Symptom
The drive displays an overcurrent fault code and stops. The fault may occur at every start, only under load, or intermittently, and the drive fault log shows the current at the trip.
The short answer
Drive Faults on Overcurrent
A drive trips on overcurrent when the output current exceeds a limit the drive cannot sustain, typically well above the motor rating for a fraction of a second. The timing tells the cause: at the instant of start it is usually a shorted motor or cable, a ground fault, or a locked rotor; during acceleration it is a ramp too short for the load or a jammed pump; at steady speed it is a mechanical jam, a sudden load, or a failing motor; at deceleration it is regeneration. Test the motor and cable insulation with the drive disconnected, check the mechanical load, and only then look at the ramp and current limit parameters.
Key points
- Read the fault log: the current at trip, the output frequency, and the time since start. The timing names the cause.
- A trip at the instant of start is a short: motor, cable, or ground fault. Test insulation before restarting.
- A trip during acceleration is a load the ramp cannot bring up: a jammed pump or a ramp too short.
- A trip at steady speed with no load change is mechanical: rags, a bearing, a coupling.
- Nuisance trips from parameters are the last diagnosis, not the first. Do not raise the limit to make the fault go away.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Motor winding shorted, turn to turn or to ground | Insulation resistance test on the motor with the drive disconnected; a low reading or a phase-to-phase resistance imbalance. |
| Motor cable shorted, damaged, or wet | Test the cable separately; inspect the run for damage; a submersible cable is the usual suspect. |
| Ground fault in the motor or cable | Often reported as a separate ground fault code; the drive trips on the current it cannot account for. |
| Pump jammed or locked rotor | Lock out and turn the shaft; rags around a wastewater impeller; a seized bearing. The trip is during acceleration or at the start of load. |
| Acceleration ramp too short for the load inertia or the head | The trip occurs at a consistent point in the ramp; lengthening the ramp removes it. |
| Sudden mechanical load | A trip at steady speed with a mechanical event: a check valve slam, a coupling failure, a pump ingesting a solid. |
| Deceleration too fast, regeneration | The trip is on stop or on a large speed reduction, often reported as overvoltage instead; lengthen the deceleration ramp or add braking. |
| Motor parameters wrong in the drive | Nameplate data, especially full-load current and the motor identification, entered wrong; the drive flux and current limit calculations are off. |
| Output contactor or bypass switching while running | A contactor between the drive and the motor opened or closed with the drive running; the drive sees a step and trips. |
| Drive output stage fault | The drive trips with the motor disconnected; an output transistor or a current sensor failure. |
| Long cable with high capacitance | Charging current on a long cable trips the drive at the switching frequency; an output reactor or a lower switching frequency. |
Read the fault log first
Every drive records the conditions at the trip: the output current, the output frequency, the DC bus voltage, the run time, and often the state of the inputs. The fault code itself may distinguish overcurrent at start, during acceleration, at steady speed, and at deceleration, or a ground fault, which is a different code on most drives. That record is the diagnosis in most cases.
| When it trips | Current at trip | Points toward |
|---|---|---|
| The instant of start, zero frequency | Very high, at the drive limit | Shorted motor or cable, ground fault, a locked rotor |
| During acceleration, at a consistent frequency | High, climbing through the ramp | Ramp too short; a pump that cannot be brought up to speed; a locked or heavily loaded pump |
| At steady speed, suddenly | A step increase | Mechanical event: rags, a bearing, a coupling, a solid in the pump |
| At steady speed, gradually | Climbing over minutes | A pump clogging, a bearing failing, a motor overheating |
| On deceleration or a speed reduction | High, with the DC bus voltage also high | Regeneration: the load is driving the motor; deceleration too fast |
| At random, with no pattern | Various | An intermittent cable fault, a wet motor, an output contactor, or noise on the drive control |
| With the motor disconnected | Reported with no load | The drive itself: output stage or current sensor |
Diagnostic procedure
- 1
Record the fault data
Fault code, current, frequency, bus voltage, time since start, and the count of the same fault in the log. Do not clear the log until it is recorded.
- 2
Lock out and test the motor circuit
Disconnect the motor leads at the drive. Insulation resistance phase to ground and phase to phase, on the cable and the motor separately where the junction allows. Winding resistance phase to phase for balance. A submersible pump motor and cable are tested as a unit at the panel, then separated if the result is poor.
- 3
Check the mechanical load
With power locked out, turn the shaft or the impeller by hand. Rags, grit, a seized bearing, a failed coupling. On a submersible, a pull is the only way to see the impeller.
