Symptom
The pump is commanded to run, from the HOA in HAND or from the controller in AUTO, and the motor does not turn. There may be a fault indication, or nothing at all.
The short answer
Pump Will Not Start
A pump that will not start is stopped by one of five things, checked in order: the controller is not calling it (mode, permissives, interlocks, or a latched fault), the control circuit is open (control power, stop circuit, overload contact, safety devices), the starter or drive is not closing (coil, contactor, drive fault or enable), the power circuit is open (breaker, fuses, phase loss, disconnect), or the motor or pump is mechanically stuck. Work from the controller outward and confirm each stage with a measurement, not an assumption.
Key points
- Establish first whether the pump starts in HAND. That splits the problem in half.
- A pump that starts in HAND but not in AUTO is a controller or permissive problem.
- A pump that starts in neither is a control circuit, starter, drive, power, or mechanical problem.
- Follow the control circuit with a meter from the source to the coil. The open is where the voltage stops.
- A humming motor that does not turn is a mechanical or single-phase problem. Stop trying.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Not in AUTO, or a permissive is not met | HOA position on the panel and the HMI; permissive and interlock status in the controller. A phase monitor, a seal-leak input, a low-level cutoff, or a lockout bit will all hold the call off. |
| Latched fault in the controller or the drive | Fault history in the program and on the drive display. Reset only after reading the fault. |
| Control power lost or the control circuit open | Voltage at the control transformer secondary, then at each device in series to the starter coil: stop button, overload contact, seal-leak relay, thermal switch, HOA contact. |
| Overload relay tripped | Trip indicator or reset button on the overload. Note the cause before resetting; a tripped overload had a reason. |
| Starter coil or contactor failed | Voltage at the coil terminals when called. Coil energized and contactor not pulling in means the contactor; no coil voltage means the circuit ahead of it. |
| Drive not enabled, faulted, or not receiving the run command | Drive display: fault code, enable input status, run command source, speed reference. A drive with the enable open shows ready and never runs. |
| Power circuit open: breaker, fuses, disconnect, phase loss | Voltage on all three phases at the line side and the load side of the starter or drive. One blown fuse gives single phasing: hum and no rotation, or a trip. |
| Motor winding or cable fault | Insulation resistance test on the motor and cable with power locked out and the drive disconnected. Low insulation resistance or an open phase. |
| Pump or motor mechanically seized | With power locked out, try to turn the shaft or impeller by hand. Rags, a bearing, or a jammed impeller. Submersibles are pulled for this. |
The first test
Put the HOA switch in HAND. If the pump starts, everything from the starter to the motor to the pump is working, and the problem is in the automatic call: the controller, its inputs, its permissives, or the wiring between the controller output and the starter. If the pump does not start in HAND either, the controller is not the problem, and the fault is in the control circuit, the starter or drive, the power circuit, or the machine. This one action halves the search, and it takes ten seconds.
Starts in HAND, not in AUTO
- 1
Check the call
Is the controller actually calling the pump? Look at the output bit and the physical output indicator. If the bit is off, the problem is upstream in the logic: the level or pressure has not reached the start point, a minimum off time is running, the pump is not the current lead, or a permissive is false.
- 2
Read the permissives and interlocks
Most programs show them on a pump faceplate or a status screen. A phase monitor healthy contact, a seal-leak input, a high motor temperature input, a low-level cutoff, a remote lockout from SCADA, and an alternator state that holds this pump out of rotation are the usual holds.
- 3
Check the failed-to-prove latch
If the pump was called earlier and did not prove, the program may have latched a failure and removed the pump from the rotation. The latch needs a reset after the cause is found.
- 4
Follow the output to the starter
If the output bit is on, measure at the output terminal, then at the interposing relay if there is one, then at the AUTO contact of the HOA, then at the coil. The voltage stops where the open is.
- 5
Check the drive command source
On a drive, the run command may come from a digital input or over a network. Confirm the drive sees the command: a status word or an input indicator on the display.
Starts in neither
- 6
Look at the indicators
A fault light, a tripped overload, a drive fault code, a phase monitor indicator, or a breaker handle in the tripped position. Read before resetting. A fault code that is cleared without being recorded is a fault that will come back unexplained.
- 7
Confirm control power
Measure the control transformer secondary. No control power means a blown control fuse, a tripped control breaker, or a lost primary. A blown control fuse has a cause: a shorted coil, a wet device, or a wiring fault.
- 8
Walk the control circuit
Starting at the control power source, measure at each device in series toward the coil: the stop circuit, the overload auxiliary contact, the seal-leak and thermal relay contacts, the HOA HAND contact. Where the voltage disappears is the open device.
