Symptom
The SCADA shows one site offline with a communication alarm while other sites on the same master and channel are polling normally; the site may have gone silent after a storm, a power event, or a visit; the master diagnostics show no response or a weak, noisy response from that site.
The short answer
Remote Site Stops Communicating
A single radio site that stops answering while its neighbors on the same channel are fine has a problem at the site or on its path: the site has lost power, the radio has lost power or failed, the antenna or the coax has been damaged by lightning, wind, or water, the radio has reset its configuration, the controller behind the radio has stopped or lost its serial or Ethernet link to it, or the path has been obstructed by something new. The master radio diagnostics say whether the site radio is heard at all and at what signal level, which decides whether the visit starts at the power, the radio, or the antenna, and at the site the checks run from the power supply through the radio indicators and the received signal to the antenna system and the controller. Meanwhile the site runs on local control, which is the reason it can.
Key points
- One site down and its neighbors up puts the fault at the site or its path, not the master.
- Read the master diagnostics first: heard weakly, heard with errors, or not heard at all points the visit.
- At the site: power, radio, signal, antenna and coax, controller, in that order.
- Lightning and water are the usual antenna system killers; a coax that has taken water reads as a weak site.
- The site is pumping on local control while it is silent; confirm that before anything else.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Site power lost | The power fail alarm, if it arrived before the site went dark; at the site, the panel and the radio supply. A UPS on the radio lets the site report the outage. |
| Radio power supply or fuse failed | Radio indicators dark with the panel live; the radio fuse and its supply voltage. |
| Antenna, coax, or lightning arrestor damaged | The master hears the site weakly or not at all after a storm; at the site, the reflected power or the standing wave ratio is high, the arrestor is burned, or water is in the coax. Inspect and test the antenna system. |
| Radio configuration reset or changed | The radio came back on defaults after a power event or a firmware update: wrong frequency, address, or data rate. Compare with the configuration record. |
| Radio failed | Power present, indicators abnormal, no transmit, no receive of the master that other sites hear. Substitute the spare radio. |
| Controller stopped or lost its link to the radio | The radio hears the master and is polled but nothing answers: the controller is faulted, or the serial or Ethernet cable between them is out. Check the controller status and the cable. |
| Path obstructed by something new | Weak signal at the site and at the master with the antenna system healthy; a new building, a grown tree line, a new tank. Look along the path. |
| Master or repeater problem affecting only this path | The site is on a repeater that has failed while direct sites are fine; the repeater status. |
| Address or channel conflict after maintenance | A radio replaced with the wrong address, or two sites with the same address after a swap. Compare the configuration record. |
Before the drive
| Master diagnostics show | Meaning | Start at |
|---|---|---|
| Site not heard at all | Site radio not transmitting: power, radio, or antenna system | Site power and radio |
| Site heard weakly with errors | Antenna or coax damage, water, or a path change | Antenna system, then the path |
| Site heard normally, no data | The controller or its link to the radio | Controller and the radio cable |
| Several sites on one repeater silent | The repeater | The repeater site |
| Site heard, wrong address or garbage | Configuration reset or a duplicate address | The radio configuration |
At the site
- 1
The process first
The wet well level, the pumps, the floats: is the site controlling itself. If not, that is the emergency and the radio waits.
- 2
Power
Panel power, the radio supply voltage at the radio, the fuse. A UPS if one exists, and its status.
- 3
Radio indicators
Power, receive activity when the master polls, transmit activity when the radio answers, any fault indication.
- 4
Received signal
The radio diagnostic page or display: the received signal strength from the master compared with the commissioning record. Normal signal with no answer points at the controller; weak signal points at the antenna system or the path.
- 5
Antenna system
The coax connectors for water and corrosion; the arrestor for lightning damage; the antenna for physical damage and alignment; a standing wave ratio or return loss test on the coax and antenna.
- 6
Configuration
Frequency or hop set, address, data rate, and any setting that a reset would change, against the configuration record.
- 7
Controller and its link
The controller running; the cable from the controller to the radio; the port settings on both.
- 8
Substitute
The spare radio with the site configuration loaded, if the radio is suspect. Then the antenna if the substitute also reads weak.
After the storm
Lightning finds antennas. A site that went silent during a storm usually has a burned arrestor, a coax with a carbonized connector, or a radio whose receiver front end is gone, and sometimes all three. The arrestor is replaced, the coax is tested and replaced if it has taken water or shows a bad return loss, and the radio is tested against the spare. A site that survives storms has a properly grounded mast, an arrestor bonded to the site ground with a short strap, and a coax route that does not bring the surge into the panel.
While it is dark
The site keeps pumping on its controller and its floats, and the operators cannot see it. The communication alarm goes to the on-call list, the site is visited if its consequences justify it, and the design that makes that acceptable is local control that needs nothing from the master, a high level alarm dialer at the site where the consequences are severe, and a second path for the sites that cannot be lost.
Frequently asked questions
- The site radio shows a good signal from the master but the master cannot hear the site.
- The site transmitter is the problem, or its path outbound: a transmitter that has failed, a transmit power reset to minimum, or an amplifier stage damaged by lightning while the receiver survived. Substitute the radio.
- The site came back on its own after an hour. Should I still visit?
- Yes, and soon. A site that recovers on its own had a marginal condition: water drying in a connector, a power supply that reset, an intermittent path. It will do it again, and the visit while the evidence is fresh finds it.
- Can I diagnose the antenna without a test set?
- Partly: inspect the connectors for water and corrosion, the arrestor for damage, the coax for cuts and kinks, and the antenna for alignment; compare the received signal with the record. A standing wave ratio meter or an antenna analyzer is inexpensive and settles the question; a radio system without one is diagnosed by replacement.
- Why did only this site lose the path?
- Each site has its own path, and something on this one changed: a tree line grew, a building went up, a tank was painted, the antenna was turned by wind or by a contractor. Compare the received signal at both ends with the record and look along the path.
Related topics
- Lost CommunicationsWhat should happen when SCADA loses a device, a site, or everything, how the pattern tells which, the diagnostic order from the server outward through network, firewall, medium, and site, and the design that makes a lost link an alarm rather than an incident.
- Poor Signal MarginA path with too little signal above receiver threshold to survive rain, leaves, and inversions: the link budget from transmitter to receiver, the Fresnel zone, and why the margin is smaller than the study said. How to compute, measure, and add to it.
- Intermittent Radio PathA site that drops and returns by the hour, season, or weather: thin fade margin, foliage, a new obstruction, a loosened antenna, coax taking water, a corroding connector, interference, or a marginal supply. How to trend signal against time and weather.
- Lift Station Backup ControlHow a lift station keeps pumping when the transmitter, the PLC, or the SCADA link is gone: float backup logic, the control transfer relay, redundant-off protection, and how to test it with the controller actually dead.
- SCADA CommunicationsHow SCADA servers talk to controllers and the field: polling and report by exception, the protocols and what each is for, media from plant Ethernet to radio and cellular, poll rate arithmetic, timeouts and quality, time sync, store and forward, and security.
- UPS Not Carrying LoadThe power failed and the controls went down anyway: a battery aged out or never connected, a UPS sitting in bypass since a fault, an overload, loads on the wrong receptacles, or a failed self-test nobody read. Finding out which, and testing properly.