Symptom
The controller resets or logs a power cycle; contactors drop out and reseal; drives fault on undervoltage; HMIs restart; pilot lights blink; it happens when a large motor starts, when the generator transfers, or at random, and the control power is present when anyone looks.
The short answer
Loss of Control Voltage
A momentary loss of control voltage is a sag or an interruption on the control circuit that lasts long enough for a controller to reset, a contactor to drop, or a drive to fault, and the source is found by recording the control voltage through the events and correlating them: utility sags when a large motor starts on the same feeder or in the neighborhood, transfer switch operations, a loose neutral or a corroded connection that drops under load, a control transformer overloaded so that its output sags when several coils pull in, a UPS that has silently gone to bypass or has a dead battery, or a power supply with too little hold-up. The fix is a control supply that rides through: a UPS for the controller and the communications, a constant voltage transformer or a DC supply with hold-up for the control circuit, DC coils on critical contactors, and repair of any loose connection found.
Key points
- Catch it with a recorder on the control voltage; the timing and depth of the sag name the source.
- Correlated with a motor start: a weak source or a shared feeder. With a transfer: the switch timing. At random: a loose connection.
- A control transformer that sags when coils pull in is overloaded.
- A UPS in bypass or with a dead battery passes every sag through; check it, do not assume it.
- Ride-through is the fix: UPS, constant voltage transformer, DC supply hold-up, DC coils.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Utility voltage sag when a large load starts | The recorder shows a sag of a few cycles to a second coinciding with a motor start on site or nearby. Compare the timing with the motor starts; check with the utility for events. |
| Transfer switch operation | The event coincides with a generator transfer or retransfer, or with the exercise timer. Read the transfer switch log. |
| Loose or corroded neutral or connection | Sags with load changes, worse with vibration or heat; a warm or discolored termination. Thermal scan under load; torque and clean. |
| Control transformer overloaded | The control voltage dips when several coils pull in together; the transformer is warm. Measure control current against the transformer rating; stagger coils; a larger transformer. |
| UPS in bypass, failed, or with a dead battery | The UPS status shows bypass or a battery fault; a pull of the input drops the load. Test it; replace the battery. |
| DC power supply with insufficient hold-up | The supply output drops during a sag that a better supply would ride through. Check the hold-up specification; use a supply with longer hold-up or a DC UPS. |
| Contactor coil inrush on a weak control source | The control bus dips as a large contactor pulls in. Record it; use DC coils or a separate control source for the big contactors. |
| Generator voltage regulation | Sags only on generator power when loads start. Check the regulator and the generator sizing. |
Catch it
A meter held on the control terminals shows the normal voltage, because the event lasts a few cycles and happened an hour ago. A power quality recorder or a logging meter set to capture minimum voltage with a timestamp, connected across the control circuit and left through the period when the events happen, shows the sag depth, its duration, and the time, and the time is compared with the pump start log, the transfer switch log, and the controller event log. The first recording usually names the source.
The pattern
| Recording shows | Likely source | Fix |
|---|---|---|
| Sag of a few cycles to a second at each large motor start | Motor inrush on a weak source or a shared feeder | Soft start or drive on the motor; separate control feed; ride-through for the controls |
| Interruption of seconds at generator transfer | Open-transition transfer switch; the generator start delay | UPS on the controls sized for the transfer; the transfer timing reviewed |
| Sags at random, worse under load or with heat | Loose or corroded connection, or a neutral problem | Thermal scan; re-terminate; check the neutral |
| Dips when several coils pull in | Control transformer overloaded | Larger transformer; stagger the coils; DC control |
| Every utility disturbance reaches the controls | UPS in bypass or dead | Test the UPS; replace the battery; alarm the UPS status |
| Sags only on generator | Generator regulation or sizing | Generator service; load sequencing on transfer |
Ride-through
- A UPS for the controller, the network switches, the radio, and the HMI, sized for the transfer time and a clean shutdown, with its status alarmed.
- A constant voltage transformer or a DC control supply with hold-up for the control circuit, so a sag of a few cycles does not drop the relays.
- DC coils, or AC coils with a hold-in circuit, on contactors that must not drop during a sag.
- Drives configured for undervoltage ride-through and a flying restart where the process allows, per the manual.
- The controller power supply with the longest hold-up the platform offers, and a power-fail input that lets the program handle a dip.
When it is the wiring
A loose neutral, a corroded connection at a transformer terminal, a breaker terminal that has lost its torque: each drops voltage under load and recovers when the load falls, and each heats. A thermal scan of the panel under load finds them, and re-terminating with the right torque fixes them. A neutral problem shows as a neutral-to-ground voltage that swings with load, which is its own page.
Frequently asked questions
- The controller resets once a week and the control voltage is always fine when I look.
- Because the sag lasted a fraction of a second. Read the controller event log for the reset times, then correlate with pump starts and the transfer switch exercise schedule. A recorder on the control circuit through the next week catches it.
- We have a UPS. How can the controls still lose power?
- The UPS may be in bypass after a fault, its battery may be dead, the controls may be on a receptacle that is not on the UPS output, or the sag may be on a circuit the UPS does not feed. Test the UPS by pulling its input with the load on it, and trace which loads it actually feeds.
- How deep a sag matters?
- Contactor coils drop out around two thirds to three quarters of rated voltage; controllers and supplies ride through brief sags and reset on deeper or longer ones per their hold-up; drives fault on undervoltage per their setting. A sag to 80 percent for a few cycles is survivable for most controls; one to 50 percent for half a second is not.
- Would a bigger control transformer fix the motor start sag?
- Only if the sag is the transformer itself under coil load. A sag caused by the motor pulling the line down reaches the transformer input and comes out the secondary; the fix for that is ride-through on the controls or a soft start on the motor.
Related topics
- Voltage Sag on Motor StartLights dim, contactors drop, and controllers reset every time the big pump starts: the starting current of an across-the-line motor pulling down a weak source. Measuring the sag, checking the source, and fixing it with a soft starter or ride-through.
- UPS Not Carrying LoadThe power failed and the controls went down anyway: a battery aged out or never connected, a UPS sitting in bypass since a fault, an overload, loads on the wrong receptacles, or a failed self-test nobody read. Finding out which, and testing properly.
- Generator Transfer ProblemsThe generator started and something still went wrong: no transfer, controls reset during the gap, drives faulted, pumps ran backward, or the retransfer caused a second outage. The sequence and its timers, neutral and rotation, and the monthly test.
- UPS for Control PanelsKeeping the controller, the radio, and the SCADA server alive through an outage: AC and DC UPS types, what to put on the UPS and what not to, sizing for runtime and inrush, the battery as a maintenance item, the alarms a UPS must provide, and what happens when the UPS is the thing that fails.
- High Neutral-to-Ground VoltageWhat a neutral-to-ground voltage reading means, the values that are normal, and the causes of a high one: a long or heavily loaded neutral, harmonic current, a loose or open neutral, a missing service bond, or an extra bond downstream, and telling them apart.
- Retentive Data LostThe plant came back from a power cycle with zero setpoints, zero totals, and the wrong pump as lead. Which backup failed, which restore overwrote what, and how to get the data back and keep it.