Symptom
A client shows a connection error, a spinning connection dialog, a certificate warning, a license refusal, or an authentication failure; one client is affected or all of them; the failure followed an update, a reboot, a password change, or a network change.
The short answer
Client Cannot Connect
A client that cannot connect has failed at one of a short list of layers, and testing them in order from the bottom finds it: the network path to the server, name resolution for the server name, the service listening on its port, the certificate the client must trust, the license or session count, the software version the server accepts, and the account the user presents. A single client failing while others work is that client, its network, or its user; every client failing at once is the server, its service, or the path to it; a client that worked until an update is a version or certificate change. The server log names the refusal in nearly every case, and it is the first thing to read after confirming the server is up.
Key points
- One client failing is the client, its path, or its user; every client failing is the server, its service, or the network.
- Test in order: ping, name resolution, the port, the certificate, the license, the version, the account.
- The server log names the refusal; read it before changing anything.
- Updates change versions and certificates, and clients that were not updated stop connecting.
- A session or license limit reached by abandoned sessions looks like a server fault and is fixed by closing them.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Server or service down | Every client fails; the server console, the service status, and the redundancy state. Restart the service or fail over. |
| Network path or firewall | Ping and a port test from the client to the server; a rule that was changed, a virtual network change, a switch port. One client on a new network segment is the common case. |
| Name resolution | The client resolves the server name to the wrong or no address; a name server change, a host file entry, a server that moved. Test with the address instead of the name. |
| Certificate expired, untrusted, or renamed | A certificate warning or a silent refusal after an expiry date or a server rename; the certificate validity and the trust store on the client. |
| License or session limit | The server refuses with a license message; abandoned sessions from workstations that were not logged out, or a license that expired. Clear sessions and check the license. |
| Version mismatch after an update | Clients that were not updated when the server was; the server log shows a version refusal. Update the clients. |
| Account locked, expired, or not authorized | One user fails on any client; the directory or the application user list. Unlock or reset, and confirm the role. |
| Client configuration pointing at the wrong server | A client set up for the old server, the wrong redundant pair, or a test system. Check the client project or connection settings. |
| Time difference between client and server | Authentication fails when the clocks differ by more than the tolerance; the time synchronization on both. |
| Web client browser or plugin problem | A browser update, a blocked script, a cached old page; try another browser and clear the cache. |
Bottom-up tests
- 1
Scope
One client or all. Ask the other operators before touching anything.
- 2
Server
The server console, the service status, the redundancy state, the disk, and the event log. If it is down, that is the job.
- 3
Path
From the client, ping the server by address. Then test the service port with a port test tool. A ping that works and a port that does not is a firewall or a service that is not listening.
- 4
Name
Resolve the server name from the client and compare with the real address. A client that connects by address but not by name has a name resolution problem.
- 5
Certificate
The certificate the server presents: valid dates, the name it was issued for, and whether the client trusts the issuer. An expired certificate stops every client on the same day.
- 6
License and sessions
The server license status and the active session list; close abandoned sessions.
- 7
Version
Client version against the server version, and the compatibility rule for the platform.
- 8
Account
The user account state and role; try a known-good account on the failing client and the failing user on a working client.
| Test | Fails | Meaning |
|---|---|---|
| Ping by address | Yes | Network path, client network settings, or the server is off |
| Ping by address | No | Path is up; continue |
| Port test to the service | Yes | Firewall in the path, host firewall, or the service is not listening |
| Resolve the server name | Wrong or none | Name server or host file; connect by address as a workaround only |
| Certificate check | Expired, untrusted, wrong name | Renew, install the issuer, or fix the server name |
| Session list | At the limit | Close abandoned sessions; review the license count |
| Known-good account | Works | The original user account is the problem |
After an update
The day after a server update is the day the clients stop connecting. The server now requires a client version the workstations do not have, presents a new certificate the clients do not trust, listens on a changed port, or enforces an encryption setting that the old clients cannot negotiate. The update plan for a SCADA server includes the clients, the certificates, the firewall rules, and a test from every kind of client before the operators need it.
Remote and web clients
A remote client adds layers: the virtual private network, the remote access gateway, and the browser. The same order applies with those inserted: is the tunnel up, does the gateway reach the server, does the browser trust the certificate and allow what the page needs. A client that works inside the plant and not from outside has failed in the added layers, and the gateway log is the one to read.
Frequently asked questions
- The client connects by address but not by name. Can I just use the address?
- As a workaround to get the operator working, yes. As a fix, no: the certificate is issued for the name, redundancy fails over by name, and the next name resolution failure will take out something else. Fix the name server or the host entry.
- The server says the license is exceeded but only two people are logged in.
- Sessions from workstations that were closed without logging out, web sessions in abandoned browser tabs, and a test client left running all hold licenses. The session list on the server shows them; close them and set a session timeout.
- Everything worked yesterday and nothing changed.
- Something changed: a certificate reached its expiry date, a password aged out, an automatic update ran on the server or the workstation, or a firewall policy was pushed. The server log and the update history for the last day name it.
- Should I reboot the server?
- Not first. A reboot on a running plant costs the operators their view and may not fix a certificate, a license, or a network problem. Read the log, test the layers, and reboot only when the service is hung and a restart of the service alone does not clear it.
Related topics
- Client ProblemsDiagnosing the operator station rather than the system: a client that will not connect, shows nothing, runs slowly, freezes, or stays silent on an alarm, with the causes, the order of checks, and the standard build and spare that make the fix a swap.
- SCADA ClientsThe workstations, browsers, and mobile devices operators use to see and control the system: thick, thin, web, and mobile clients, roles and permissions, where control is allowed from, workstation design, session policy, licensing, and failover behavior.
- Server FailureHow SCADA servers fail and what to do when one does: failure modes from a full disk to a dead hypervisor host, what the plant experiences with and without redundancy, the recovery sequence from restore to alarm verification, and the monitoring that warns.
- Cannot Ping Across VLANsTwo devices that work on their own networks but cannot reach each other across a VLAN boundary: no route, a wrong or missing gateway, a mask that puts the target on the wrong side, a trunk missing the VLAN, or a firewall rule. Testing each in order.
- VPN DesignHow a VPN fits remote access for a control system: it terminates in the DMZ and lands on a jump host, never the control network; site-to-site tunnels carry telemetry; user tunnels require multi-factor and individual accounts; the concentrator is patched fast.
- Time SynchronizationWhy every clock in a control system must agree and what happens when they do not: out-of-order events, historian gaps at daylight saving, authentication failures, wrong totals. The time source and hierarchy, how each device is synchronized, and the checks.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.