.
- If the drive ran in AUTO last week, look for what changed: a parameter reset, a swapped drive, a program download.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Command source set to keypad or terminal only | Drive parameter for the start command source in the AUTO or remote mode. A replaced or reset drive defaults to keypad. |
| Run input not reaching the drive | Digital input status on the drive display while the controller calls. Follow the controller output through the interposing relay and the HOA AUTO contact to the drive terminal. |
| Enable or safe torque off input open | Both inputs on the display. Commonly wired through the HOA, a seal-leak relay, or a safety relay, and made in HAND by a different path than in AUTO. |
| Speed reference at zero or below minimum | Reference value on the display. Analog reference wiring, scaling in the controller, or a network reference of zero. Some drives will not start below a minimum reference. |
| Reference source set to the wrong input | Drive parameter for the reference source in AUTO. An analog reference wired to input 2 while the drive reads input 1 gives zero. |
| Network control word wrong or connection not established | Drive network status; the control word being sent; the drive state machine. A drive that requires a specific enable sequence in the control word stays in ready. |
| Fault not reset, or a warning that blocks start | Fault and warning list on the display. Some conditions show as warnings and still block a start. |
| Wrong drive parameter set after replacement | Compare the parameter list with the backup. A replaced drive that ran on defaults for a day is the classic cause. |
| Run permissive in the drive not met | Some drives have a separate run permissive or external interlock input. Check every input the drive lists as required. |
| Controller not actually calling | Output bit, output terminal, and the permissives in the program. Covered under the pump-will-not-start page; confirm before working on the drive. |
Read the display first
Every drive shows on its keypad, or through its software, the state of each digital input, the active command source, the active reference source and value, the enable and safe torque off status, and any fault or warning. That is the diagnostic list. Five minutes with the display usually finds the cause; an hour in the controller program usually does not, because the program is doing what it was told and the drive is not receiving it.
| Display shows | Meaning | Look at |
|---|---|---|
| Ready, no run command | The drive is not seeing a start from the active source | Command source parameter; run input state; controller output path |
| Run command present, not running, enable or STO off | A hardwired input the run command does not control is open | Enable and safe torque off wiring through the HOA and safety relays |
| Running, 0 Hz | Commanded and enabled, with a zero reference | Reference source parameter; analog reference wiring; controller scaling; network reference |
| Not ready, or a warning | A condition the drive treats as a block | Warning list; DC bus voltage; motor overtemperature input; external fault input |
| Fault | A latched fault | Fault code and history; reset only after reading |
| Network: not connected or timeout | The network command is not arriving | Network status LEDs; controller connection status; control word |
Diagnostic procedure
- 1
Confirm the controller is calling
Output bit on, output terminal live, and the permissives true. If the controller is not calling, this is not a drive problem.
- 2
Check the command source
The drive parameter that selects where the start command comes from in AUTO: a terminal input, a network, or the keypad. A drive replaced or reset to defaults usually reverts to keypad. Set it to the intended source.
- 3
Check the run input
On the display, watch the input the run command is wired to while the controller calls. If it does not change, follow the wire: output module, interposing relay, HOA AUTO contact, drive terminal. If the input changes and the drive does not run, move on.
- 4
Check enable and safe torque off
Both must be made. They are often wired through the HOA switch in a way that makes them in HAND and expects the controller to make them in AUTO through a relay that was never wired, or through a seal-leak or safety relay that has dropped out.
- 5
Check the reference
The reference value on the display. If it is zero: the reference source parameter, the analog input the reference is wired to, the controller output that drives it, and the scaling. If the drive has a minimum frequency and the reference is below it, some drives will not start.
- 6
Check the network
On a networked drive, confirm the connection is established, the control word matches the drive state machine requirements, and the reference is in the expected units. A control word that never sends the switch-on step leaves the drive in ready forever.
- 7
Check faults and warnings
Read the list. Reset after recording. If the fault returns immediately, the drive is telling you something the run command cannot override.
- 8
Compare parameters to the backup
If the drive was replaced, serviced, or reset, load the saved parameter set or compare line by line. Command source, reference source, input functions, and minimum frequency are the parameters that matter here.
The HAND path and the AUTO path are different circuits
The reason a drive runs in HAND and not in AUTO is almost always that HAND makes something that AUTO does not. In HAND the HOA switch may close the run input, the enable input, and select a keypad or preset reference all at once. In AUTO the run input comes from the controller, the enable is expected from somewhere else, and the reference is an analog or network value from the controller. A panel where the enable was wired through the HAND contact only, or where the AUTO reference was never connected, works perfectly in HAND and never in AUTO. Compare the two paths on the drawing.
Common mistakes
- Downloading a program change before checking the drive display. The program was not the thing that changed.
- Resetting the drive to factory defaults to clear a problem, which sets the command source to keypad.
- Assuming the enable is part of the run command. It is a separate input on most drives and a separate safety circuit on many.
- Reading the reference in the controller and not on the drive. The controller can send 60 Hz to an analog output that goes to the wrong terminal.
- Replacing the drive when a parameter was wrong. The new drive arrives with defaults and the same symptom.
Frequently asked questions
- The drive shows the run command and the reference, and still will not run. What is left?
- Enable, safe torque off, an external fault or interlock input, a warning that blocks start such as motor overtemperature, or a drive that requires a rising edge on the run command and is seeing a level. Check every input the drive lists as required, and check whether the drive expects two-wire or three-wire control.
- How do I tell whether the drive uses two-wire or three-wire control?
- Two-wire control runs while the run input is held closed. Three-wire control starts on a momentary start input and stops on a normally closed stop input. A controller output wired as a maintained contact to a drive configured for three-wire control gives one start and then nothing, or nothing at all if the stop input is open.
- The drive ran in AUTO yesterday. What changed?
- Something. A parameter reset or a swapped drive, a program download that changed an output or a scaling, a relay that failed, a seal-leak or safety relay that dropped out, a network connection lost. The drive display and the change log narrow it. The most common answer is a drive that was replaced and configured for HAND operation only, because that was what was tested.
- Should the drive enable be controlled by the PLC?
- It is usually hardwired through the HOA and the safety devices, so that the drive is enabled whenever the pump is in HAND or AUTO and disabled in OFF and on a safety trip, independent of the controller. Wire it that way, document it, and do not route it through a controller output unless the design calls for it.
Related topics
- Pump Will Not StartA pump that is called and does nothing. The order to check: permissives and mode, control power, the starter or drive, the motor circuit, and the pump itself, with the measurements that settle each one in minutes.
- Hand-Off-Auto SelectorsWhat each position of an HOA selector does, how it is wired into the starter circuit, which protections must survive Hand, what the controller should see, and the mistakes that let a pump run with nobody watching.
- Outputs Not EnergizingThe program says the output is on and the equipment is not running. Where the signal gets lost between the output image and the field device, and how to find the point in a few measurements.
- EtherNet/IPHow EtherNet/IP moves control data: CIP over standard Ethernet, implicit I/O connections on a requested packet interval, explicit messaging, producer and consumer tags, and what the network has to provide.
- Distribution Pressure ControlHow a booster or high service pump station holds discharge pressure with variable speed pumps, how pumps are staged, and what stops the system hunting.
- Drive Faults on OvercurrentAn overcurrent trip on a variable frequency drive: what the drive measured and when, the difference between a trip at start, during acceleration, at steady speed, and at deceleration, the motor and cable faults behind each, the parameter settings that cause nuisance trips, and the tests that separate them.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.