Symptom
The DC OK indicator is off or flashing; the output reads zero, low, or pulses on and off; the supply is hot or its fan has stopped; controllers and I/O are dead or resetting; the supply hums or ticks.
The short answer
Power Supply Failure
A power supply that appears to have failed is more often overloaded: disconnect the output load and a supply that returns to voltage is being asked for more current than it has, by a short, a ground fault, or loads added over time, while a supply that stays dead or low with no load has failed. Supplies fail from heat, from the capacitors that age faster in a hot panel, from input voltage outside their range, from a cooling fan that stopped, from surges, and from a loose output terminal that arcs. The replacement is the same or an equivalent model sized from the load with margin, installed with the ventilation the manual requires, and the prevention is a cooler panel, a redundant pair where the load matters, a monitored DC OK contact, and a trend of the output current so that growth is seen before it becomes an outage.
Key points
- Disconnect the load: output returns, it is overloaded; output stays dead, it has failed.
- A supply that pulses on and off is in hiccup current limit; something on the output is drawing too much.
- Heat is what kills supplies; a hot panel halves their life.
- Replace with the same rating or larger, sized from the measured load with margin.
- Alarm the DC OK contact and trend the output current.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Short or ground fault on the output circuit | The supply cycles or sits in current limit; the output recovers with the load disconnected. Divide the DC branches to find the short. |
| Load grown beyond the rating | Output low under full load, correct at light load; loads added over years. Measure the total DC current against the rating. |
| Supply failed from heat and age | Output dead or low with no load; the supply has been in a hot panel for years. Replace it and address the heat. |
| Input voltage outside the range | The input measured against the supply nameplate; a supply on a 120 volt tap fed with 208, or a wide-range supply on a sagging generator. |
| Cooling fan failed on a fan-cooled supply | The fan stopped; the supply shuts down on temperature after a period of running. Replace the supply or the fan per the manual. |
| Surge or lightning damage | Failure after a storm; other devices damaged too. Replace; check the surge protection at the panel feed. |
| Loose or corroded output terminal | Voltage correct at the supply terminals and low or intermittent at the load; a warm terminal. Re-terminate. |
| Inrush of the load exceeding the supply startup capability | The supply will not start with the load connected but runs if the load is connected after it starts. A supply with more startup current or a soft-start on the load. |
The one test
- 1
Read the indicators
DC OK off, flashing, or a fault code; the output voltage on a meter; the input voltage.
- 2
Disconnect the load
Lift the output positive at the supply terminal, or open every DC branch breaker.
- 3
Read the output again
At voltage with no load: the supply is fine and the load is the problem. Dead or low with no load: the supply has failed.
- 4
If the load is the problem
Reconnect the branches one at a time, watching the output. The branch that pulls it down has the short, the ground fault, or the overload.
- 5
If the supply has failed
Check the input voltage and the panel temperature before installing the replacement, or the replacement will follow it.
What the behavior means
| Behavior | Meaning |
|---|---|
| Output pulses on and off, ticking | Hiccup current limit: a short or a heavy overload on the output |
| Output steady but low | Constant current limit: overload a little above the rating; or a supply degrading |
| Output correct, DC OK off | The DC OK threshold or the contact; or a supply reporting a fault such as temperature |
| Output dead, input present | Failed supply; or a fuse inside; or a fan-cooled supply shut down on temperature |
| Output dead, input absent | The input protection or the control power, not the supply |
| Output noisy, loads resetting | Capacitors aged; or a load injecting noise; or a loose connection |
| Will not start with the load, runs if load added later | Load inrush exceeds the supply startup capability |
Sizing the replacement
The replacement carries the measured load with margin: the sum of the steady currents of everything on the supply, plus the inrush of the largest load at startup, at no more than about two thirds of the supply rating so that the supply runs cool and has room. A supply of the same rating that failed because the load had grown will fail again; a supply run at its rating in a hot panel fails early. The panel drawing and the load list are updated with the new rating.
Preventing the next one
- A cooler panel: the heat calculation and the cooling fixed, since temperature is the main cause of supply failure.
- The supply mounted with the clearance and orientation the manual requires; supplies mounted sideways or stacked run hot.
- Surge protection at the panel feed and on long field circuits that the DC reaches.
- A load list on the drawing so that additions are checked against the rating.
- A replacement schedule for supplies in hot or critical panels before they fail, at the life the manufacturer states for the temperature.
Frequently asked questions
- The supply says 24 volts on its display but the controller is dead.
- Measure at the controller terminals. A loose output terminal, an open branch breaker, or a broken wire between the supply and the load leaves the supply happy and the load dead. The supply display is not the load.
- Can I replace it with a bigger supply?
- Yes, if the input circuit and the DC branch protection are still adequate, and it is often the right choice when the load has grown. The branch protection protects the wiring from the larger supply current, so check that the branch breakers and fuses still match the conductors.
- The new supply failed after a month. Why?
- The condition that killed the first one is still there: heat, an input voltage out of range, a load at the rating, a surge path, or a load that cycles the supply into current limit repeatedly. Measure the panel temperature and the load current before installing a third.
- Should the DC common be grounded?
- Either is permitted, and the plant should have one policy. A grounded common makes a positive-side ground fault trip the branch protection, which is obvious; an ungrounded common tolerates one fault and needs a monitor. Whatever the policy, a supply feeding a circuit that is grounded twice in different places is carrying ground current.
Related topics
- Panel Power SuppliesThe 24 V DC supply behind everything in a modern panel: sizing with real inrush and duty, single versus redundant with diode modules, how a switch-mode supply behaves under a short, distribution and fusing per branch, monitoring, and the failure modes that take out a whole panel at once.
- How to Size a Control Panel Power SupplyAdd up the real load, account for inrush and simultaneity, add headroom, and check the heat you just added to the enclosure.
- Panel OverheatingA panel that runs hot: drives tripping on temperature in the afternoon, controllers faulting in summer, components discolored, a fan that never stops. The causes from an undersized enclosure to a clogged filter, measuring the rise, and the fixes.
- Ground Fault PresentThe ground fault indicator is on, the monitor alarms, or a fuse opens when a field circuit is energized: how to find which conductor touches ground and where, by dividing the circuit with the monitor or an insulation tester, and where faults hide.
- Control Power SuppliesSizing the 24 VDC supplies that run a controller and its field devices, separating loads that should not share a supply, and keeping the controller alive through a power event.
- No Control Power in PanelThe panel is dead: no pilot lights, no controller, no HMI. The order of checks from the disconnect through the control transformer and its fuses, the control breaker, the emergency stop chain, and the DC supply, with the readings that locate the break.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.