Symptom
A process condition that should have raised an alarm did not appear in the alarm summary, did not sound, or did not reach the on-call phone, and was discovered by some other means.
The short answer
Alarms Not Annunciating
An alarm that fails to annunciate is lost at one of a few points: the condition never set the alarm bit in the controller, the tag carrying it has bad quality or a wrong address, the alarm server did not evaluate it or is not running, the alarm is shelved, suppressed, or out of service, the display is filtered so it is not shown, the audible is silenced, or the notifier did not deliver it. Check the controller bit first, then the tag, then the alarm server state, then the filters and lists, then the notifier, and test the whole chain when it is fixed.
Key points
- Start at the controller. If the alarm bit never set, nothing downstream could annunciate it.
- Check the shelved, suppressed, disabled, and out-of-service lists. Most lost alarms are in one of them.
- A display filter or an area assignment hides alarms from the operator who needed them.
- The alarm server and the notifier are services. Confirm they are running and current.
- After the fix, drive the condition and follow the alarm to the screen and the phone.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| The condition did not set the alarm bit | Setpoint, deadband, on-delay, or a suppression condition in the controller logic. Monitor the bit online while driving the condition. |
| Tag quality bad or address wrong | The alarm tag in SCADA shows bad quality or never changes. Check the address and the driver. |
| Alarm disabled or out of service | The alarm configuration or the device out-of-service flag. Check the disabled and out-of-service lists. |
| Alarm shelved | An operator shelved it and the shelf timer is long or indefinite. Check the shelved list. |
| Alarm suppressed by design | A parent condition or a state is suppressing it, correctly or not. Check the suppressed list and the suppression logic. |
| Alarm server not running or not evaluating | The alarm service stopped, is on the standby server, or lost its connection to the tag source. |
| Display filter or area assignment | The operator client is filtered to an area or a priority that excludes the alarm, or the alarm is in an area the client is not assigned. |
| Priority below the annunciation threshold | The alarm is configured at a priority that does not sound or appear in the banner. |
| Audible silenced or hardware failed | Silence latched, speaker unplugged, sound disabled on the client. |
| Notification rule missing or the notifier failed | The alarm is not in the notification rule set, or the notifier service, modem, or account failed. Check the notifier log for the alarm. |
| On-call schedule wrong | The notifier called someone who was not on call or a number that no longer works. Check the schedule and the delivery log. |
Follow the chain
An alarm passes through a chain of stages between the process and the person, and each one can drop it. The chain is the same on every platform even if the names differ: the controller sets a bit; a driver reads it into a tag; an alarm server evaluates the tag and creates an alarm; the alarm is filtered by state (enabled, shelved, suppressed, out of service); clients display it according to their filters; the audible sounds according to priority and silence state; the notifier sends it according to its rules and schedule. The diagnosis follows the chain from the controller outward, and the first stage where the alarm is missing is the fault.
| Stage | Check | Where |
|---|---|---|
| Controller | The alarm bit set when the condition occurred | Online monitor of the bit and its logic; the historian if the bit is logged |
| Tag | The SCADA tag changed with the bit and has good quality | Tag browser: value, quality, timestamp |
| Alarm server | The alarm was created in the alarm database | Alarm history or journal for the tag and time |
| State filters | Enabled, not shelved, not suppressed, not out of service | The disabled, shelved, suppressed, and out-of-service lists |
| Client display | The client shows the alarm area and priority | Client filter settings and area assignments |
| Audible | Sound configured for the priority and not silenced | Client audio settings; the silence state |
| Notifier | A rule exists, the notifier processed it, the delivery succeeded | Notifier log; delivery status; schedule |
Diagnostic procedure
- 1
Establish what should have happened
From the master alarm database: the setpoint, delay, priority, and notification rule for the alarm. If the alarm is not in the database, or has no notification rule, the diagnosis is already done.
- 2
Check the controller
Did the bit set? Look at the historian for the bit and the process value at the time. If the value crossed the setpoint and the bit did not set, the logic is wrong: setpoint, deadband, delay, a suppression condition, or a bit written elsewhere. Drive the condition and watch online.
