Symptom
Retries and errors with normal or strong received signal; the problem follows a schedule such as business hours or a shift; the radio diagnostic shows a raised noise floor or received signal with the far end silent; a scanner hears a foreign signal on the frequency; several sites near one location are affected.
The short answer
Interference on Channel
Interference is energy on the channel that is not the wanted signal, and it shows as retries and lost data while the received signal strength stays healthy. The noise floor, measured at the receiver with the far end silent, rises when the interferer is present, and its timing and its direction identify it: another licensed or unlicensed system on or near the frequency, a cellular or paging transmitter on a shared tower overloading the receiver front end or mixing with another signal to land on the channel, a drive, a welder, or a lighting system radiating broadband noise near the site antenna, or a radio in the utility own system whose transmitter has locked on. The cures are a bandpass or cavity filter on the receiver, a directional antenna aimed away from the source, separation from the offending transmitter, a channel or hop set change, suppression of the noise source, and for a licensed frequency the coordination process that protects it.
Key points
- Strong signal with lost data is interference; the noise floor with the far end silent proves it.
- Timing finds the source: business hours, a shift, a drive running, a broadcast schedule.
- Direction finds the location: a directional antenna or a drive with a scanner.
- A stuck transmitter in the utility own system is the first thing to rule out.
- Filters, directional antennas, and separation cure most of it; licensing coordination cures the rest.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Another system on the same or an adjacent frequency | A scanner or a spectrum analyzer hears the other signal; its schedule and its location. For a licensed frequency, the coordinator; for unlicensed, a different hop set or channel. |
| Nearby high-power transmitter overloading the receiver | A cellular, paging, or broadcast transmitter on the same tower or nearby; the receiver desensitizes when it transmits. A bandpass or cavity filter; antenna separation. |
| Intermodulation on a shared tower | Two strong signals mixing in a rusty joint or a receiver to produce a product on the channel; appears when both are on. Filters; the tower owner for the joint. |
| Broadband noise from a drive, a welder, or lighting | Noise floor rises when the equipment runs; the source close to the site antenna. Suppress at the source; move the antenna; shielded motor cable on the drive. |
| Stuck transmitter in the utility system | Constant carrier on the channel; every site retries; the master diagnostics show continuous receive. Turn off sites one at a time, or drive toward the strongest signal. |
| Second master or a misconfigured site transmitting unsolicited | Collisions in bursts; a poller that should not exist, or a site set to report on its own. Configuration review. |
| Harmonic from a lower-frequency transmitter | A signal at exactly half or a third of the channel frequency nearby; its harmonic lands on the channel. Filter at the source or the receiver. |
| Receiver damaged by lightning, now noisy | Noise floor high at one site with no external source; the receiver front end. Substitute the radio. |
Prove it
- 1
Silence the far end
Stop the polling to the site, or power the far radio off, so that nothing wanted is on the channel.
- 2
Read the noise floor
The received signal strength or the noise reading on the radio diagnostic with nothing wanted present. A healthy channel reads near the receiver floor; interference reads well above it.
- 3
Log it
The noise reading against time for a day or a week; the pattern is the schedule of the source.
- 4
Listen
A scanner or a spectrum analyzer on the frequency: a voice system, a data burst, a continuous carrier, a broadband hiss, or a signal that appears with a drive.
- 5
Locate
A directional antenna rotated for the strongest reading; a drive with a scanner toward it; the tower list for the frequencies nearby.
Patterns
| Pattern | Likely source | Cure |
|---|---|---|
| Business hours or a shift | Another commercial system | Coordination; channel change; directional antenna |
| Continuous carrier, every site affected | A stuck transmitter, usually in the utility own system | Find and repair the radio |
| When a drive or a machine runs | Broadband noise | Suppress at the source; shielded motor cable; move the antenna |
| When a nearby transmitter keys | Receiver overload or intermodulation | Bandpass or cavity filter; separation |
| Bursts, all sites | Collisions from a second poller or an unsolicited site | Configuration |
| One site only, no external signal found | A damaged receiver | Replace the radio |
Cures
- A bandpass or a cavity filter between the antenna and the receiver, tuned to the channel, rejects strong signals nearby. The standard fix for a shared tower.