- 9
Check the coil and the contactor
Voltage at the coil with the circuit made and no pull-in: the coil is open or the contactor is mechanically jammed. Contactor pulls in and the motor does nothing: the problem is in the power circuit or the motor.
- 10
Check the power circuit
All three phases on the line side of the starter or drive, then the load side with the contactor closed. A missing phase on the line side is a fuse, a breaker pole, or the utility. A missing phase on the load side with the contactor closed is a burned contact.
- 11
Check the drive
A drive that will not run shows why on its display. Enable input open, safe torque off active, DC bus undervoltage, a stored fault, or a parameter set that expects the run command from somewhere else are all common. Reset a fault only after recording it.
- 12
Check the motor and pump
With power locked out and verified: insulation resistance of the motor and cable, continuity of each phase, and whether the shaft turns freely. A submersible is pulled to check the impeller. Rags around the impeller are the most common mechanical cause at a lift station.
What the motor sound tells you
| Observation | Likely cause |
|---|---|
| Silent, contactor does not pull in | Control circuit open or coil failed |
| Contactor pulls in, motor silent | Power circuit open on the load side, or motor cable open |
| Loud hum, no rotation, trips in seconds | Single phasing from a blown fuse or burned contact, or a seized pump |
| Starts and immediately trips the overload | Locked rotor from rags or a bearing, or a wrong overload setting |
| Drive runs, motor does not turn | Motor cable open, drive output phase lost, or the drive at zero speed reference |
| Starts, runs, stops after a set time | Failed-to-prove logic timing out on a missing run confirmation; check the auxiliary contact |
Common mistakes
- Resetting the overload or the drive fault and walking away. The overload tripped because the motor drew too much current; find out why.
- Replacing the contactor when the coil circuit is open. Measure at the coil first.
- Not checking the HAND position, and spending an hour in the program on a blown control fuse.
- Assuming the phase monitor is faulty because all three phases read on a meter. Phase monitors also trip on reversal, imbalance, and undervoltage, and a meter does not show sequence.
- Pulling a submersible pump before checking the panel. It is the most expensive step and often unnecessary.
Frequently asked questions
- The pump starts in HAND and the controller output is on, but it will not run in AUTO. What is left?
- The path between the controller output and the starter in the AUTO position: the output module channel, an interposing relay, the AUTO contact of the HOA, and the wiring. Measure at each. An output channel can be on in the program and dead on the terminal.
- The overload trips every time I reset it. Should I raise the setting?
- No. The overload is set from the motor nameplate full-load current, and a motor that trips a correctly set overload is drawing more than it should: locked rotor, rags, a failing bearing, single phasing, or a wrong voltage. Raising the setting turns a tripped overload into a burned motor.
- How do I know whether the drive is receiving the run command?
- The drive status display or the keypad shows the state of the digital inputs and, on a networked drive, the command word. If the drive shows ready and no run command, the problem is the source of the command. If it shows the run command and does not run, look at the enable, safe torque off, and fault status.
- What causes a pump to fail to start only occasionally?
- A marginal control circuit: a corroded HOA contact, an overload auxiliary that is intermittent, a loose terminal, a coil at the low end of its voltage tolerance on a long control run, or a float contact that only sometimes closes. Catch it with a trend of the call and the run confirmation, and measure while it is failing.
Related topics
- Hand-Off-Auto SelectorsWhat each position of an HOA selector does, how it is wired into the starter circuit, which protections must survive Hand, what the controller should see, and the mistakes that let a pump run with nobody watching.
- Outputs Not EnergizingThe program says the output is on and the equipment is not running. Where the signal gets lost between the output image and the field device, and how to find the point in a few measurements.
- Lift Station Lead/Lag ControlHow a duplex or triplex station decides when one pump is enough and when it is not: the setpoint ladder, cycle volume, the lag call, parallel pumping, and what to do when the lead pump fails.
- Interlocks and PermissivesA permissive lets you start. An interlock stops you. Confusing the two produces equipment that either will not run or will not protect itself.
- Pump Runs But No FlowThe motor turns and nothing moves. How to tell a clogged impeller from an air-bound pump, a closed valve, a stuck check, a broken coupling, or reverse rotation, using motor current and discharge pressure before pulling anything.
- Drive Will Not Start in AUTOThe drive runs from the keypad or in HAND but not from the controller. The command source, the enable and safe torque off inputs, the speed reference, and the network control word, checked in the order that finds the problem fastest.