- 3
Check the tag
Quality and timestamp at the time, from the historian, or now by driving the condition. A tag with bad quality or a wrong address never carries the alarm.
- 4
Check the alarm journal
Every platform logs alarm events. If the journal shows the alarm occurred, the loss is downstream: state, display, audible, or notifier. If it does not, the alarm server did not evaluate the tag: service state, server failover, or the alarm configuration.
- 5
Check the state lists
Shelved, suppressed, disabled, and out of service. Each list shows who did it and when. A suppression by design is checked against its logic; a shelf is checked against its timer; a disable is a finding.
- 6
Check the client
On the operator client that should have shown it: area assignment, filter settings, priority threshold for the banner and the audible, silence state, sound hardware. Log in as the operator, not as an administrator, because filters are per user.
- 7
Check the notifier
The notifier log for the alarm: received, rule matched, calls placed, acknowledgment. No entry means the rule or the link from SCADA; an entry with failed delivery means the modem, the service, or the number; a successful delivery to the wrong person means the schedule.
- 8
Fix and test end to end
Drive the real condition where safe, or the tag from the controller, and follow it to the summary, the banner, the sound, and the on-call phone. Record the test.
Systemic causes
A single lost alarm has a single cause. A pattern of lost alarms has a systemic one: a client filter that everyone uses without knowing, an area that was added without being assigned to the operator group, a notifier rule set that was never updated for new sites, an alarm server that fails over and does not resume evaluation, or an audible that has been silenced with a latch nobody clears. The alarm test at every commissioning, and a periodic end-to-end test of a sample of alarms on the live system, find these before an incident does.
Frequently asked questions
- The alarm shows in the summary but never sounded. Why?
- The priority is below the audible threshold on that client, the client is silenced, or the sound hardware failed. Check the client audio configuration for the priority and test the sound. A silenced state that persists across alarms is a configuration fault.
- The alarm was in the journal and nobody was called. Why?
- The notification rule did not match, the notifier did not receive the alarm from SCADA, the notifier failed, or it called the wrong person. The notifier log answers it. If the notifier keeps no log, that is the first problem to fix.
- The alarm bit set and the tag was good, but the alarm server has no record. Why?
- The alarm server was not evaluating: the service was stopped, the standby server had the alarm role after a failover and was not running it, or the alarm configuration for the tag was removed. Check the service state and the failover history at the time.
- How do I prevent this?
- A master alarm database that is the configuration source, permissions that keep disabling and indefinite shelving away from ordinary users, area and filter settings under change control, a notifier heartbeat that is acknowledged every shift, and an end-to-end alarm test on a schedule.
Related topics
- Alarm Notification and CalloutGetting the alarm to the person on call when no one is watching the screen: notification paths, escalation, acknowledgment from the field, which alarms qualify, and the failure modes that leave a station in high level with nobody paged.
- Alarm FloodsWhat an alarm flood is, why it happens at exactly the wrong moment, the ISA-18.2 rate targets, and the design measures that keep a power failure or a communication loss from burying the one alarm that matters.
- Alarm Indication on the HMIHow an alarm looks and sounds on the operator screen: the ISA-101 and ISA-18.2 rules for color, shape, and blink, the alarm banner and summary, acknowledgment behavior, navigation to the alarm, and indication that survives colorblindness and a noisy control room.
- Alarm RationalizationThe meeting where every alarm earns its place: who attends, what is decided for each alarm, how to document it in a master alarm database, and how to run it at a utility that cannot spare a week.
- How to Add an AlarmFrom a request to a working alarm: define it against the philosophy, build the condition in the PLC with deadband and delays, configure the SCADA alarm with priority and message, test it end to end, and record it in the master alarm database.
- How to Diagnose a Bad Quality TagTrace a bad quality indication from the SCADA screen back to its source: the tag configuration, the driver and device connection, the controller tag, and the field signal, using the diagnostics each layer provides, and separate a stale value from a bad one.