Drive Will Not Start in AUTO

The drive runs from the keypad or in HAND but not from the controller. The command source, the enable and safe torque off inputs, the speed reference, and the network control word, checked in the order that finds the problem fastest.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

Symptom

With the HOA in AUTO and the controller calling the pump, the drive shows ready and does not run, or runs at zero speed. In HAND or from the keypad it runs normally.

The short answer

Drive Will Not Start in AUTO

A drive that runs locally but not in AUTO is not receiving a valid start command, a valid speed reference, or both, from the automatic source. Check the drive command source parameter, confirm the drive sees the run input or the network control word, confirm the enable and safe torque off inputs are made in AUTO, confirm the speed reference is above the minimum, and confirm nothing in the drive is waiting for a reset. The drive display shows every one of these.

Key points

  • The drive display shows the command source, the input states, the reference, and the fault. Read it before opening the program.
  • A drive can be ready, commanded, and enabled, and still not run on a zero speed reference.
  • Safe torque off and the enable input are separate from the run command and are often wired through a relay the controller does not know about.
  • On a networked drive, the control word must be exactly what the drive expects, including the switch-on sequence.
  • If the drive ran in AUTO last week, look for what changed: a parameter reset, a swapped drive, a program download.

Possible causes and what to check

Possible causeWhat to check
Command source set to keypad or terminal onlyDrive parameter for the start command source in the AUTO or remote mode. A replaced or reset drive defaults to keypad.
Run input not reaching the driveDigital input status on the drive display while the controller calls. Follow the controller output through the interposing relay and the HOA AUTO contact to the drive terminal.
Enable or safe torque off input openBoth inputs on the display. Commonly wired through the HOA, a seal-leak relay, or a safety relay, and made in HAND by a different path than in AUTO.
Speed reference at zero or below minimumReference value on the display. Analog reference wiring, scaling in the controller, or a network reference of zero. Some drives will not start below a minimum reference.
Reference source set to the wrong inputDrive parameter for the reference source in AUTO. An analog reference wired to input 2 while the drive reads input 1 gives zero.
Network control word wrong or connection not establishedDrive network status; the control word being sent; the drive state machine. A drive that requires a specific enable sequence in the control word stays in ready.
Fault not reset, or a warning that blocks startFault and warning list on the display. Some conditions show as warnings and still block a start.
Wrong drive parameter set after replacementCompare the parameter list with the backup. A replaced drive that ran on defaults for a day is the classic cause.
Run permissive in the drive not metSome drives have a separate run permissive or external interlock input. Check every input the drive lists as required.
Controller not actually callingOutput bit, output terminal, and the permissives in the program. Covered under the pump-will-not-start page; confirm before working on the drive.

Read the display first

Every drive shows on its keypad, or through its software, the state of each digital input, the active command source, the active reference source and value, the enable and safe torque off status, and any fault or warning. That is the diagnostic list. Five minutes with the display usually finds the cause; an hour in the controller program usually does not, because the program is doing what it was told and the drive is not receiving it.

Display showsMeaningLook at
Ready, no run commandThe drive is not seeing a start from the active sourceCommand source parameter; run input state; controller output path
Run command present, not running, enable or STO offA hardwired input the run command does not control is openEnable and safe torque off wiring through the HOA and safety relays
Running, 0 HzCommanded and enabled, with a zero referenceReference source parameter; analog reference wiring; controller scaling; network reference
Not ready, or a warningA condition the drive treats as a blockWarning list; DC bus voltage; motor overtemperature input; external fault input
FaultA latched faultFault code and history; reset only after reading
Network: not connected or timeoutThe network command is not arrivingNetwork status LEDs; controller connection status; control word

Diagnostic procedure

  1. 1

    Confirm the controller is calling

    Output bit on, output terminal live, and the permissives true. If the controller is not calling, this is not a drive problem.

  2. 2

    Check the command source

    The drive parameter that selects where the start command comes from in AUTO: a terminal input, a network, or the keypad. A drive replaced or reset to defaults usually reverts to keypad. Set it to the intended source.

  3. 3

    Check the run input

    On the display, watch the input the run command is wired to while the controller calls. If it does not change, follow the wire: output module, interposing relay, HOA AUTO contact, drive terminal. If the input changes and the drive does not run, move on.

  4. 4

    Check enable and safe torque off

    Both must be made. They are often wired through the HOA switch in a way that makes them in HAND and expects the controller to make them in AUTO through a relay that was never wired, or through a seal-leak or safety relay that has dropped out.

  5. 5

    Check the reference

    The reference value on the display. If it is zero: the reference source parameter, the analog input the reference is wired to, the controller output that drives it, and the scaling. If the drive has a minimum frequency and the reference is below it, some drives will not start.

  6. 6

    Check the network

    On a networked drive, confirm the connection is established, the control word matches the drive state machine requirements, and the reference is in the expected units. A control word that never sends the switch-on step leaves the drive in ready forever.

  7. 7

    Check faults and warnings

    Read the list. Reset after recording. If the fault returns immediately, the drive is telling you something the run command cannot override.

  8. 8

    Compare parameters to the backup

    If the drive was replaced, serviced, or reset, load the saved parameter set or compare line by line. Command source, reference source, input functions, and minimum frequency are the parameters that matter here.

The HAND path and the AUTO path are different circuits

The reason a drive runs in HAND and not in AUTO is almost always that HAND makes something that AUTO does not. In HAND the HOA switch may close the run input, the enable input, and select a keypad or preset reference all at once. In AUTO the run input comes from the controller, the enable is expected from somewhere else, and the reference is an analog or network value from the controller. A panel where the enable was wired through the HAND contact only, or where the AUTO reference was never connected, works perfectly in HAND and never in AUTO. Compare the two paths on the drawing.

Common mistakes

  • Downloading a program change before checking the drive display. The program was not the thing that changed.
  • Resetting the drive to factory defaults to clear a problem, which sets the command source to keypad.
  • Assuming the enable is part of the run command. It is a separate input on most drives and a separate safety circuit on many.
  • Reading the reference in the controller and not on the drive. The controller can send 60 Hz to an analog output that goes to the wrong terminal.
  • Replacing the drive when a parameter was wrong. The new drive arrives with defaults and the same symptom.

Frequently asked questions

The drive shows the run command and the reference, and still will not run. What is left?
Enable, safe torque off, an external fault or interlock input, a warning that blocks start such as motor overtemperature, or a drive that requires a rising edge on the run command and is seeing a level. Check every input the drive lists as required, and check whether the drive expects two-wire or three-wire control.
How do I tell whether the drive uses two-wire or three-wire control?
Two-wire control runs while the run input is held closed. Three-wire control starts on a momentary start input and stops on a normally closed stop input. A controller output wired as a maintained contact to a drive configured for three-wire control gives one start and then nothing, or nothing at all if the stop input is open.
The drive ran in AUTO yesterday. What changed?
Something. A parameter reset or a swapped drive, a program download that changed an output or a scaling, a relay that failed, a seal-leak or safety relay that dropped out, a network connection lost. The drive display and the change log narrow it. The most common answer is a drive that was replaced and configured for HAND operation only, because that was what was tested.
Should the drive enable be controlled by the PLC?
It is usually hardwired through the HOA and the safety devices, so that the drive is enabled whenever the pump is in HAND or AUTO and disabled in OFF and on a safety trip, independent of the controller. Wire it that way, document it, and do not route it through a controller output unless the design calls for it.

Direct contact