- 4
Run the drive with no motor
Where the manual permits it, run the drive into an open output. A drive that faults with no load has a failed output stage or a current sensor and is repaired or replaced.
- 5
Check the motor parameters
Nameplate voltage, current, frequency, speed, and power entered in the drive; the motor identification or auto-tune run and current. A drive controlling a motor it believes is a different size mismanages the current.
- 6
Check the output circuit
Any contactor, disconnect, or bypass between the drive and the motor: it must not operate while the drive is running. An output reactor or filter where the cable is long.
- 7
Check the ramps and limits
Acceleration time against the load inertia and the head; deceleration time against the regeneration the load produces; the current limit setting against the motor rating. Lengthen a ramp that trips at a consistent frequency. Never raise a current limit above the motor rating to stop a trip.
- 8
Check the process
A pump that trips under load at steady speed is a pump problem: rags, a closed valve on the discharge that dead-heads it, a sudden change in the force main. The pump troubleshooting pages take it from there.
- 9
Restart and monitor
After the fix, trend the current through several starts and a full cycle. A trip that returns has a cause that was not found.
Common mistakes
- Restarting repeatedly into a shorted motor cable until the drive output stage fails, then replacing the drive into the same cable.
- Reading the fault code without the recorded current and frequency, and guessing.
- Replacing the drive when the motor is the fault. Test the motor first; it is cheaper to test than the drive is to replace.
- Lengthening the ramp to hide a pump that is jammed. The pump comes up slower and still draws the current of a jammed pump.
- Ignoring a trip that clears on reset and happens once a week. It is a cable or a motor on its way out.
Frequently asked questions
- The drive trips the moment I press start, even with the pump valve open. What is it?
- Almost always the motor circuit: a shorted winding, a shorted or wet cable, or a ground fault. Lock out, disconnect the motor at the drive, and test the insulation. A locked rotor is the other possibility; turn the shaft.
- The drive trips at the same frequency every time during the ramp. Why?
- The load at that speed exceeds what the drive can deliver within the ramp: a pump reaching the head where the check valve opens and the current jumps, or a ramp too short for the inertia. Lengthen the acceleration time and watch the current at that frequency. If the current is still above the motor rating with a long ramp, the pump is jammed or wrong for the head.
- Can a long motor cable cause overcurrent trips?
- Yes. A long cable has capacitance that the drive charges at every switching edge, and the charging current adds to the motor current; on a submersible pump with hundreds of feet of cable it can trip the drive. An output reactor, a dV/dt filter, or a lower switching frequency, per the drive manufacturer cable length guidance.
- The drive trips on overcurrent on stop. Why on stop?
- The pump is driving the motor as it decelerates, and the energy comes back into the drive; the drive sees it as current and, usually, as a rising bus voltage. Lengthen the deceleration ramp, enable the drive overvoltage control, or add a braking resistor where the load requires a fast stop. On a pump, a coast to stop is often acceptable.
Related topics
- Drive Faults on OvervoltageA DC bus overvoltage trip on a drive: where the bus voltage comes from, why deceleration and a driving load raise it, the utility-side causes from a high supply and capacitor switching, the deceleration ramp and overvoltage controller settings, braking resistors, and how to tell a regeneration trip from a supply transient.
- Drive Trips on Ground FaultA ground fault trip on a variable frequency drive: how the drive detects it, the motor and cable insulation faults behind most trips, the submersible cable problem, the capacitive leakage on long cables and filters that produces nuisance trips, wiring errors, and the insulation test that decides it.
- Pump Runs But No FlowThe motor turns and nothing moves. How to tell a clogged impeller from an air-bound pump, a closed valve, a stuck check, a broken coupling, or reverse rotation, using motor current and discharge pressure before pulling anything.
- Variable Frequency Drives in Pump PanelsWhat a drive adds to a pump panel and what it costs: speed control, soft start, reduced inrush, and diagnostics against heat, harmonics, cable and motor stress, bypass, and the minimum speed below which a pump does no work.
- Drive Will Not Start in AUTOThe drive runs from the keypad or in HAND but not from the controller. The command source, the enable and safe torque off inputs, the speed reference, and the network control word, checked in the order that finds the problem fastest.
- Motor Will Not Reach SpeedA drive that runs but never gets the motor to the commanded speed: the reference and its scaling, the maximum frequency and speed limits, current limit holding the ramp, a load beyond the motor, a wrong motor parameter set, and a low supply, with the drive readouts that separate them.