- A directional antenna at the affected end, aimed at the far end and away from the source; the pattern nulls can be aimed at an interferer.
- Separation: the antenna moved away from the offending transmitter, vertically on the tower or to another structure.
- A channel change or a different hop set on unlicensed radios; a coordinated frequency change on licensed ones.
- Suppression of a noise source: shielded motor cable and filtering on a drive, replacement of a noisy light ballast, repair of a welder.
- Repair of the stuck transmitter, and a timeout in the radio that limits how long it may key.
- For a licensed frequency, the complaint to the frequency coordinator and, if needed, the regulator; the license is the protection, and the utility is expected to have used it.
Unlicensed spectrum
Spread spectrum radios in the unlicensed bands share the spectrum with everything else there: other utilities, industrial systems, consumer devices, and the wireless internet providers who fill those bands in many areas. A hop set change, a different channel plan, a directional antenna, and the radio own interference rejection are the tools; there is no coordinator to call. A utility whose telemetry depends on unlicensed spectrum in an area that is filling up plans a licensed channel or a different medium before the interference makes the decision.
Frequently asked questions
- We have a license. Can the interferer be made to stop?
- If the interferer is another licensed user on the same or an adjacent channel, the coordinator resolves it; if it is an unlicensed device, the regulator rules apply, and the utility documents the interference with measurements and times. In practice a filter and a directional antenna solve most cases faster than the process.
- The cell carrier put a site on our tower and the telemetry got worse.
- Receiver overload or intermodulation from the new transmitters. A cavity filter on the telemetry receiver and vertical separation on the tower are the usual cures, and the tower lease often obliges the new tenant to resolve interference they caused.
- Can a drive really interfere with a radio?
- A drive with an unshielded motor cable radiates broadband noise into the hundreds of megahertz, and a site antenna a few feet from it hears the noise floor rise every time the pump runs. The shielded motor cable, the drive grounding, and moving the antenna up the mast fix it.
- How do I know whether the interference is at my end or the far end?
- Measure the noise floor at both ends with the other silent. Interference near one site raises that site noise floor only, and that site loses the polls it should receive; the other end hears the site fine. The retries and the noise reading together say which end.
Related topics
- High Retry CountPolls that succeed on the second or third try: a weak or noisy path, interference, collisions from a second master, a timeout shorter than the radio turnaround, a data rate the path cannot carry, or a slow controller. Reading retry statistics per site.
- Intermittent Radio PathA site that drops and returns by the hour, season, or weather: thin fade margin, foliage, a new obstruction, a loosened antenna, coax taking water, a corroding connector, interference, or a marginal supply. How to trend signal against time and weather.
- Poor Signal MarginA path with too little signal above receiver threshold to survive rain, leaves, and inversions: the link budget from transmitter to receiver, the Fresnel zone, and why the margin is smaller than the study said. How to compute, measure, and add to it.
- Radio Frequency InterferenceReadings that jump when a handheld radio is keyed, inputs that flicker near a telemetry antenna, transmitters that drift beside a modem: how radio energy gets into control circuits, how to prove it with the radio itself, and the fixes.
- Drive Causes Instrument NoiseWhen many instruments became noisy after a drive was installed, the drive installation is the place to look: the checklist for motor cable, shielding, grounding, filters, and carrier frequency that decides how much noise a drive puts into the plant.
- SCADA CommunicationsHow SCADA servers talk to controllers and the field: polling and report by exception, the protocols and what each is for, media from plant Ethernet to radio and cellular, poll rate arithmetic, timeouts and quality, time sync, store and forward, and security.